background image

2

SAVE THESE INSTRUCTIONS

This manual contains instructions and warnings that should be followed during the 

installation, operation and storage of this product. Failure to heed these warnings 

may affect the warranty.

UPS Location Warnings

•  Install your UPS indoors, away from excess moisture or heat, conductive contaminants, 

dust or direct sunlight.

•  For best performance, keep the indoor temperature between 32º F and 104º F (0º C and 

40º C).

•  Leave adequate space around all sides of the UPS for proper ventilation.
•  Only set the UPS upright on a sturdy flat surface. Do not block fans or ventilation holes, as 

this will seriously inhibit the unit's internal cooling and cause product damage not covered 

under warranty.

UPS Connection Warnings

•  Connect your UPS directly to a properly grounded AC power outlet. Do not plug the UPS into 

itself; this will damage the UPS.

•  Do not modify the UPS plug, and do not use an adapter that would eliminate the UPS 

ground connection.

•  Do not use extension cords to connect the UPS to an AC outlet.
•  If the UPS receives power from a motor-powered AC generator, the generator must provide 

clean, filtered, computer-grade output.

•  The mains socket outlet that supplies the UPS should be easily accessible and located near 

the UPS.

Equipment Connection Warnings

Install in accordance with National Electrical Code standards ANSI/NFPA 

70 and Canadian Electrical Code, Part I, C22.1. 
Short-circuit backup protection and overcurrent protection is provided by 

the building installation. 
To reduce the risk of fire, connect only to a circuit provided branch circuit 

overcurrent protection in accordance with the National Electrical Code, 

ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1. The plug on 

the power supply cord is intended to serve as the disconnect device. Be 

sure that the socket-outlet is installed near the equipment and is made 

easily accessible.

•  Use of this equipment in life support applications where failure of this equipment can 

reasonably be expected to cause the failure of the life support equipment or to significantly 
affect its safety or effectiveness is not recommended. 

•  Do not connect surge protectors or extension cords to the output of your UPS. This might 

damage the UPS and may affect the surge protector and UPS warranties.

•  Connect the UPS to an outlet that is adequately protected against excess currents, short 

circuits and earth faults as part of the building installation.

Important Safety Instructions

Summary of Contents for AG-0552

Page 1: ...ory Compliance Español 11 Français Warnings and Safety Instructions 21 Owner s Manual 1111 W 35th Street Chicago IL 60609 USA tripplite com support Copyright 2021 Tripp Lite All rights reserved WARRANTY REGISTRATION Register your product today and be automatically entered to win an ISOBAR surge protector in our monthly drawing tripplite com warranty Series Number AG 0552 Series Number AG 0553 Seri...

Page 2: ...mputer grade output The mains socket outlet that supplies the UPS should be easily accessible and located near the UPS Equipment Connection Warnings Install in accordance with National Electrical Code standards ANSI NFPA 70 and Canadian Electrical Code Part I C22 1 Short circuit backup protection and overcurrent protection is provided by the building installation To reduce the risk of fire connect...

Page 3: ...B C Visit Tripp Lite on the Web at tripplite com products battery finder to locate the specific replacement battery for your UPS CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves Do not lay tools...

Page 4: ...ive utility power Installation and Operation To turn the UPS off press the power button The green LED will turn off and the BATTERY BACKUP outlets will stop passing power STEP 3 Plug your equipment into the UPS There are two sets of outlets on your UPS Outlets marked SURGE ONLY do not provide battery backup power during power outages Connect common desktop items like printers scanners and other ac...

Page 5: ...ult Status Line Mode when load levels of 125 or greater occur for a duration of 10 minutes and 20 seconds UPS remains silent in Battery Backup Mode until low battery notification occurs UPS goes to Overload Shutdown Battery Mode with load levels of 110 or greater Shutdown occurs within 36 seconds Alarm Configuration Note The alarm is factory configured to remain silent in battery mode until the lo...

Page 6: ...rrent status of the UPS For detailed description see LED Indicators for more information 3 Battery Backup Outlets These outlets offer battery backup support and premium surge suppression for critical devices requiring battery backup support 4 Surge Only Outlets These outlets offer premium surge suppression for devices not requiring battery backup support ...

Page 7: ... to a computer in order to automatically save open files and shut down the computer if it is left unattended during an extended power failure Use with Tripp Lite s PowerAlert software and appropriate USB cable Download PowerAlert software free of charge from tripplite com support and follow the installation instructions Any user supplied USB cable may be used to connect your UPS to your computer N...

Page 8: ...oblem does not originate from a misreading of the instructions 2 If the problem continues do not contact or return the product to the dealer Instead visit tripplite com support 3 If the problem requires service visit tripplite com support and click the Product Returns link From here you can request a Returned Material Authorization RMA number which is required for service This simple online form w...

Page 9: ...A 120V 8 8A 120V Maximum Output P F P F 0 6 P F 0 6 P F 0 5 Efficiency with Normal Load 98 3 98 4 98 4 Efficiency at Rated Load 98 3 98 4 98 4 Maximum Operating Altitude at 100 of Nominal Power 3000 m 3000 m 3000 m Online Overload Capacity 125 for 10 minutes 20 seconds 125 for 10 minutes 20 seconds 125 for 10 minutes 20 seconds Overload Capacity in Battery Mode 110 for up to 36 seconds 110 for up ...

Page 10: ...ts the telecommunications network protective operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements Document s The Department does not guarantee the equipment will operate to the user s satisfaction Before installing this equipment users should ensure that it is permissible to be connected to the facilities of the local telecommunications com...

Page 11: ...ía 17 Almacenamiento y Servicio 18 Especificaciones 19 Cumplimiento de las 20 Regulaciones English 1 Français Advertencias e Instrucciones 21 de Seguridad Manual del Propietario 1111 W 35th Street Chicago IL 60609 EE UU tripplite com support Copyright 2021 Tripp Lite Todos los derechos reservados Número de Serie AG 0552 Número de Serie AG 0553 Número de Serie AG 0554 No es adecuado para aplicacion...

Page 12: ...n de un generador de CA accionado por motor debe probarse que el generador proporciona una salida de grado computadora limpia y filtrada El tomacorrientes que alimenta al UPS debe ser fácilmente accesible y estar cerca del UPS Advertencias para la Conexión del Equipo Instale de acuerdo con los estándares del Código Eléctrico Nacional ANSI NFPA 70 y Código Eléctrico Canadiense Parte I C22 1 La prot...

Page 13: ...uchos de Batería de Repuesto R B C para Sistemas UPS Para localizar la batería de reemplazo específica para su UPS visite Tripp Lite en el sitio tripplite com products battery finder PRECAUCIÓN Una batería puede presentar un riesgo de descarga eléctrica y alta corriente de cortocircuito Deben observarse las siguientes precauciones al trabajar con baterías Retire relojes anillos u otros objetos met...

Page 14: ...a activa de la red pública Para apagar el UPS presione el botón de encendido El LED verde se apagará y los tomacorrientes con RESPALDO POR BATERÍA dejarán de pasar energía PASO 3 Enchufe su equipo en el UPS Hay dos grupos de tomacorrientes en su UPS Los tomacorrientes marcados SURGE ONLY no proporcionan respaldo de alimentación por batería durante apagones Conecte en estos tomacorrientes los equip...

Page 15: ...o de Falla por Sobrecarga Modo en Línea cuando los niveles de carga de 125 o más ocurran por una duración de 10 minutos y 20 segundos El UPS permanece silencioso en modo de respaldo por batería hasta que se realice la notificación de batería baja El UPS se va a apagar por Sobrecarga Modo de Respaldo por Batería con niveles de carga de 110 o más el apagado ocurre en un lapso de 36 segundos Nota de ...

Page 16: ...sulte los Indicadores LED para obtener más información 3 Tomacorrientes Respaldados por la Batería Estos tomacorrientes ofrecen soporte de respaldo por batería y supresión de sobretensiones premium para dispositivos críticos que requieran soporte de respaldo por batería 4 Tomacorrientes Únicamente para Supresión de Sobretensiones Estos tomacorrientes ofrecen supresión premium de sobretensiones par...

Page 17: ...utadora para guardar automáticamente los archivos abiertos y apagar la computadora si se deja sin supervisión durante una falla prolongada de energía Utilice con el Software PowerAlert de Tripp Lite y un cable USB adecuado Descargue el software PowerAlert sin cargo de tripplite com support y siga las instrucciones de instalación Puede utilizarse cualquier cable USB suministrado por el usuario para...

Page 18: ...ectura de las instrucciones 2 Si el problema persiste no se ponga en contacto con el distribuidor ni le devuelva el producto En su lugar visite tripplite com support 3 Si el problema requiere de servicio visite tripplite com support y haga click en el enlace Devolución de productos Desde aquí puede solicitar un número de Autorización de Devolución de Mercancía RMA que se requiere para servicio Est...

Page 19: ...A 120V 8 8A 120V F P Máximo de Salida F P 0 6 F P 0 6 F P 0 5 Eficiencia con Carga Normal 98 3 98 4 98 4 Eficiencia a la Carga Especificada 98 3 98 4 98 4 Altitud Máxima de Funcionamiento al 100 de la Potencia Nominal 3000 m 3000 m 3000 m Capacidad de Sobrecarga en Línea 125 por 10 minutos 20 segundos 125 por 10 minutos 20 segundos 125 por 10 minutos 20 segundos Capacidad de Sobrecarga en Modo de ...

Page 20: ...serie exclusivo El número de serie se puede encontrar en la etiqueta de placa de identificación junto con todas las marcas e información requeridas de aprobación Al solicitar información de conformidad para este producto refiérase siempre al número de serie El número de serie no debe confundirse con el nombre de la marca o el número de modelo del producto Tripp Lite tiene una política de mejora co...

Page 21: ...iliser de rallonges électriques pour brancher l onduleur à une prise de courant CA Si l onduleur est alimenté à partir d une génératrice CA entraînée par un moteur la génératrice doit fournir une tension de sortie propre filtrée et adaptée aux équipements informatiques La prise de courant du secteur alimentant l onduleur devrait être facilement accessible et située près de l appareil Avertissement...

Page 22: ...atteries ou visiter tripplite com support recycling program pour obtenir plus de renseignements au sujet du recyclage Tripp Lite offre une gamme complète de cartouches de batterie de remplacement pour onduleur R B C Visiter Tripp Lite sur le Web à tripplite com products battery finder pour trouver la batterie de remplacement qui correspond à l onduleur MISE EN GARDE Une batterie peut présenter un ...

Page 23: ...23 ...

Page 24: ...24 1111 W 35th Street Chicago IL 60609 USA tripplite com support 21 03 279 93 3CE8_RevB ...

Reviews: