Site survey
A qualified engineer must survey the
installation site to determine the
correct ground preparation for the size
and weight of the RTM-75kW user unit, in
accordance with local regulations.
The RTM-75kW user unit is best
installed following the recommended site
configuration requirements.
Ground fixing
The RTM-75kW user unit is to be fixed to
the ground through the baseplate
fixing holes with 4 x M16 fasteners.
Fasteners are not supplied, because the
type required depends on the foundation
used and must be chosen by the installer
accordingly.
The fasteners should fix the RTM-75kW
user unit securely to the foundation
through the baseplate in accordance with
the dimensions and fixing points shown in
Base plate dimensions.
Note:
Keep the plastic inserts from the
bolts for use in the baseplate holes.
Conduit requirement
Up to Ø 110mm OD conduit maximum.
Ø50 and Ø25mm conduit standard.
Foundation requirements
The foundation must be flat, even, and
have the appropriate density for the
weight of the user unit.
Check the flatness and level of the
foundation and level of the RTM-75kW
user unit baseplate prior to fixing.
Communications
Wired ethernet or 3G/4G network
capability.
Power supply
The RTM-75kW user unit is designed to
accommodate input wiring from either an
underground foundation or above ground.
High power (HP) input wiring
High power input wiring can be provided
to the charger in three different
scenarios:
1. A single multi-conductor cable
Ø27-38mm to suit the supplied M50
cable gland.
2. Running the wiring in a 50mm conduit
and installing using the provided M50
conduit adaptor and seal.
3. Individual wires can be used with the
provided alternate gland plate and 4x
M32 cable glands. Each individual cable
must be Ø13-18mm.
Auxiliary field wiring
The auxiliary field wire must be a single
multi-conductor cable Ø10 - 14mm, to
use the supplied M25 cable gland.
If the auxiliary wire is smaller than Ø10
the 25mm conduit installation must be
used.
CRITICAL
It is critical to product safety and
warranty that IP65 is achieved for
all input wiring.