Tripp Lite SmartOnline 120/208V Owner'S Manual Download Page 7

7

WIRING CONNECTION

Connect your wiring to the input and output terminal blocks located on the rear panel of your UPS (see figure below).  

CAUTION! 
Qualified personnel should follow all procedures prescribed by N.E.C. and other local 
codes for hardwiring devices to a utility source. 
Ensure that cables are fitted with cable sleeves and are secured by connector clamps. 
Tighten connections with a torque of not less than 35 inch-pounds. Observe the 
appropriate cable connection regulations [e.g. National Electrical Code (NEC) in the 
U.S.] at all times. Using cables of improper size may damage your equipment and cause 
fire hazards. 

Note:

 

When shipped from the factory, bypass input and main input wires are connected.

•  Press the front “OFF” button.  Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display  
  will show “ON BYPASS.”
•  Turn the Main Input Switch and Bypass Input Switch Circuit Breakers OFF. Your load will no longer be energized, and the LCD display will be dark.
  NOTE: If the UPS System remains off for an extended period of time, it should be turned back on periodically to allow the internal batteries to  
  recharge. The UPS System should be turned on and the internal batteries should be recharged at least one uninterrupted 24-hour period every  
  3 months. Failure to provide periodic recharge time may cause irreversible battery damage.  

•  Make sure the UPS is properly installed (see section 3, 

Installation

) and the Manual Bypass Switch is set to NORMAL.

•  Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON. 
•  If your AC input is providing power normally within your selected range, your connected load will energize in Bypass. However, the UPS's inverter  
  is not yet on. Press the front “ON” button to begin inverter operation.
•  If your AC input is not providing power normally, you have the option of starting  from battery. (Your battery must be at least partially charged for  
  this operation to succeed.) Press and hold both the "Battery Start" switch  and the “ON” button for three seconds to start your UPS in “ON BATTERY”  
  mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on  
  the UPS.
•  The UPS will perform a brief self-test and show the results on the LCD Display. (See section 4.3, 

Self-Testing

 for display sequence.) After a  

 

  successful self-test, the UPS will provide AC power from the inverter to your load.

When you turn the UPS ON, it will perform a brief self-test. See charts below for display sequences.

Display sequence when AC input power is present:

Display sequence when AC input power is absent:  
(possible only with the "Battery Start" Switch)

SELF TESTING...

SELF TESTING...

RECTIFIER OK

BATTERY OK

CHARGER OK

DC TO DC OK

BATTERY OK

INVERTER TEST

DC TO DC OK

INVERTER TEST

4.1 Turning the UPS On

4.2 Turning the UPS Off

4.3 Self-Testing

3.5 Initial Battery Charging

3.4 UPS Input And Output Hardwire Connection 

(continued)

4. Operation (Normal Conditions)

3. Installation 

(continued)

Although the internal batteries are charged prior to shipping, allow the internal batteries to charge uninterrupted for 24 hours after initial installation.

N

2

N

1

T

2

R

1

S

2

S

1

R

2

T

1

G

G

Summary of Contents for SmartOnline 120/208V

Page 1: ...Operation Of Manual Bypass Switch 9 6 Communications 10 6 1 RS 232 Interface 10 6 2 AS 400 Interface 10 6 3 Dry Contact Interface 10 6 4 Remote Emergency Power Off EPO 11 7 Adding or Replacing Intern...

Page 2: ...where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this...

Page 3: ...l illuminate constantly to indicate the UPS s AC DC converter is activated BATTERY LED 9 This red light will flash when the UPS is discharging the battery to provide connected equipment with AC power...

Page 4: ...s Internal Battery Pack Connectors Red Black 3 Connect the individual internal battery packs to the overall battery system Internal Battery Pack Jumper Cables White Blue 4 Connect the internal battery...

Page 5: ...ort 7 This female DB9 port sends contact closure signals to indicate line fail and low battery status See section 6 Communications Accessory Slot 8 Remove the small cover panel and use optional access...

Page 6: ...h a torque of not less than 35 inch lbs 3 9 NM Keep ground wire connected at all times after installation Warning When installing the unit verify that any maintenance bypass panel used is configured c...

Page 7: ...Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON If your AC input is providing power normally within your selected range your connected load will energize in Bypass However t...

Page 8: ...SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button While in Bypass Mode the UPS monitors the input voltage which on B...

Page 9: ...should save files and shut down connected equipment The BATTERY LOW message indicates the UPS s batteries are nearly out of power and UPS shutdown is imminent Your UPS will shut down and the LCD will...

Page 10: ...to an IBM AS 400 computer via an AS 400 cable The port uses AS 400 communications to report UPS status It can be used to allow an AS 400 to automatically save open files and shut down its operating sy...

Page 11: ...plastic sleeve covering the battery strings The sleeve is designed to prevent accidental contact with the terminals on the individual batteries Contact with the terminals will create a potential for s...

Page 12: ...wiring diagram prior to adding or replacing batteries The battery module can accept up to four battery packs each pack consisting of two strings The diagram shows all four battery packs connected for...

Page 13: ...nect the RED and BLACK cables attached to each internal battery pack 3 3 Remove the battery cartridge fuses from each fuse block Save the fuses 4 4 Disconnect the BLUE and WHITE jumper cables attached...

Page 14: ...nd position the cable to allow adequate room to add the battery strings 7B 7 7 Slide the battery string with the BLACK cable next to it on the left in the empty slot as shown Make sure that the string...

Page 15: ...connector connect the voltmeter s RED probe to the battery pack s RED connector To get a proper reading make sure the voltmeter s probes touch the metal contacts inside the battery pack s connectors T...

Page 16: ...y Void where prohibited Some restrictions apply See website for details Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and identification your Tri...

Page 17: ...odel SU20K3 3XR5 Input Input Voltage 120 208V AC 3 4 Wire plus ground wye Input Frequency 60 Hz 3 Hz Voltage Correction Range 88 144 166 250V AC Input Current Per Phase On Line 60A Inrush Current 300A...

Page 18: ...ltage 120 208V AC 3 4 Wire plus ground wye Input Frequency 60 Hz 3 Hz Voltage Correction Range 88 144 166 250V AC Input Current Per Phase On Line 90A Inrush Current 300A Power Factor Full Load 0 95 Ef...

Reviews: