Contents · Technical Data

Contents · Technical Data

2

Description · Application

3

Installation Instructions

4

Circuit Diagram · Wiring Diagrams

5

Overview of Functions

6

Inspection and Maintenance

7

Order Details

8

Smoke detector with power supply, monitoring electronics, 
smoke alarm and air velocity monitor

Connection (plug socket) for diagnostic instrument

Push button “Test/Reset”

Green LED “System Monitoring”

Red LED “Alarm”

Yellow LED “Pollution Monitoring”

 

Blue LED “Air Velocity Monitoring”

Remote control terminal

Diagnostic instrument

Note:
Smoke detectors type RM-O-VS require maintenance
only once per year due to the increased safety
monitoring function.

Technical Data

– Supply voltage:  230 V, 50/60 Hz
– Power consumption:  max 25 VA
– Enclosure rating:  IP 42
– Permitted ambient temperature: + 10 °C to + 60 °C
– Permitted air velocity in ventilation duct:

1 m/s to 20 m/s

– Permitted relative humidity: 0 – 90 % relative humidity

(condensation and water vapour can cause false alarms)

– Warning limit for air flow: 

2 m/s

– Warning limit for high pollution: > 70 ± 10 units
– System monitoring: electric fault
– EMC: interference suppression to EN 60801-2 and 

60801-4

– Weight: 1,5 kg

Scope of Supply

Visual smoke alarm, power supply, switched relay, signal
lights (LED), pushbutton, remote control and diagnostic
instrument connection, electronic monitor, integrated in 
a plastic housing, wired ready for connection to snap
terminals, drilling template and fixing materials.

Available accessories:
– Diagnostic instrument type D-RM-O-VS to scan pollution

level, measurement range 0 to 100 units; hand held unit
with 1m long connecting lead and plug, battery supply 
9 V.

– Remote control terminal type T-RM-O-VS surface 

mounting or type T-RM-O-VS/1 panel mounting (size 
48 x 96 x 63) with LED’s for alarm, air flow, pollution and
system monitoring; plug socket connection for diagnostic
instrument type D-RM-O-VS and pushbutton for test/reset
function.

2

Smoke Detector

Type RM-0-VS

Terminal

Type T-RM-0-VS

Terminal

Type T-RM-0-VS/1

Diagnostic

Instrument

Type D-RM-0-VS

              

                 

Summary of Contents for RM-O-VS

Page 1: ...Smoke Detector Type RM O VS Approved by the German Institut f r Bautechnik 4 6 1 EN 3...

Page 2: ...y condensation and water vapour can cause false alarms Warning limit for air flow 2 m s Warning limit for high pollution 70 10 units System monitoring electric fault EMC interference suppression to EN...

Page 3: ...by an LED and closing relay contact The actual pollution value can be scanned directly at the smoke detector or on the remote control terminal using the diagnostic instrument Installation of a remote...

Page 4: ...r to replace the smoke alarm an inspection opening should be provided on the upper or lower side of the air duct Optional electrical connections mains connection and connection to control device of fi...

Page 5: ...trol device A on the fire damper to be controlled maximum switched power 250 V 10 A L1 Mains connection 230V 50 60 Hz L3 Control device connection volt free Switched power 250 V 10 A or 24 V 200 W L4...

Page 6: ...Velocity Monitoring Green LED System Monitoring Terminal Strip L9 6 5 Terminal Strip L9 4 3 Terminal Strip L9 2 1 Terminal Strip L3 2 3 1 Yellow LED Pollution Monitoring With air flow LED on Without a...

Page 7: ...rol devices on fire damper Response of smoke alarm to smoke aerosol e g cigarette smoke or smoke from smoke cartridge When the permitted concentration limit is exceeded the smoke alarm interrupts the...

Page 8: ...ution level on the smoke alarm sampling chamber and the system electronics maintenance once year Scope of supply see page 2 Order Example Make TROX Type RM O VS Quantity 5 RM O VS Order Code Descripti...

Reviews: