12 TX9165-UM-EN-07
1.6 Electrical Details
Description
Mining Ex
General Purpose
Supply voltage
12 V dc (+/- 10%)
24 V dc (+/- 10%)/
85 to 265 V ac
Supply current
200 mA (maximum loading including one pellistor eModule)
Output relays
Four independent alarms relays each programmable to any
alarm setpoint on any monitoring channel for preferred alarm
priority grouping
Relay contacts
One changeover contact on each relay
Contact rating
Suitable for, and clearance
compatible for, intrinsically
safe circuits
2 Amps 230 V ac