background image

6

Move your UPS over short distances using its wheels. 

Note: The wheels are not designed to provide long-term support for the UPS system after final 

installation. Mounting bracket installation is required.

 

DANGER!  

RISK OF PRODUCT DAMAGE AND SERIOUS PERSONAL INJURY

The  UPS  System's  wheels  are  not  designed  to  provide  long-term  support  for  the  UPS  system  after  final 
installation. 

Mounting bracket installation is required.

 If the mounting brackets are not installed, the 

wheels may eventually fail and potentially damage the UPS System and cause serious personal injury.

Using the included bolts, install one mounting bracket on each side of the 
UPS System as shown. If desired, install the bracket to the floor surface 
with user-supplied hardware.

Using  a  user-supplied  4  AWG  ground  wire,  connect  the  UPS  System's 
ground lug to earth ground. Tighten connections with a torque of not less 
than 35 inch-lbs. (3.9 NM). Keep ground wire connected at all times after 
installation.

Warning: When installing the unit, verify that any maintenance bypass panel used is configured correctly before applying power to the unit.

In addition to the instructions listed below, follow all warnings found in section 1, 

Important Safety Warnings

, prior to connection.

•  Install with flex cable of sufficient length to move UPS clear of surrounding equipment for servicing (sides and rear).
•  Use ferrule caps to cover termination cables connected to UPS to avoid frayed ends from shorting on terminal block.
•  Neutral conductor must be same size as current conductors.

WIRING SELECTION

Choose appropriate cabling (rated VW-1, FT-1 or better) to connect your UPS to an AC power supply and your equipment.

UPS System Model

Wiring Size

20kVA

6 AWG / 14 mm2

30kVA

4 AWG / 22 mm2

Maximum Cable Length: 10 m (32.8 ft)

Front View

Rear View

3.2 Mounting Bracket Installation

3.3 Grounding Connection

3.4 UPS Input And Output Hardwire Connection

3.1 UPS Location

3. Installation

Summary of Contents for SmartOnline 120/208V

Page 1: ...Operation Of Manual Bypass Switch 9 6 Communications 10 6 1 RS 232 Interface 10 6 2 AS 400 Interface 10 6 3 Dry Contact Interface 10 6 4 Remote Emergency Power Off EPO 11 7 Adding or Replacing Intern...

Page 2: ...where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this...

Page 3: ...l illuminate constantly to indicate the UPS s AC DC converter is activated BATTERY LED 9 This red light will flash when the UPS is discharging the battery to provide connected equipment with AC power...

Page 4: ...s Internal Battery Pack Connectors Red Black 3 Connect the individual internal battery packs to the overall battery system Internal Battery Pack Jumper Cables White Blue 4 Connect the internal battery...

Page 5: ...ort 7 This female DB9 port sends contact closure signals to indicate line fail and low battery status See section 6 Communications Accessory Slot 8 Remove the small cover panel and use optional access...

Page 6: ...h a torque of not less than 35 inch lbs 3 9 NM Keep ground wire connected at all times after installation Warning When installing the unit verify that any maintenance bypass panel used is configured c...

Page 7: ...Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON If your AC input is providing power normally within your selected range your connected load will energize in Bypass However t...

Page 8: ...SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button Press SELECT Button While in Bypass Mode the UPS monitors the input voltage which on B...

Page 9: ...should save files and shut down connected equipment The BATTERY LOW message indicates the UPS s batteries are nearly out of power and UPS shutdown is imminent Your UPS will shut down and the LCD will...

Page 10: ...to an IBM AS 400 computer via an AS 400 cable The port uses AS 400 communications to report UPS status It can be used to allow an AS 400 to automatically save open files and shut down its operating sy...

Page 11: ...plastic sleeve covering the battery strings The sleeve is designed to prevent accidental contact with the terminals on the individual batteries Contact with the terminals will create a potential for s...

Page 12: ...wiring diagram prior to adding or replacing batteries The battery module can accept up to four battery packs each pack consisting of two strings The diagram shows all four battery packs connected for...

Page 13: ...nect the RED and BLACK cables attached to each internal battery pack 3 3 Remove the battery cartridge fuses from each fuse block Save the fuses 4 4 Disconnect the BLUE and WHITE jumper cables attached...

Page 14: ...nd position the cable to allow adequate room to add the battery strings 7B 7 7 Slide the battery string with the BLACK cable next to it on the left in the empty slot as shown Make sure that the string...

Page 15: ...connector connect the voltmeter s RED probe to the battery pack s RED connector To get a proper reading make sure the voltmeter s probes touch the metal contacts inside the battery pack s connectors T...

Page 16: ...y Void where prohibited Some restrictions apply See website for details Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and identification your Tri...

Page 17: ...odel SU20K3 3XR5 Input Input Voltage 120 208V AC 3 4 Wire plus ground wye Input Frequency 60 Hz 3 Hz Voltage Correction Range 88 144 166 250V AC Input Current Per Phase On Line 60A Inrush Current 300A...

Page 18: ...ltage 120 208V AC 3 4 Wire plus ground wye Input Frequency 60 Hz 3 Hz Voltage Correction Range 88 144 166 250V AC Input Current Per Phase On Line 90A Inrush Current 300A Power Factor Full Load 0 95 Ef...

Reviews: