SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance 
of all Tripp Lite SmartOnline 3-Phase 20kVA and 30kVA UPS Systems.

UPS Location Warnings

•  Install your UPS in a controlled environment.
•  Install your UPS indoors, away from heat, direct sunlight, dust, and excess moisture or other conductive contaminants.
•  Install your UPS in a structurally sound area that is level. Your UPS is extremely heavy; take care when moving and lifting the unit.
•  Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor temperatures  
  between 62° F and 84° F (between 17° C and 29° C).
•  Leave adequate space around all sides of the UPS for proper ventilation.
•  Do not install the UPS near magnetic storage media, as this may result in data corruption.
•  The UPS System is designed to support a maximum load rating of one (1) power module and up to two (2) fully-loaded battery modules. Failure to  
  observe this maximum load rating (by stacking more than one power module and/or more than two battery modules) will cause permanent damage  
  to the UPS System and create a potential for serious personal injury.
•  The UPS System's caster wheels are only designed for slight position adjustments within the final installation area; they are not designed for  
  moving the UPS System over considerable distances. The wheels are not designed to provide long-term support for the UPS system after final  
  installation. Mounting bracket installation is required. (See section 3, 

Installation.

)

UPS Connection Warnings

•  The power supply for this unit must be three phase rated in accordance with the equipment nameplate. It also must be suitably grounded according  
  to all applicable local electrical wiring regulations.

•  When installing the unit, verify that any maintenance bypass panel used is configured correctly before applying power to the unit.

Equipment Connection Warnings

•  Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support  
  equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable  
  anesthetic mixture with air, oxygen or nitrous oxide.
•  The UPS system contains its own energy source (battery). The output terminals may be live even when the UPS is not connected to an AC supply.

Battery Warnings

•  Your UPS does not require routine maintenance. Do not open the UPS's power module for any reason; there are no user-serviceable parts inside.  
  Because of the risk of electrical shock, only qualified electricians should open the battery module.
•  Because the batteries present a risk of electrical shock and burn from high short-circuit current, batteries should be changed only by trained service  
  personnel observing proper precautions. Remove watches, rings, and other metal objects. Use tools with insulated handles. Wear rubber gloves and  
  boots. Do not lay tools or metal parts on top of the batteries. Do not short or bridge the battery terminals with any object. 
•  Do not dispose of the batteries in a fire. The UPS batteries are recyclable. Refer to local codes for disposal requirements, or in the USA only, refer  
  to these sources for recycling information: 1-800-SAV-LEAD (1-800-728-5323), 1-800-8-BATTERY (1-800-8-228-8379), or www.rbrc.com.
•  Internal batteries must be replaced by equivalent batteries available from Tripp Lite.
•  Do not operate your UPS without batteries.
•  Battery fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number  
  and type. 
•  Potentially lethal voltages exist within this unit as long as the battery supply is connected. Service and repair should be done only by trained  
  personnel. During any service work, the UPS should be turned off or put into manual bypass.
•  Do not connect or disconnect the battery modules while the UPS is operating from the battery supply or when the unit is not in bypass mode.
•  The UPS system ships with the internal batteries disconnected. Refer to section 7, 

Adding or Replacing Internal Batteries

, for battery connection  

  instructions.

1. Important Safety Warnings

Summary of Contents for SmartOnline 120/208V

Page 1: ...Operation Of Manual Bypass Switch 9 6 Communications 10 6 1 RS 232 Interface 10 6 2 AS 400 Interface 10 6 3 Dry Contact Interface 10 6 4 Remote Emergency Power Off EPO 11 7 Adding or Replacing Intern...

Page 2: ...where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this...

Page 3: ...l illuminate constantly to indicate the UPS s AC DC converter is activated BATTERY LED 9 This red light will flash when the UPS is discharging the battery to provide connected equipment with AC power...

Page 4: ...s Internal Battery Pack Connectors Red Black 3 Connect the individual internal battery packs to the overall battery system Internal Battery Pack Jumper Cables White Blue 4 Connect the internal battery...

Page 5: ...ort 7 This female DB9 port sends contact closure signals to indicate line fail and low battery status See section 6 Communications Accessory Slot 8 Remove the small cover panel and use optional access...

Page 6: ...h a torque of not less than 35 inch lbs 3 9 NM Keep ground wire connected at all times after installation Warning When installing the unit verify that any maintenance bypass panel used is configured c...

Page 7: ...Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON If your AC input is providing power normally within your selected range your connected load will energize in Bypass However t...

Page 8: ...SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button While in Bypass Mode the UPS monitors the input voltage which on B...

Page 9: ...should save files and shut down connected equipment The BATTERY LOW message indicates the UPS s batteries are nearly out of power and UPS shutdown is imminent Your UPS will shut down and the LCD will...

Page 10: ...to an IBM AS 400 computer via an AS 400 cable The port uses AS 400 communications to report UPS status It can be used to allow an AS 400 to automatically save open files and shut down its operating sy...

Page 11: ...plastic sleeve covering the battery strings The sleeve is designed to prevent accidental contact with the terminals on the individual batteries Contact with the terminals will create a potential for s...

Page 12: ...wiring diagram prior to adding or replacing batteries The battery module can accept up to four battery packs each pack consisting of two strings The diagram shows all four battery packs connected for...

Page 13: ...nect the RED and BLACK cables attached to each internal battery pack 3 3 Remove the battery cartridge fuses from each fuse block Save the fuses 4 4 Disconnect the BLUE and WHITE jumper cables attached...

Page 14: ...nd position the cable to allow adequate room to add the battery strings 7B 7 7 Slide the battery string with the BLACK cable next to it on the left in the empty slot as shown Make sure that the string...

Page 15: ...connector connect the voltmeter s RED probe to the battery pack s RED connector To get a proper reading make sure the voltmeter s probes touch the metal contacts inside the battery pack s connectors T...

Page 16: ...y Void where prohibited Some restrictions apply See website for details Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and identification your Tri...

Page 17: ...odel SU20K3 3XR5 Input Input Voltage 120 208V AC 3 4 Wire plus ground wye Input Frequency 60 Hz 3 Hz Voltage Correction Range 88 144 166 250V AC Input Current Per Phase On Line 60A Inrush Current 300A...

Page 18: ...ltage 120 208V AC 3 4 Wire plus ground wye Input Frequency 60 Hz 3 Hz Voltage Correction Range 88 144 166 250V AC Input Current Per Phase On Line 90A Inrush Current 300A Power Factor Full Load 0 95 Ef...

Reviews: