Description · Application

3

Description

The smoke detector works on the optical light scattering
principle and is used to monitor the ventilation duct in air
conditioning systems.  When used with a fire damper, it
prevents cold smoke with a temperature of 

72 °C from

propagating through the AC system.
In the function mode, the smoke alarm of the smoke 
detector is permanently flushed by the air flow in the duct
being monitored. If the smoke density exceeds a specific
concentration, the smoke alarm breaks the power circuit 
to the control device of the fire damper; and the damper 
closes. To ensure the specified function, the smoke detector
is also fitted with an air velocity sensor which monitors the
air flow in the immediate vicinity of the smoke alarm. A lack
of air flow, eg. caused by a closed damper or fan failure, is
signalled by an LED and opening relay contact.

The electrical safety circuits of the smoke detector are
constantly checked electronically and signalled on failure 
by an LED and closing relay contact. At the same time, the
opening of the alarm relay contact interrupts the control
circuit and the fire damper closes. To avoid false alarms 
due to pollution, the smoke alarm sampling chamber is
continuously monitored electronically. If a permitted threshold
of “> 70 ± 10 units” is exceeded, a signal is given by an LED
and closing relay contact.
The actual pollution value can be scanned directly at the
smoke detector or on the remote control terminal using the
diagnostic instrument.
Installation of a remote control terminal enables the electrical
function tests to be carried out from a central point, e.g. fire
control room.

Application

All fire dampers fitted with electric or electric/pneumatic
control devices which operate when voltage is removed may
be controlled via the smoke detector. 
This is recorded in the general building authority permits for
Trox fire damper.
The smoke detectors are marked with the U symbol in
accordance with the Approval Mark regulations in Germany.
The external verification prescribed by law is carried out by
VdS e.V, Cologne.

Smoke detector with 
power supply, monitoring 
electronics, smoke alarm 
and air velocity monitor

Remote control terminal

Diagnostic instrument

Fire damper

Spring return actuator

Central control point

Test

Rückstellung / 

Reset

Rauchauslöseeinrichtung
Typ RM-O-VS

>70%

v <2m/sec

Elektronik

Rauch /
Smoke

Schmutz /

Pollution

Luft /

Air

Betrieb / Operation

Gebrüder Trox GmbH
D-47504  Neukirchen-Vluyn 
Telefon 0 28 45/2 02-0
Telefax 0 28 45/20 22 65

Alarm / Störung / Failure

Anschluß

Diagnosegerät
Diagnostic link

Betrieb / Operation

Alarm / Störung / Failure

Rauch /
Smoke

Elektronik

Test / Rück-

stellung  

Reset

Anschluß

Diagnosegerät
Diagnostic link

Schmutz /

Pollution

Luft /

Air

>70%

v < 2m/sec

Terminal T-RM-O-VS zur
Rauchauslöseeinrichtung
RM-O-VS

15

Typ D-RM-0-VS

1

8

9

10

11

12

Airflow

v = 1-20 m/s

Summary of Contents for RM-O-VS

Page 1: ...Smoke Detector Type RM O VS Approved by the German Institut f r Bautechnik 4 6 1 EN 3...

Page 2: ...y condensation and water vapour can cause false alarms Warning limit for air flow 2 m s Warning limit for high pollution 70 10 units System monitoring electric fault EMC interference suppression to EN...

Page 3: ...by an LED and closing relay contact The actual pollution value can be scanned directly at the smoke detector or on the remote control terminal using the diagnostic instrument Installation of a remote...

Page 4: ...r to replace the smoke alarm an inspection opening should be provided on the upper or lower side of the air duct Optional electrical connections mains connection and connection to control device of fi...

Page 5: ...trol device A on the fire damper to be controlled maximum switched power 250 V 10 A L1 Mains connection 230V 50 60 Hz L3 Control device connection volt free Switched power 250 V 10 A or 24 V 200 W L4...

Page 6: ...Velocity Monitoring Green LED System Monitoring Terminal Strip L9 6 5 Terminal Strip L9 4 3 Terminal Strip L9 2 1 Terminal Strip L3 2 3 1 Yellow LED Pollution Monitoring With air flow LED on Without a...

Page 7: ...rol devices on fire damper Response of smoke alarm to smoke aerosol e g cigarette smoke or smoke from smoke cartridge When the permitted concentration limit is exceeded the smoke alarm interrupts the...

Page 8: ...ution level on the smoke alarm sampling chamber and the system electronics maintenance once year Scope of supply see page 2 Order Example Make TROX Type RM O VS Quantity 5 RM O VS Order Code Descripti...