Installation manual for automatic extract air valve

6

4.  product description

Functional description

The automatic extract air valve HFA works with two volume 
flow rates:

Basic volume flow rate

When the room to be ventilated is not in use, the damper 
remains closed and only the basic volume flow rate V0 is 
extracted. This basic volume flow rate V0 can be increased by 
breaking out one or more plastic plugs in the damper.

Required volume flow rate

When the room to be ventilated is in use and the electro-ther-
mal damper actuator is activated by a switch contact typical 
for this room, e.g. a light switch, the damper opens to the set 
damper limit A, B, C or D in approx. 2-3 minutes. The volume 
flow rate is thereby increased to the volume required. Once the 
switch contact is interrupted, the damper remains open for ap-
prox. 5-10 minutes to ensure proper follow-up ventilation. The 
damper then returns to its initial position and only the previous-
ly selected basic volume flow rate is extracted.

Dimensions

Special features of the HFA

-  Depending on the building, heating energy
  can be reduced by 10 – 30%  

 

  in terms of total consumption.
-  The heating system can be designed to smaller dimensions.
-  The automatic extract air valve HFA is suitable for use in all 
buildings with  

 

  central extract air systems.
-  The automatic extract air valve HFA works with two volume 
flow rates:

  Basic volume flow rate       (can be selected)

  Required volume flow rate    (can be set)

-  If required, the damper opens via an electro- 

 

  thermal actuator with an automatic delay (2-3 min.)
-  To prevent contamination of the exhaust duct, there is 
     a fitted filter pad that can be easily replaced (commercially 
available  

 

 filter).
-  Assembly of the automatic extract air valve HFA is simple.

1

2

240

Ø 103

~52

5

163

~84

7

8

9

10

Ø 10

(13.5)

84

(97.5)

52

65.5

13.5

4

6

35

Ø 22

150

115

55

(35)

(90)

75

44

11

Typ: 

HFA / ATVC / TKR

Volt: 

230~

Watt: 

8 (60)

AB       CD

IP54

12

 

1

  Main housing 

 

2

 Cover 

 

4

  Cable penetration (for flush mounting) 

 

5

  Cable feed-through (for surface mounting) 

 

6

  Electrical socket 

 

7

   Fixing holes 

 

8

   Junction box 

 

9

  Electro-thermal actuator 

10

   Damper with volume flow rate plugs 

12

 Pressure  tap

1

2

240

Ø 103

~52

5

163

~84

7

8

9

10

Ø 10

(13.5)

84

(97.5)

52

65.5

13.5

4

6

35

Ø 22

150

115

55

(35)

(90)

75

44

11

Typ: 

HFA / ATVC / TKR

Volt: 

230~

Watt: 

8 (60)

AB       CD

IP54

12

Summary of Contents for HESCO HFA

Page 1: ...Installation manual Automatic extract air valve Type HFA Subject to change All rights reserved L 50 6 01e ...

Page 2: ...HFA 9 9 Maintenance 10 Maintenance and cleaning 10 1 General information This installation manual describes the automatic extract air valve type HFA To ensure correct functioning of the automatic extract air valve it is essential to read the provided installation manual before starting any work and to comply with it The manufacturer does not accept any liability for any malfunction or damage resul...

Page 3: ...erden in Ex Bereichen im Freien ohne ausreichenden Schutz gegen Witterungseinflüsse in Atmosphären die planmässig oder ausserplan mässig aufgrund chemischer Reaktionen eine schädigende und oder Korrosion verursachende Wirkung auf das Produkt ausüben WARNUNG Verletzungsgefahr bei unzureichender Qualifikation Unsachgemässer Umgang kann zu erheblichen Personen und Sachschäden führen Alle Tätigkeiten ...

Page 4: ...ing knowledge and actual experience to enable them to carry out their assigned duties understand any potential hazards related to the work under consideration and recognise and avoid any risks involved Limitation of liability The information in this manual has been compiled with refe rence to the applicable standards and guidelines the state of the art and our expertise and experience of many year...

Page 5: ...e transported to the installation location in their original packaging Use only lifting and transport gear designed for the required load Always secure the load against tipping and falling Cumbersome equipment should be transported with at least two people to prevent injury and damage Storage Please note Store the product only in its original packaging Protect the product from the effects of weath...

Page 6: ...epending on the building heating energy can be reduced by 10 30 in terms of total consumption The heating system can be designed to smaller dimensions The automatic extract air valve HFA is suitable for use in all buildings with central extract air systems The automatic extract air valve HFA works with two volume flow rates Basic volume flow rate can be selected Required volume flow rate can be se...

Page 7: ...3 Snap fastener 4 Cable penetration for flush mounting 5 Cable feed through for surface mounting 6 Electrical socket 7 Fixing holes Ø10 8 Junction box 9 Electro thermal actuator 10 Damper with volume flow rate plugs 11 4 plastic dowels Nr 5 x 25 12 4 washers Ø4 3 x 14 13 4 cross head screws Ø3 5 x 32 Installation Opening the cover Press the snap fastener and lift the cover out of the main housing ...

Page 8: ... the mains after installation unless the unit is equipped with a switch to 24 3 This can be done by making the plug accessible or by fitting a switch into the fixed installation in compliance with the installa tion regulations Connection diagram P Phase N Neutral E Earth Note The automatic extract air valve can be controlled with a separate switch or coupled with the light switch 75 44 2 1 Ø 100 1...

Page 9: ...l p s Pa Grundvolumenstrom o Volumenstrom m h 0 1 2 3 4 50 dB A 45 dB A 40 dB A 35 dB A 30 dB A 400 300 200 100 80 60 50 40 30 20 6 8 10 20 30 50 100 150 LwA HFA 200 ps Perte de charge statique p s Pa Débit d air de base o Débit d air m h 0 1 2 3 4 50 dB A 45 dB A 40 dB A 35 dB A 30 dB A 400 300 200 100 80 60 50 40 30 20 6 8 10 20 30 50 100 150 LwA HFA 200 ps p s Pa Base air volumen rate o 0 1 2 3...

Page 10: ... die Versorgungs spannung ausschalten Maintenance and cleaning Please note Clean surfaces with a damp cloth Only use commercially available non corrosive cleaning agents Do not use cleaning agents that contain chlorine The use of cleaning tools for removing persistent contamination e g scrubbing sponges and scouring agents can damage the surface and is not permitted Contaminated filter elements ne...

Reviews: