C14 inlet accepts user-supplied AC power cord with grounded country-specific plug
1-USB port for monitoring interface
Complete surge protection, line isolation and EMI/RFI noise filtering
2 phone line surge suppression for modems, fax machines and other phone accessories
Complete remote monitoring cabling included, PowerAlert UPS management software available via free download
4 diagnostic LEDs indicate AC present, on battery, voltage correction & battery low/replace
Battery replacement door
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
350
Output Watt Capacity
(watts)
225
Nominal Output
Voltage(s) Supported
220V; 230V; 240V
Nominal Voltage details
230v nominal inverter output voltage
Frequency compatibility
50 / 60 Hz
Frequency
compatibility details
Automatic frequency selection
Output voltage
regulation (line mode)
-18%, +8%
Built-in UPS output
receptacles
6 C13 outlet(s)
INPUT
Rated input current (at
maximum load)
1.8A
Nominal Input
Voltage(s) Supported
230V AC
UPS input connection
type
C14 inlet
UPS input connection
description
C14 inlet accepts user-supplied AC power cord with grounded country-specific plug
UPS Input cord length
(ft.)
6 inch dongle, 16 gauge
UPS Input cord length
(m)
1.83
Recommended
Electrical Service
10A 230V
Voltage compatibility
(VAC)
230
Phase
Single-Phase
BATTERY
Full load runtime
(minutes)
15.5 min. (225w)
Half load runtime
(minutes)
37 min. (115w)