1
5
9
3
7
11
2
6
10
4
8
12
13
14
SNMPWEBCARD Slot
Input Dry Contact
Interface
Parallel
Configuration Port
Parallel
Configuration Port
DIP
Switches
RS-232
Serial Port
Output Dry
Contact Interface
52
11 – Communications
Note: The communications connections described in this section are optional. The UPS system will function properly without these connections.
11-1 Communications Interfaces
11-2 SNMPWEBCARD Slot
Remove the cover panel to install a Tripp Lite SNMPWEBCARD or MODBUSCARD accessory. These accessories provide a network interface
for the UPS system and enable remote monitoring and control via Modbus, SNMP, Web browser or telnet. Visit www.tripplite.com for more
information about ordering.
11-3 Input Dry Contact Interface
The input dry contact interface receives contact-closure signals that allow the UPS system to receive commands and monitor external battery
conditions:
P1—Remote Emergency Power Off (EPO) (See
Section 11-4
.)
P2—Auxiliary Dry Contact Inputs (2 sets) (Input Contact A: Pin 1,2 Rated for 12V DC minimum 0.1A (nominal); Input Contact B: Pin 3,4 Rated
for 12V DC minimum 0.1A (nominal). See
Section 11-5
.)
P3—External Battery Cabinet Temperature 1 (Temperature Sensor Inputs from external battery cabinets. See
Section 11-6
.)
P4—External Battery Cabinet Temperature 2 (Temperature Sensor Inputs from external battery cabinets. See
Section 11-6
.)
P5—External Battery Cabinet Temperature 3 (Temperature Sensor Inputs from external battery cabinets. See
Section 11-6
.)
P6—External Battery Cabinet Temperature 4 (Temperature Sensor Inputs from external battery cabinets. See
Section 11-6
.)
P7—External Battery Status (For use with battery status cable supplied with external battery cabinets-BP480V26B or BP480V40C.)
Note: Do not apply voltages to the REPO contacts or auxiliary dry contacts. Damage to the UPS may result. For the REPO, the switch must be
latching in order to keep output power OFF from the UPS output.
Note: The following connectors are provided with the UPS: P1, P2 and a 12 position strip for the output dry contacts. P3 and P7 are only shipped
with the optional battery cabinets, which include battery monitoring circuits.
12-212-93-3141.indb 52
12/28/2012 11:18:14 AM