3

Basic Operation 

(Front Panel)

“ON/OFF” Button

To turn the UPS on:

Press and hold the ON/OFF Button for one 

second.* If utility power is absent, pressing the Button will “cold-
start” the UPS, i.e. turn it on and supply power from its battery.** 

To turn the UPS off:

Press and hold the ON/OFF Button for one

second.* The UPS will be turned completely off (deactivated).

* The alarm will beep once briefly after one second has passed. ** Providing runtime
proportionate to the UPS battery's level of charge.

“MUTE/TEST” Button

To Silence (or "Mute") UPS Alarms:

briefly press and release 

the MUTE/TEST button. Note: continuous alarms (warning 
you to immediately shut down connected equipment) cannot be 
silenced.

To Run a Self-Test:

with your UPS plugged in and turned on, 

press and hold the MUTE/TEST button for two seconds. 
Continue holding the button until the alarm beeps several times 
and the UPS performs a self-test. See “Results of a Self-Test” 
below. Note: you can leave connected equipment on during a self-
test.

CAUTION! Do not unplug your UPS to test its battery. This
will remove safe electrical grounding and may introduce a
damaging surge into your network connections.

Results of a Self-Test:

The test will last approximately 10 seconds

as the UPS switches to battery to test its load capacity and charge.
All LCD Display icons will be illuminated and the UPS alarm will
sound.

• If the “FAULT” icon remains lit and the alarm continues to 

sound after the test, the battery-supported outlets are overloaded. 
To clear the overload, unplug some of your equipment from the 
battery-supported outlets and run the self-test repeatedly until 
the “FAULT” icon is no longer lit and the alarm is no longer 
sounding.

CAUTION! Any overload that is not corrected by the user
immediately following a self-test may cause the UPS to shut 
down and cease supplying output power in the event of a
blackout or brownout.

• If the “REPLACE” icon remains lit and the alarm continues to 

sound after the test, the UPS batteries need to be recharged 
or replaced. Allow the UPS to recharge continuously for 24 
hours, and repeat the self-test. If the icon continues to 
illuminate after repeated self tests, contact Tripp Lite for service. 
Battery replacement should only be performed by 
qualified service personnel. If the UPS requires battery 
replacement, Tripp Lite offers a complete line of replacement 
batteries at www.tripplite.com.

LCD Display

The LCD Display indicates a variety of UPS operational
conditions. All descriptions apply when the UPS is plugged into an
AC outlet and turned on. The LCD Display can be rotated for easy
viewing, regardless of whether the UPS is in a horizontal or vertical
(“tower”) position. To rotate the display: insert a small tool in the
slots on the sides of the display to pop it out of the UPS housing;
rotate the display, and snap it back into the UPS housing.

3a) “INPUT VOLTAGE” Meter:

This meter measures, in real

time, the AC voltage that the UPS system is receiving from the
utility wall outlet. Although the Meter may occasionally display
input voltages which stray (due to poor quality utility service)
outside the range of standard computer tolerance, rest assured that
the UPS is designed (through the use of automatic voltage
regulation) to continuously supply connected equipment with
stable, computer-grade output voltage. In the event of a blackout
(power loss), severe brownout (low power) or overvoltage (high
power), the UPS will rely on its internal battery to supply
computer-grade output voltage. The Input Voltage Meter can be
used as a diagnostic tool to identify poor quality input power. By
plugging the UPS into different outlets within a facility, you can
identify individual circuits that are consistently providing low
power, which can be caused by the combined equipment load
demanding more power than the circuit is designed to supply. If
all circuits within a facility consistently provide low power, the
facility may be served by inadequate utility service or may be in an
industrial or commercial area with an overburdened power grid.

3b) “BATTERY CAPACITY” Meter:

This meter displays the

approximate charge level (in 20% increments) of the UPS's
internal battery. During a blackout or severe brownout, the UPS
will switch to battery power, the “ON BAT” icon will be
illuminated, and the charge level will deplete.

3c) “AVR” (Automatic Voltage Regulation) Icon:

This icon will

illuminate whenever your UPS is automatically correcting low AC line
voltage without depleting battery power. This is a normal, automatic
operation of your UPS, and no action is required on your part.

3d) “REPLACE” (Battery Recharge/Replace) Icon:

This icon

will illuminate and an alarm will sound after a self-test to indicate
the UPS battery needs to be recharged or replaced. Allow the UPS
to recharge continuously for 24 hours, and repeat the self-test. If the
icon continues to illuminate, contact Tripp Lite for service. Battery
replacement should only be performed by qualified service
personnel. If the UPS requires battery replacement, Tripp Lite
offers a complete line of replacement batteries at www.tripplite.com.

3e) “ON BAT” (On Battery) Icon:

During a severe brownout or

blackout, this icon illuminates and an alarm sounds (4 short beeps
followed by a pause) to indicate the UPS is operating from its
internal batteries. Monitor the “Battery Capacity” Meter to
determine the approximate battery charge level available to
support equipment. During a prolonged brownout or blackout, the
alarm will sound continuously (and the “BATTERY CAPACITY”
Meter will show one 20% capacity segment shaded) to indicate
the UPS's batteries are nearly out of power; you should save files
and shut down your equipment immediately.

3f) “FAULT” Icon:

This icon will illuminate and an alarm will

sound after a self-test to indicate the battery-supported outlets are
overloaded. To clear the overload, unplug some of your
equipment from the battery-supported outlets and run the self-test
repeatedly until the icon is no longer illuminated and the alarm is
no longer sounding.

CAUTION! Any overload that is not corrected by the user
immediately following a self-test may cause the UPS to shut
down and cease supplying output power in the event of a
blackout or brownout.

ON/OFF Button

MUTE/TEST Button

1

2

LCD Display

3

3a

3b

3c

3d

3e

3f

1

2

3

Summary of Contents for SMX1000LCD

Page 1: ...Источники бесперебойного питания Tripplite SmartPro 1000VA LCD SMX1000LCD Инструкция пользователя ...

Page 2: ...ns 1111 W 35th Street Chicago IL 60609 USA 773 869 1234 www tripplite com Copyright 2005 Tripp Lite All rights reserved Important Safety Instructions Quick Installation Basic Operation Front Panel Basic Operation Rear Panel Storage Service 3 4 4 2 2 Español Français Póññêèé 5 9 13 ...

Page 3: ...on CAUTION The UPS must be plugged into a live AC outlet and turned on for 24 hours after initial installation to fully charge the UPS s internal battery Your connected equipment will receive utility supplied AC power if present immediately after the UPS is plugged in and turned on however your connected equipment may not receive full battery backup in the event of a blackout or severe brownout un...

Page 4: ...hich stray due to poor quality utility service outside the range of standard computer tolerance rest assured that the UPS is designed through the use of automatic voltage regulation to continuously supply connected equipment with stable computer grade output voltage In the event of a blackout power loss severe brownout low power or overvoltage high power the UPS will rely on its internal battery t...

Page 5: ... remove the two screws on the UPS back panel to access the internal battery Tripp Lite offers a complete line of replacement batteries at www tripplite com Tel DSL Jacks USB Port 6 7 AC Input Outlet 8 Surge Only Protected Outlets 4 Battery Backup Surge Protected Outlets 5 4 5 6 7 8 Storage Service Storage To avoid battery drain all connected equipment should be turned off and disconnected from the...

Page 6: ...th Street Chicago IL 60609 USA 773 869 1234 www tripplite com 2005 Tripp Lite Todos los derechos reservados Instrucciones de seguridad importantes Instalación rápida Operación básica Panel frontal Operación básica Panel posterior Almacenamiento y Servicio 7 8 8 6 6 English Français Póññêèé 1 9 13 ...

Page 7: ... por 24 horas después de la instalación inicial para cargar completamente la batería interna Su equipo conectado recibirá energía de CA suministrada de la red si está disponible inmediatamente después que el UPS esté conectado y encendido sin embargo su equipo conectado no podrá recibir completo respaldo de batería en el caso de una falla del servicio eléctrico o una severa baja de voltaje a menos...

Page 8: ...ngo de tolerancia estándar de computadora puede estar seguro que el UPS está diseñado mediante el empleo de regulación automática de voltaje para suministrar continuamente al equipo conectado un voltaje de salida estable de grado computadora En el caso de una falla del servicio eléctrico pérdida de energía una severa baja de voltaje baja de potencia o un sobrevoltaje subida de potencia el UPS empl...

Page 9: ...siguiente procedimiento Apagar el UPS desconectar el cordón de alimentación y retirar los dos tornillos en el panel posterior del UPS para acceder a la batería interna Tripp Lite ofrece una línea completa de baterías de reemplazo en www tripplite com Puerto USB 6 7 Toma de entrada de CA 8 Salidas protegidas sólo contra sobretensiones 4 Respaldo de batería Salidas protegidas contra sobretensiones 5...

Page 10: ...11 W 35th Street Chicago IL 60609 USA 773 869 1234 www tripplite com Copyright 2005 Tripp Lite Tous droits réservés Importantes consignes de sécurité Installation rapide Fonctionnement de base panneau avant Fonctionnement de base panneau arrière Entreposage et service 11 12 12 10 10 Español English Póññêèé 5 1 13 ...

Page 11: ... la description du bouton MUTE TEST ATTENTION L onduleur UPS doit être branché dans une prise de courant active et mis en marche pendant 24 heures après l installation initiale pour charger complètement sa batterie interne Votre équipement connecté recevra le courant de secteur s il est présent immédiatement après que l onduleur UPS a été branché et mis en marche cependant votre équipement connect...

Page 12: ...assent à cause de la piètre qualité du secteur le registre de la tolérance de l équipement standard soyez assuré que l onduleur UPS est conçu grâce à sa régulation automatique de tension pour fournir en permanence à l équipement connecté une tension de sortie stable classée pour ordinateur Dans le cas d une panne perte de courant de baisse sévère de tension courant faible ou de surtension courant ...

Page 13: ...ité et doit observer la procédure suivante Fermer l onduleur UPS débrancher le cordon d alimentation et dévisser les deux vis au dos du panneau arrière de l onduleur UPS pour accéder à la batterie interne Tripp Lite offre une gamme complète de batteries de remplacement à www tripplite com Prises tél et DSL Port USB 6 7 Prise d entrée CA 8 Prises protégées des surtensions seulement 4 Prises protégé...

Page 14: ...L 60609 USA 773 869 1234 www tripplite com Àâòîðñêîå ïðàâî 2005 Tripp Lite Âñå ïðàâà îõðàíÿþòñÿ Âàæíûå èíñòðóêöèè ïî òåõíèêå áåçîïàñíîñòè Áûñòðàÿ óñòàíîâêà Îñíîâíûå ïðèåìû ðàáîòû ï ïå åð ðå åä äí íÿ ÿÿ ÿ ï ïà àí íå åë ëü ü Îñíîâíûå ïðàâèëà ðàáîòû ç çà àä äí íÿ ÿÿ ÿ ï ïà àí íå åë ëü ü Õðàíåíèå è îáñëóæèâàíèå 15 16 16 14 14 Español Français English 5 9 1 ...

Page 15: ...ííîãî òîêà è âêëþ åí íà 24 àñà äëÿ ïîëíîé çàðÿäêè âíóòðåííèõ áàòàðåé Ïîäêëþ åííîå îáîðóäîâàíèå ïîëó èòü ýëåêòðîïèòàíèå ïåðåìåííîãî òîêà îò ñåòè åñëè åñòü íàïðÿæåíèå â ñåòè ñðàçó æå ïîñëå òîãî êàê ÈÁÏ áóäåò ïîäêëþ åí ê ðîçåòêå è âêëþ åí îäíàêî ïîäêëþ åííîå îáîðóäîâàíèå ìîæåò è íå ïîëó èòü ïîëíîé áàòàðåéíîé ïîääåðæêè â ñëó àå îòêëþ åíèÿ ýëåêòðè åñòâà èëè ñèëüíîãî ïîíèæåíèÿ íàïðÿæåíèÿ åñëè âíóòðåííèå...

Page 16: ...äüòå óâåðåíû òî ÈÁÏ ðàññ èòàí áëàãîäàðÿ àâòîìàòè åñêîé ðåãóëèðîâêå íàïðÿæåíèÿ íà ïîñòîÿííîå ñíàáæåíèå ïðèñîåäèíåííîãî îáîðóäîâàíèÿ ñòàáèëèçèðîâàííûì íàïðÿæåíèåì êîìïüþòåðíîãî êà åñòâà Â ñëó àå îòêëþ åíèÿ ýëåêòðè åñòâà ðåçêîãî ñíèæåíèÿ íàïðÿæåíèÿ èëè ïåðåãðóçêè ÈÁÏ ïîëàãàåòñÿ ïðè ïîäà å âûõîäíîãî íàïðÿæåíèÿ êîìïüþòåðíîãî êà åñòâà íà ñâîè âíóòðåííèå áàòàðåè Èçìåðèòåëü âõîäíîãî íàïðÿæåíèÿ ìîæíî òàêæå...

Page 17: ... äåéñòâóþùåé ðîçåòêå ïåðåìåííîãî òîêà âêëþ èòå åãî ïóòåì íàæàòèÿ è óäåðæàíèÿ â òå åíèå îäíîé ñåêóíäû êíîïêè ON OFF è äàéòå áàòàðåÿì çàðÿæàòüñÿ â òå åíèå 24 àñîâ Åñëè îñòàâèòü áàòàðåè ÈÁÏ íåçàðÿæåííûìè íà ïðîäîëæèòåëüíîå âðåìÿ îíè ïîñòðàäàþò îò íåâîñïîëíèìîé ïîòåðè åìêîñòè Îáñëóæèâàíèå Ïðåæäå åì îòïðàâëÿòü ÈÁÏ íà îáñëóæèâàíèå âûïîëíèòå ñëåäóþùèå äåéñòâèÿ 1 Ïðîñìîòðèòåòå óêàçàíèÿ ïî èíñòàëëÿöèè è ýê...

Page 18: ...Клавиатуры и комплекты Веб камеры Двойники тройники переходники в розетку Аккумуляторы свинцово кислотные AGM VLRA SLA Микрофоны Обжимки Наушники Геймпады джойстики рули Патч корды патч панели Кабели питания Сканеры ...

Reviews: