background image

18

NOTE:

 

In normal use, it is in order to leave the 

water supply permanently on to the shower 
unit, but as with most electrical appliances,

 the 

unit 

MUST

 be switched off at the isolating 

switch when not in use.

10

Continued

SECTION

OPERATING FUNCTIONS

Power on indicator 

(fig.20)

When the electricity supply to the shower is 
switched on at the isolating switch, the neon in 
the START/STOP button will illuminate.

TP – Temperature Protection

During normal operation if the temperature 
exceeds the showering safety limit the power 
to the elements will be removed completely, 
although water will continue to flow. When the 
temperature has cooled sufficiently, power to the 
elements will be automatically restored to the 
settings at the time of interruption.

Abnormal Safety cut-out

The unit is fitted with a non-resettable thermal 
cut-out safety device. In the event of abnormal 
operation which could cause unsafe temperatures 
within the unit, the device will disconnect the 
heating elements. It will require a visit from a 
qualified engineer to determine the nature of the 
fault and replace the safety device, once the unit 
has been repaired.

Low pressure indicator

If this indicator is on, this means the water 
pressure has fallen below the minimum required 
for correct operation of the shower, resulting in 
the low pressure cut-out operating. This switches 
off power to the heating elements preventing any 
undue temperature rises (water will continue to 
flow). Power will automatically be restored when 
adequate water pressure returns.

Power ‘on’ 

indicator

Fig.20

Low pressure 

indicator

Summary of Contents for T80 Easi-fit

Page 1: ... electric shower 2181509A Nov 2016 Patents Pending GB 2489547 GB 2495343 Patent GB 2481878 EC Registered Design No 001902388 0005 to 0007 The showerhead and hose supplied with this product are an integral part of the safety of your shower Failure to use genuine Triton parts may cause injury and will invalidate your warranty ...

Page 2: ...icles 2 PLUMBING 2 1 The plumbing installation must comply with Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806 2 2 The supply pipe must be flushed to clear debris before connecting to the shower unit 2 3 DO NOT solder pipes or fittings within 300mm of the shower unit as heat ca...

Page 3: ... pipes or fittings within 300mm of the shower unit as heat can transfer along the pipework and damage components 2 4 DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can 2 5 DO NOT use excessive force when making connections to the flexible hose or showerhead finger tight is sufficient 2 6 All plumbing connections must be completed before making the electrical...

Page 4: ...shower is in use If pressure drops appreciably below the minimum the heating elements will automatically cut out NOTE If ever the water becomes too hot and you cannot obtain cooler water first check that the sprayplate in the showerhead has not become blocked DO NOT place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the cover and backplate AD...

Page 5: ...NERAL ADVICE TO USERS CLEANING ADVICE SPECIFICATIONS 2 DIMENSIONS CABLE WATER ENTRY POINTS 3 ELECTRICAL REQUIREMENTS 4 5 INSTALLING THE SHOWER 6 14 Siting of the shower 6 7 Plumbing installation 8 Electrical installation 9 Fit to the wall connect shower supplies 9 13 Fitting the cover 13 14 COMMISSIONING PROCEDURE 15 USER OPERATING INSTRUCTIONS 16 18 Operating functions 18 Cleaning the filter inst...

Page 6: ...ximum static pressure 1000 kPa 10 bar Maximum inlet temperature 28 C Minimum inlet temperature 2 C Inlet connection 15mm diameter Outlet connection BSP male thread MATERIALS ABS Backplate cover controls showerhead Acetal Sprayplate Minerally insulated corrosion resistant metal sheathing Elements STANDARDS and APPROVALS Splashproof rating IPX4 Safety Complies with the requirements of current Britis...

Page 7: ...mm ENTRY POINTS DIMENSIONS WATER Left Bottom Back Top Side Right Bottom Back Top Side CABLE Left Bottom Back Top Right Bottom Back Top Back Back Others Others 334mm PLEASE NOTE Deviation from the approved entry points will invalidate product specifications and warranty ...

Page 8: ...f in any doubt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket outlet lighting circuit or cooker circuit 3 1 The electrical supply must be adequate for the loading of the unit and existing circuits 4 Check your consumer unit main fuse box ha...

Page 9: ...ng in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those rooms must be protected by a 30mA RCD 8 The current carrying capacity of the cable must be at least that of the shower circuit protection see Table B 8 1 To obtain full advantage of the power provided b...

Page 10: ...o achieve optimum performance from the unit throughout the year During periods of high ambient temperatures it may be necessary to select the economy power setting to achieve your preferred shower temperature Fig 5 shows a typical system layout NOTE The control knobs are an integral part of the cover Do not attempt to remove them Lift the cover from the backplate and remove the trimplate page 21 i...

Page 11: ...wer hose or a blocked showerhead This may cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose Failure to follow this procedure may cause the PRD to operate Make sure the shower is positioned over a bath or shower tray If the PRD operates then water will eject from the bottom of the unit Should this happen turn off the electricity and water supplies to ...

Page 12: ...he surface of the wall This area MUST be left clear when plastering and tiling around the pipework in order to make the nut accessible for future adjustments NOTE An additional stopvalve complying with Water Regulations must be fitted in the mains water supply to the shower as an independent means of isolating the water supply should maintenance or servicing be necessary IMPORTANT Before completin...

Page 13: ... INSTALLATION NOTE Deviations from the designated entry points will invalidate product approvals The cable entry points are listed on page 3 Seal around rear entry cable to prevent water ingress into the wall FIT TO THE WALL CONNECT THE SHOWER SUPPLIES The water inlet has been designed to allow left or right fitting fig 8 decide the inlet direction and then turn the inlet either left or right 6 ch...

Page 14: ...build house After choosing the site for the shower use the fitting template supplied to mark the two fixing holes and establish pipe and electric entry points Fitting Procedure replacing an existing shower Turn off water supply either at the mains stopvalve or the isolating stopvalve Temporarily connect the mains water supply to the inlet of the shower using a 15mm x 15mm compression fitting Use t...

Page 15: ...een completed Connect the mains water supply to the inlet DO NOT use excessive force when making the connection Make sure the backplate is square on the wall and tighten the retaining screws which hold it to the wall Turn on the mains water supply and check for leaks in the pipework connection to the shower NOTE At this stage no water can flow through the unit IMPORTANT A suitable sealant should a...

Page 16: ...taining screw back through the Terminal block to secure it 7 Continued SECTION 3 2 1 Fig 11 Terminal block in right hand entry position Earth terminal 2 Earth terminal 1 DO NOT DISCONNECT THE TOP WIRES Install the Earth cable to Earth terminal 1 or 2 to match the left or right Terminal block position Route the cable into the shower unit for connection to the terminal block as follows Earth cable t...

Page 17: ...the correct control knob position when replacing the cover Clip the neon into the back of the Start Stop assembly on the inside of the cover Check to ensure that the wiring is not trapped and replace the cover squarely to the backplate and guide into position so that the knobs locate correctly into the splined spindles Should any difficulty arise recheck the points above While applying slight pres...

Page 18: ...t it goes to Maximum HOT fig 16 Fig 16 FITTING THE COVER continued Figures 13 14 15 and 16 show the correct control knob position when replacing the cover Fig 13 Flat section to left hand side B With the cover off the shower turn the stabi liser valve spindle fully clockwise until resistance is felt fig 14 Fig 14 Stabiliser valve C With the cover off the shower turn the power selector to the COLD ...

Page 19: ...isolating switch 3 Press the Start Stop button fig 17 and wait until water starts to flow from the flexible hose 4 Slowly rotate the temperature control fully anti clockwise to the MAXIMUM flow position fig 18 It will take about thirty seconds for a smooth flow of water to be obtained while air and any debris is flushed from the shower When a smooth flow of water is obtained rotate the temperature...

Page 20: ...rt Stop button COOLER Fig 19 HOTTER To use the power selector The power selector has three positions COLD ECONOMY and HIGH Cold setting single blue line Cold the cold setting does not provide any heat from the heater can to the incoming water Economy setting single red line Economy uses only one of the elements within the heater can NOTE If the stated flow rate required for the unit cannot be met ...

Page 21: ...will give a different temperature to the same position on HIGH To decrease the shower temperature Turn the temperature control anti clockwise this will increase the flow of water through the shower and make the water colder To increase the shower temperature Turn the temperature control clockwise this will decrease the flow of water through the shower and make the water hotter NOTE It is advisable...

Page 22: ...atically restored to the settings at the time of interruption Abnormal Safety cut out The unit is fitted with a non resettable thermal cut out safety device In the event of abnormal operation which could cause unsafe temperatures within the unit the device will disconnect the heating elements It will require a visit from a qualified engineer to determine the nature of the fault and replace the saf...

Page 23: ...alve The inlet filter is situated inside the water inlet fitting fig 21 To gain access to the filter remove the cover and bottom left trimplate Unscrew the filter cap from the bottom of the inlet pipe Inspect the O ring for damage when the filter cap is removed When cleaning the filter DO NOT use a sharp object as it will cause damage It is preferable to use an old toothbrush or similar To reassem...

Page 24: ...trol 2 1 2 Blocked showerhead clean or replace blocked sprayplate in showerhead 2 2 1 Check if stop valves are fully open Check if a blockage in the inlet filter 2 3 1 Readjust flow rate to give increased flow 2 3 2 Select ECONOMY power 3 1 1 See Water too hot causes 2 1 2 2 and 2 3 and their appropriate action cures If it continues contact Triton Customer Service 4 1 1 Reduce flow rate via temper...

Page 25: ...operated Have the unit checked by a suitably qualified engineer or contact Customer Service 5 1 1 Wait until the water pressure resumes to normal 6 1 1 Clean or replace blocked sprayplate in showerhead and then fit new PRD 6 2 1 Check for free passage through hose Replace the hose if necessary and fit new PRD 6 3 1 Fit new PRD Commission unit with showerhead removed 7 1 1 Replace start stop switch...

Page 26: ...22 SPARE PARTS 1 1 2 2 5 5 7 7 6 6 9 11 11 3 3 4 4 8 8 10 10 12 13 12 14 13 15 14 15 16 Images are for reference only due to continual development supplied spares may have modified appearance 9 ...

Page 27: ...ly P22611001 5 Pressure Switch Module P22611003 6 Trimplate 7054303 7 Terminal Block and Wires S82201190 8 Outlet Pipe Assembly S85000260 9 Micro switch set of 2 83314900 10 Thermal Cut Out TCO 22012340 11 Stabiliser Valve P22640800 12 Solenoid Valve P22610801 13 Pipe Trims Top Left 7054305 14 Pipe Trims Top Right 7054307 15 Pressure Relief Device 82800450 16 Cover Assembly P80000091 Neon Assembly...

Page 28: ...24 ...

Page 29: ...25 ...

Page 30: ...nder the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659 All our electric products are labelled accordingly with the crossed out wheeled bin symbol This indicates for disposal purposes at end of life that these products must be taken to a recognised collection points such as local authority sit...

Page 31: ...r switch OFF 2 To start the shower press the Start Stop button COLD ECONOMY HIGH HOT COLD HOT COLD HOT COLD HOTTER slower flow COLDER faster flow C O L D HOT COLD 0 1 2 HEATER ELEMENTS USED HEATER ELEMENTS USED NONE OF THE ELEMENTS USED 0 1 2 1 OF THE ELEMENTS USED HEATER ELEMENTS USED 2 OF THE ELEMENTS USED 0 1 2 H O T HOT COLD To START or STOP your shower To alter the FLOW and Temperature of you...

Page 32: ...duct is no longer covered by the guarantee an up front fixed fee will be charged before the site visit 8 Should proof of purchase not be available on an in guarantee call or should the service engineer find that the product is no longer under guarantee the engineer will charge the same fixed price and the customer will be expected to pay the engineer before he leaves If payment is not made on the ...

Reviews: