background image

7

3. Battery Cabinet Installation

3.4 Internal Wiring (Typical)

• Battery cabinets use multiple 12 VDC batteries connected in series to provide nominal DC voltages ranging from 192 VDC to 480 VDC 

(±240 VDC).

• Internal cabling is sized for specific application load currents. The insulated cables can be 2 AWG, 4 AWG, 1/0 AWG, 2/0 AWG, 4/0 AWG or 

dual 2/0 AWG.

• Each battery cabinet includes a specific wiring diagram. 
• All circuit breakers are in the top tier of the battery cabinet, except for model BP480V200, which contains the circuit breaker in the 

bottom tier of the battery cabinet.

• All load connection polarities will be marked by a POS (+) or NEG (-) label (or an “N” center label for ±240 VDC strings).
• All battery cabinets are provided with a branch circuit overcurrent protection device and may be wired directly to the load or UPS.
• If the battery cabinet includes an integrated battery charger (single-phase and “C” models only), the internal cabinet wiring will be 

preinstalled and the charger will include fusing for 120 VAC input. The integrated charger can also be powered at 208 VAC/20 A or 240 
VAC/15 A with the appropriate fusing replaced. 

The charger input must be connected to a separate AC supply circuit, not the UPS 

system.

3.5 Preliminary Electrical Check

1.  Reset the circuit breaker to the “on” position and measure the battery cabinet output voltage at the output load connection points. 

(Measure voltage with a digital voltmeter.)

2.  The measured voltage should approximately match the voltage listed on the battery cabinet nameplate. The battery cabinet output 

voltage will be equal to the number of individual batteries installed in series multiplied by the unit voltage. (For example: 40 batteries x 
12.84 VDC = 513.6 VDC output.) 

3.  If the measured voltage is significantly different than anticipated, determine the cause (e.g. low charge, shorted cell, reversed battery, 

faulty wiring) and correct the voltage disparity before proceeding.

4.   Set the circuit breaker to the “off” position as a safety precaution during installation.

3.6 Battery Cabinet Placement

Place the battery cabinet in a cool location with free airflow that is away from direct heat sources. The lifespan and performance of a battery 
can be affected dramatically by elevated temperature, decreasing 50% for each 15° F above 77° F.
1.  Prepare the surface where the cabinet will be placed. The surface must be clean, flat and able to support the battery cabinet and other 

equipment installed nearby. (See 

Section 7.1

 for floor loading specifications.)

2.  Allow adequate clearance around the front and rear of the battery cabinet for ventilation and maintenance. The front door must be 

accessible to allow easy access to internal batteries, internal fuses and other overcurrent protection devices. (See 

Section 7.1

 for 

dimensions. See 

Section 6.1

 for detailed battery cabinet measurements.)

3.  If the cabinet will be anchored to the floor, install appropriate anchor bolts in the mounting hole at the bottom of the cabinet. Use 

washers to create a level surface between the mounting areas around the anchor bolts.

4.  Using extreme caution, remove the bolts securing the battery cabinet to the shipping pallet.
5.  If the cabinet does not have casters proceed to step 8. For cabinets with casters, remove the mount brackets from the cabinet to allow 

the cabinet to roll freely on the casters.  This can be done by loosening the nuts between the leveling feet and the mount brackets.

6.  Cabinets with casters are packaged on shipping pallets with a heavy duty ramp.  Lower the ramp and with extreme caution, move the 

cabinet down the ramp and into position.

7.  If the cabinet with casters is to be secured to the floor, reinstall the mount brackets and mark the floor to install the appropriate floor 

anchors and secure in place.

8.  For cabinets without casters, forklift forks should be at maximum width within the cabinet clearance opening and fully inserted to prevent 

tipping. Lift cabinet from bottom only. Be careful not to damage the sheet metal floor of the cabinet with the forks.

9.  If the battery cabinet will be secured to the floor, carefully align and lower the battery cabinet down on the floor anchor bolts and secure 

it in place.

10. If the cabinet will not be secured to the floor, lower it into the designated space and then level it using shims. (Leveling does not affect 

performance but does align the battery cabinet with other equipment in the facility.)

Summary of Contents for BP192V787C-1PH

Page 1: ...lications BP192V787C 1PH Single Phase BP480V200 and All BP240V Models BP480V300 and BP480V400 Models BP480V500 Model 1111 W 35th Street Chicago IL 60609 USA www tripplite com support Copyright 2019 Tr...

Page 2: ...ional 9 5 Maintenance 10 5 1 Maintenance Schedule 10 6 Diagrams 11 6 1 Battery Cabinet Diagrams 11 6 1 1 BP192V787C 1PH Model 2 Shelves 11 6 1 2 All BP240V Models 3 Shelves 12 6 1 3 BP480V200 Model 4...

Page 3: ...resistance Battery cabinet is shipped bolted to pallet with a double layer of protective stretch wrap and integrated corner and top protection Appropriate ventilation and convection cooling of the ind...

Page 4: ...such as freight elevators pallet jacks and forklifts Fully extend forks under load Spread forks to maximum possible width under load Lift cabinet from bottom only Wear safety shoes For emergency use...

Page 5: ...and boots Do not short or bridge the battery terminals with any object Do not lay tools or metal parts on top of batteries Replace batteries with equivalent batteries same number and type available f...

Page 6: ...ifts Fully extend forks under load Spread forks to maximum possible width under load Lift cabinet from bottom only Wear safety shoes Confirm that load limits for freight elevators handling equipment a...

Page 7: ...ee airflow that is away from direct heat sources The lifespan and performance of a battery can be affected dramatically by elevated temperature decreasing 50 for each 15 F above 77 F 1 Prepare the sur...

Page 8: ...age should measure 0 zero VDC If the measured voltage is not zero determine the cause and correct before proceeding 3 Return the internal circuit breaker in an open off position as a safety precaution...

Page 9: ...battery terminals 2 Measure and record the system float current using a clamp on ammeter 3 Measure and record the float voltage of individual battery units 4 Measure and record the temperature of sev...

Page 10: ...espan Battery lifespan is reduced by 50 for each 15 F above 77 F For example battery lifespan will be reduced by half at 92 F 2 Measure individual battery unit float charging voltages Measure voltage...

Page 11: ...11 6 Diagrams 6 1 Battery Cabinet Diagrams 6 1 1 BP192V787C 1PH Model 2 Shelves Dimensions INCHES cm...

Page 12: ...12 Dimensions INCHES cm 6 Diagrams 6 1 2 All BP240V Models 3 Shelves...

Page 13: ...13 6 Diagrams 6 1 3 BP480V200 Model 4 Shelves Dimensions INCHES cm...

Page 14: ...14 Dimensions INCHES cm 6 Diagrams 6 1 4 BP480V300 and BP480V400 Models 4 Shelves...

Page 15: ...15 6 Diagrams 6 1 5 BP480V500 Model 4 Shelves Dimensions INCHES cm...

Page 16: ...ed and rated for 600 VDC Breaker is UL listed and rated for 50 A 600 VDC 42 KAIC Cabinets with breakers are shipped with the breaker in the off open position and one of the jumper cables disconnected...

Page 17: ...ated for 70 A 600 VDC 42 KAIC Cabinets with breakers are shipped with the breaker in the off open position and one of the jumper cables disconnected Battery arrangements shown are typical but may vary...

Page 18: ...er is UL listed and rated for 150 A 600 VDC 42 KAIC Cabinets with breakers are shipped with the breaker in the off open position and one of the jumper cables disconnected Battery arrangements shown ar...

Page 19: ...ith breakers are shipped with the breaker in the off open position and one of the jumper cables disconnected Battery arrangements shown are typical but may vary depending on cabinet and battery type T...

Page 20: ...MTW 105C Hi Flex cable Battery type is CSB HRL FR series Cabinets with breakers are shipped with the breaker in the off open position and one of the jumper cables disconnected Terminal block is UL rec...

Page 21: ...e output from the circuit breaker in Cabinet 1 is factory wired to the paralleling busbars Use the included cables to connect the output from the additional cabinets to the paralleling bars in Cabinet...

Page 22: ...breaker in Cabinet 1 is factory wired to the paralleling busbars Use the included cables to connect the output from the additional cabinets to the paralleling bars in Cabinet 1 Route the cables from p...

Page 23: ...d to 13 65 V 0 15 V per battery Electronic current limiting and high voltage shutdown AC and DC fusing Included 30 A AC fusing is suitable for 120 VAC input optional 20 A for 208 VAC input and optiona...

Page 24: ...es 101 6 x 74 9 x 199 9 cm N 4760 lb 2159 kg 581 lb ft 2 2836 kg m2 EBP240V2501 3 29 x 31 5 x 58 9 inches 73 7 x 80 0 x 149 9 cm Y 1593 lb 722 kg 250 lb ft 2 1221 kg m2 EBP240V3501 3 29 x 31 5 x 58 9...

Page 25: ...239OWFR M6 Threaded Insert 78 in lbf 8 8 N m BP480V500 HRL12540WFR M6 Threaded Insert 78 in lbf 8 8 N m EBP240V2501 HRL12280WFR M6 Threaded Insert 78 in lbf 8 8 N m EBP240V3501 HRL12390WFR M6 Threaded...

Page 26: ...n accordance with all applicable instructions to be free from original defects in material and workmanship for a period of 1 year from the date of initial purchase If the product should prove defectiv...

Page 27: ...caciones m viles BP192V787C 1PH Monof sico BP480V200 y Todos los Modelos BP240V Modelos BP480V300 y BP480V400 Modelo BP480V500 1111 W 35th Street Chicago IL 60609 EE UU www tripplite com support Copyr...

Page 28: ...n Opcional 35 5 Mantenimiento 36 5 1 Programa de Mantenimiento 36 6 Diagramas 37 6 1 Diagramas del Gabinete de Bater as 37 6 1 1 Modelo BP192V787C 1PH 2 Repisas 37 6 1 2 Todos los Modelos BP240V 3 Re...

Page 29: ...ca atornillado a la tarima con una doble capa de envoltura de protecci n el stica y una protecci n integrada en las esquinas y la parte superior La ventilaci n apropiada y el enfriamiento por convecci...

Page 30: ...s al m ximo ancho posible bajo la carga Levante el gabinete por la base solamente Use calzado protector Para uso en caso de emergencia instale un extintor certificado para incendios de equipos el ctri...

Page 31: ...de hule No ponga en corto o puentee las terminales de la bater a con ning n objeto No coloque herramientas o partes met licas sobre la parte superior de las bater as Reemplace las bater as por otras e...

Page 32: ...horquillas al m ximo ancho posible bajo la carga Levante el gabinete por la base solamente Use zapatos de seguridad Confirme que los l mites de carga para montacargas equipos de manejo y pisos a lo la...

Page 33: ...ugar fresco con flujo de aire libre que est alejado de fuentes de calor directo La vida til y el rendimiento de una bater a pueden verse considerablemente afectadas por temperaturas elevadas disminuye...

Page 34: ...medir 0 cero VCD Si el voltaje medido no es cero determine la causa y corr jala antes de continuar 3 Regrese el breaker interno a una posici n abierta OFF como medida de precauci n mientras se conecta...

Page 35: ...re la corriente de flotaci n del sistema usando un amper metro de pinza 3 Mida y registre el voltaje de flotaci n de las unidades de bater a individuales 4 Mida y registre la temperatura de varias bat...

Page 36: ...se reduce en un 50 por cada 9 44 C 15 F por encima de 25 C 77 F Por ejemplo la vida til de la bater a se reducir a la mitad a 33 33 C 92 F 2 Mida los voltajes de carga en flotaci n de cada unidad indi...

Page 37: ...EN CUBIERTA TRASERA RIELES DE SOPORTE ALTOS DE BATER A O D T PICO ESPACIO LIBRE PARA RIELES B W AL FRENTE DEL GABINETE BANDEJA DE INSTALACI N PARA EL BREAKER Y EL BLOQUE DE TERMINALES RIELES HACIA ARR...

Page 38: ...38 Dimensiones PULGADAS cm 6 Diagramas 6 1 2 Todos los Modelos BP240V 3 Repisas...

Page 39: ...CIONAL LATERAL DERECHA VISTA FRONTAL SIN PUERTA FRENTE DEL GABINETE FRENTE DEL GABINETE FRENTE DEL GABINETE BANDEJA DEL BREAKER RECORTE PARA CONDUIT RECORTE PARA CONDUIT RECORTE PARA CONDUIT RECORTE P...

Page 40: ...RECORTE PARA CONDUIT RECORTE PARA CONDUIT RECORTE PARA CONDUIT ORIFICIOS DE INSTALACI N RECORTES PARA CONDUIT RECORTES PARA CONDUIT RECORTES PARA CONDUIT FRENTE DEL GABINETE FRENTE DEL GABINETE VISTA...

Page 41: ...ABINETE BANDEJA DEL BREAKER VISTA FRONTAL SIN PUERTA FRENTE DEL GABINETE FRENTE DEL GABINETE RECORTE PARA CONDUIT RECORTE PARA CONDUIT RECORTE PARA CONDUIT RECORTE PARA CONDUIT RECORTES PARA CONDUIT R...

Page 42: ...A GABINETE DE BATER AS OPCIONAL EN PARALELO AL POSITIVO DEL UPS PARA DESCONECTAR EL CARGADOR PARA DESCONECTAR EL CARGADOR DEL POSITIVO DE LA BATER A DEL NEGATIVO DE LA BATER A AL NEGATIVO DEL UPS CON...

Page 43: ...R AS OPCIONAL EN PARALELO AL POSITIVO DEL UPS PARA DESCONECTAR EL CARGADOR PARA DESCONECTAR EL CARGADOR DEL POSITIVO DE LA BATER A DEL NEGATIVO DE LA BATER A AL NEGATIVO DEL UPS CONEXI N EN PARALELO B...

Page 44: ...enteo desconectado Las disposiciones de bater as que se muestran son t picas pero pueden variar dependiendo del tipo de gabinete o bater a AL GABINETE DE BATER AS OPCIONAL EN PARALELO NEGATIVO DE LA B...

Page 45: ...be conectarse nicamente a las terminales similares en el UPS y los gabinetes de bater as en paralelo No se debe conectar a la tierra f sica ni debe conectarse con el neutro de la fuente de CA AL GABIN...

Page 46: ...esconectado El bloque de terminales est reconocido por UL y tiene una capacidad nominal de 600 VCC La conexi n a tierra es 2 6 250 MCM terminal mec nico BREAKER POSTE DE CONEXI N A TIERRA CONECTADO AL...

Page 47: ...a de CD al UPS debe conectarse a la barra de bus en paralelo del Gabinete 1 CABLEADO T PICO DE 120 120 240 V CD GABINETES T PICOS 1 Y 2 AL BREAKER CABLEADO DE LA BARRA DE BUS PARA CONEXI N EN PARALELO...

Page 48: ...DE LOS GABINETES 1 2 Y 3 BREAKER SALIDA POSITIVA DE LOS GABINETES 1 2 Y 3 BREAKER SALIDA NEUTRA DE LOS GABINETES 1 2 Y 3 BREAKER SALIDA NEGATIVA AL UPS BAT BAT N BAT SWITCH AUXILIAR NOTA CONTACTOS MO...

Page 49: ...r a Integrado de 7A Modelos Selectos Notas Todas las dimensiones son pulgadas La entrada de CA es seleccionable de 120V 208V 240V CA 60 Hz Salida de voltaje constante El voltaje de salida de CD est co...

Page 50: ...0 4 101 6 x 74 9 x 199 9 cm 40 x 29 5 x 78 7 N 2159 kg 4760 lb 2836 kg m2 581 lb pie2 EBP240V2501 3 73 7 x 80 0 x 149 9 cm 29 x 31 5 x 58 9 Y 722 kg 1593 lb 1221 kg m2 250 lb pie2 EBP240V3501 3 73 7 x...

Page 51: ...400 HRL1239OWFR Inserto Roscado M6 78 lbf 8 8 N m BP480V500 HRL12540WFR Inserto Roscado M6 78 lbf 8 8 N m EBP240V2501 HRL12280WFR Inserto Roscado M6 78 lbf 8 8 N m EBP240V3501 HRL12390WFR Inserto Rosc...

Page 52: ...de acuerdo con todas las instrucciones aplicables de que est libre de defectos en material y mano de obra por un per odo de 1 a o a partir de la fecha de compra inicial Si el producto resultara defec...

Page 53: ...53 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 2019 Tripp Lite BP192V787C 1PH BP480V200 BP240V BP480V300 BP480 400 BP480V500...

Page 54: ...1 4 2 61 4 3 61 4 4 61 5 62 5 1 62 6 63 6 1 63 6 1 1 BP192V787C 1PH 2 63 6 1 2 BP240V 3 64 6 1 3 BP480V200 4 65 6 1 4 BP480V300 BP480V400 4 66 6 1 5 BP480V500 4 67 6 2 68 6 2 1 192 68 6 2 2 240 69 6 2...

Page 55: ...55 1 Tripp Lite SmartOnline 192 240 480 55 140 A C20 1 67 12 2 3 4 4 8 10 IBC 2012 F Ss 2 0 1 5 12 7 C...

Page 56: ...56 2 0 40 C 25 C C VW 1 FT 1 C...

Page 57: ...57 2 Tripp Lite 24 3 24 C Tripp Lite...

Page 58: ...58 3 2 3 1 8 3 2 1 Tripp Lite 2 3 3 3 1 2 3 4 C Tripp Lite 5 7 2 6 7 8...

Page 59: ...59 3 3 4 12 192 480 240 B 34 2 21 2 54 2 67 2 107 2 67 2 BP480V200 N 240 C 120 208 20 240 15 3 5 1 2 40 x 12 84 513 6 3 4 3 6 50 8 25 C 1 7 1 2 7 1 6 1 3 4 5 8 6 7 8 9 10...

Page 60: ...60 3 3 7 A UL UL 1 5 NEC C 1 2 0 3 4 5 350 6 7 N 3 8 1 C 120 6 2 6 3 2 120 2 3 3 4 5 6 3 7 8 30 120 60 3 9 1 2 2 3 4 5...

Page 61: ...4 4 1 240 40 HRL12540WFR 20 x 14 4 288 20 x 13 5 13 8 270 276 4 2 1 2 Tripp Lite SmartOnline 3 24 4 5 Tripp Lite SmartOnline 6 1 24 4 3 4 3 1 2 3 4 5 6 4 4 4 4 1 2 15 5 15 3 23 5 C 26 5 C 4 5 6 IEEE...

Page 62: ...62 5 5 1 1 25 C 25 C 8 25 50 33 2 13 2 14 2 3 1 2 3 100 10 4 4 1 2 7 2 3...

Page 63: ...63 6 6 1 6 1 1 BP192V787C 1PH 2 c...

Page 64: ...64 6 6 1 2 BP240V 3 c...

Page 65: ...65 6 6 1 3 BP480V200 4 c...

Page 66: ...66 6 6 1 4 BP480V300 BP480V400 4 c...

Page 67: ...67 6 6 1 5 BP480V500 4 c...

Page 68: ...68 6 6 2 6 2 1 192 UL MTW 105 C UL 600 UL 50 600 42 216 221 120 208 240 192 218 218...

Page 69: ...69 6 6 2 2 240 UL MTW 105 C UL 600 UL 70 600 42 270 276 240 273 120 208 240 273...

Page 70: ...70 6 6 2 3 240 UL MTW 105 C UL 600 UL 150 600 42 1 2 3...

Page 71: ...71 6 6 2 4 240 UL MTW 105 C UL 600 UL 250 600 42 N...

Page 72: ...72 6 6 2 5 EBP 120 UL MTW 105 C CSB HRL FR UL 600 6 250 MCM 1 11 20 120 120 240...

Page 73: ...73 6 UL MTW 105 C CSB HRL FR UL 600 6 250 MCM 1 1 1 1 1 1 6 2 6 120 120 240 1 2 1 1 2 1 2 1 2 1 2 2 1 1 1 1 1 1 1 1 1 11 1 20 1 1 2 11 2 20 2...

Page 74: ...74 6 UL MTW 105 C CSB HRL FR UL 600 6 250 MCM 1 1 1 1 1 1 120 120 240 1 2 3 1 2 3 1 2 3 1 2 3 1 1 1 1 1 1 1 2 11 2 20 2 1 1 11 1 20 1 1 1 1 1 3 11 3 20 3 3 1 2 2 2 1 3 1...

Page 75: ...75 6 6 3 7 A c 120 208 240 60 13 65 0 15 30 120 20 208 20 240 15 A Charger OK...

Page 76: ...80 0 x 149 9 c 722 1221 2 EBP240V3501 3 73 7 x 80 0 x 149 9 c 867 1470 2 EBP240V5001 3 73 7 x 80 0 x 149 9 c 1083 1836 2 EBP240V2502 3 73 7 x 80 0 x 149 9 c 1238 2099 2 EBP240V3502 3 73 7 x 80 0 x 14...

Page 77: ...01 HRL12280WFR M6 8 8 EBP240V3501 HRL12390WFR M6 8 8 EBP240V5001 HRL12540WFR M6 8 8 EBP240V2502 HRL12280WFR M6 8 8 EBP240V3502 HRL12390WFR M6 8 8 EBP240V5002 HRL12540WFR M6 8 8 EBP240V6002 XHRL12620WF...

Page 78: ...e com support 1 2 www tripplite com support 3 www tripplite com support Product Returns RMA RMA Tripp Lite Tripp Lite 1 1 Tripp Lite 1111 W 35th Street Chicago IL 60609 USA www tripplite com support T...

Page 79: ...79...

Page 80: ...80 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 19 02 084 93 3390_RevE...

Reviews: