where to install the unit

The UV unit should be installed after all other water
conditioning equipment.  Mount the unit to a wall or
braced frame using the mounting tabs.  Install a bypass
with unions.

Install the UV treatment unit  in a sheltered area with
ample ventilation. Ambient temperatures surrounding
the unit should be between 35

o

F (2

o

C) and 110

o

F (43

o

C).

Should your requirements differ, contact the factory for
assistance.

As an ultraviolet UV treatment unit does not introduce
any chemical residue within the water, it is desirable to
install the unit as close as possible to the point of use in
order to avoid potential recontamination by discharge
pipes, fittings, etc. The base of the UV treatment unit
should be mounted on suitable support to avoid undue
strain on the unit or your related pipes and fittings.

The UV unit should be installed after all other water
conditioning equipment and as close to the end point of
use as possible. For example, it should not be installed
in a remote well house; it should be installed at the
house. If filtration or other water treatment equipment is
installed, the UV unit must be installed after all such
equipment.

how to protect your unit

The location should be free from undue vibration which
could be caused by proximity to heavy equipment and
erratic or improper pumps. Excessive vibration will
damage internal electrical components and cause
premature failure of the UV lamps.

If your piping system is subject to impulse pressure
resulting in a “water hammer” condition, a surge tank or
other means must be provided to remove this condition,
otherwise the extreme momentary pressure may rupture
and fracture the quartz sleeves.

operating pressure

Standard units are rated for a maximum operating
pressure of 120 psig (8.3 bar).

A parts check list was included when
this unit was shipped. Please refer to
this list and note that some parts are
small and can be easily overlooked
when discarding packaging.

DW-8 installation

Allow 40” (102cm) service access clearance on the inlet
side and 12”  (31cm) on the outlet side clearance on the
opposite end of  the unit. For the DW-8 DE unit, a
minimum of 2 feet clearance is required below the
bottom of the unit to operate the drain valve (supplied
by others).

If vertical installation is required due to lack of horizon-
tal access space, the inlet water connection
must be at the bottom.

DW-5 installation

Allow 16” (41 cm) service access clearance on both
ends of the unit.

If vertical installation is required due to lack of horizon-
tal access space, the inlet water connection
must be at the bottom.

grounding

It is imperative that the unit be properly grounded for
safe and proper operation.

Failure to properly ground the UV unit automatically
voids the equipment warranty.

Line voltage to the UV unit must be stable.  Performance
will be reduced should incoming line voltage drop more
than 5% from the rated voltage as indicated on the

nameplate decal on the unit.

Summary of Contents for Aquafine DW Series

Page 1: ...perated Aquafine ultraviolet treatment units will provide many years of service DW Series Installation Maintenance and Operation Manual Part No 109 1 This manual covers the preliminary installation op...

Page 2: ......

Page 3: ...Quartz Sleeves 9 10 Installing the Ultraviolet UV Lamps 11 12 Powering Up the Ultraviolet UV Unit 13 Monitoring Devices Lamps Operational Viewport 14 Maintenance Requirements 15 Cleaning the Unit 15...

Page 4: ...l codes 5 Properly ground the unit Failure to comply may result in severe or fatal electrical shock 6 Install the unit away from undue vibration that can damage the electrical components and UV lamps...

Page 5: ...5 Pretreating the water with appropriate filtration and or other devices may be necessary to bring the water quality up to acceptable UV transmission levels Only then should you install and operate th...

Page 6: ...warranty pleasefilloutand mailtheWarrantyRegistrationCardintheback pocketofthismanualandreturntoAquafineCustomer Service The following installation and operating conditions are considered hazardous or...

Page 7: ...our option and returned to sender prepaid Before returning any part contact Aquafine Corporation for return authorization and shipping instructions This guarantee is void if the equipment has not bee...

Page 8: ...cal components and cause premature failure of the UV lamps If your piping system is subject to impulse pressure resulting in a water hammer condition a surge tank or other means must be provided to re...

Page 9: ...aps to isolate any such susceptible material from direct exposure to the ultraviolet light Install the UV light traps to the inlet outlet of the UV treatment chamber prior to the connec tion of any no...

Page 10: ...wly push the sleeve through the chamber 8 Assemble the compression nut and o ring Place the o ring into the internal relief of the compression nut below the threaded area The o ring should fit into th...

Page 11: ...emble the compression nut and o ring Place the o ring into the internal relief of the compression nut below the threaded area The o ring should fit into the com pression nut 9 Place the compression nu...

Page 12: ...ion nut This ensures the lamp is secure within the chamber 8 The lamp pins must be pushed down to fit securely in the lamp socket connector 9 Screw the lamp socket retainer cap clockwise into place ov...

Page 13: ...e hand push the lamp socket boot onto the end of the ultraviolet lamp and connect the opposite lamp socket When properly attached a slight snap can be felt which indicates a proper connection Verify n...

Page 14: ...til a strong chlorine odor is detectable Leave this solution in all lines for at least four hours before purging Before flushing lines proceed to the next step since UV treated water must be used to r...

Page 15: ...p failure buzzer option For single ended units only The buzzer is an optional accessory that is activated when the UV lamp fails to operate Upon such condi tion the LED indicator will automatically tu...

Page 16: ...ays after use to see if any debris or film has settled on the outside If dirty follow these cleaning procedures 1 Turn off the main water to the unit 2 Disconnect the electrical power to the unit 3 Re...

Page 17: ...ballast by pulling it towards you Discard the old or defective ballast 6 Install the new ballast securing it with the bolt removed earlier 7 Tighten the bolt with 5 32 L shaped hex wrench 8 Reconnect...

Page 18: ...spillage 3 After the valve has been left fully open for three and one half minutes reduce the flow to a reasonable stream of water not less than 50 of full flow Continue flowing to drain three additi...

Page 19: ...18517 DW 5 Parts 1 Ballast 120 Volt 18855 2 UV lamps standard SE 254 mauve 19306 3 Quartz sleeves domed 19330 DW 8Single Ended SE Parts 1 UV lamps standard SE 254 mauve 17491 2 Quartz sleeves domed 1...

Reviews: