17
Normal Operation
During normal operation, the first line of your LCD Display shows which operating mode your UPS is in: Online Mode, Economy Mode,
Frequency Conversion Mode, Battery Mode, Bypass Mode or Parallel Mode (12kVA model only).
Online Mode:
The UPS provides AC power while utility power is available and switches to On Battery Mode instantly (zero transfer time) if
AC power is interrupted.
Economy Mode:
The UPS provides AC power at high efficiency while utility power is /- 10% rated AC input voltage and switches to
On Battery Mode (8ms transfer time) if AC power is interrupted.
Frequency Conversion Mode:
Used to convert your UPS’s input frequency to a different output frequency (i.e. Input 60 Hz to Output 50
Hz.
Note:
Output will be turned off in Frequency Conversion Mode if the unit is put into Bypass).
Battery Mode:
The UPS provides AC power from battery backup so long as battery power lasts. It switches back to Online or Economy
Mode if utility power is available and shuts down if it runs out of battery power.
Bypass Mode:
The UPS provides AC power while utility power is available. The UPS shuts down if AC power is interrupted.
Parallel Mode (SU12KRT4UHW model only):
The UPS can provide redundancy up to 6kVA or power up to 12kVA. Refer to the manual
provided with the Parallel PDU Kit for more information.
The second line of the LCD Display shows basic power conditions. In each operating mode you can push the SCROLL buttons to browse
through these basic power conditions in the sequences shown below:
Operation
(continued)
ONLINE MODE
00.00KW / 000%
STANDALONE
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
REMAINING TIME
0000 MINUTES
ON-LINE 5/6KVA
V00 CV01
Display Information
Online Mode:
ECONOMY MODE
00.00KW / 000%
STANDALONE
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
REMAINING TIME
0000 MINUTES
ON-LINE 5/6KVA
V00 CV01
Display Information
Economy Mode:
FREQ CONV MODE
00.00KW / 000%
STANDALONE
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
REMAINING TIME
0000 MINUTES
ON-LINE 5/6KVA
V00 CV01
Display Information
Frequency
Conversion Mode:
BATTERY MODE
00.00KW / 000%
STANDALONE
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
REMAINING TIME
0000 MINUTES
ON-LINE 5/6KVA
V00 CV01
Display Information
Battery Mode:
BYPASS MODE
00.00KW / 000%
STANDALONE
00.00KVA / 000%
INPUT VOLTAGE
000V / 00.0Hz
BYPASS VOLTAGE
000V / 00.0Hz
OUTPUT VOLTAGE
000V / 00.0Hz
BATTERY CAPACITY
000V / 000%
REMAINING TIME
0000 MINUTES
ON-LINE 5/6KVA
V00 CV01
Display Information
Bypass Mode:
201207113 933070.indb 17
9/17/2012 1:20:08 PM