DC system voltage
(VDC)
12
Battery recharge rate
(included batteries)
Less than 7.2 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC52
(quantity 2)
Battery Access
Battery access door allows hot-swap battery replacement without powering connected equipment off
Typical battery lifespan
3-6 years, depending on usage
VOLTAGE REGULATION
Voltage regulation
description
Line interactive UPS offers a single boost level of brownout correction to maintain usable, computer grade output
Undervoltage correction
Input voltages between 159 and 199 are boosted by 14%
Direct pass through
Input voltages between 200and 266V AC are passed through unchanged
LEDS ALARMS & SWITCHES
LED Indicators
4 LEDs indicate line power, battery power, overload and battery low/replace status
Alarms
Audible alarm indicates power failure conditions, silenceable via alarm cancel switch. Once cancelled, alarm will
resume when approximately 2 minutes of battery operation remain (assuming full load)
Switches
Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
EMI / RFI AC noise
suppression
Yes
AC suppression
response time
Instantaneous
Dataline suppression
2-Line Tel/DSL
PHYSICAL
Installation form
factors supported with
included accessories
Tower
Installation form
factors supported with
optional accessories
Wallmount (UPSWM - tower mounting kit)
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)
10.6 x 5.2 x 7.4
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)
26.9 x 13.1 x 18.8
UPS / Power Module
weight (lbs)
25.4
UPS / Power Module
weight (kg)
11.5
UPS Shipping
dimensions (height x
width x depth / inches)
14.1 x 10.4 x 8.2