3.3 Unit Specifications

Type of Unit

Centrifugal Atomizing

Mounting

Return Duct/Wall/Table-top/Ceiling

Capacity (GPD)

6 GPD, 2 Lbs./Hr., 0.9 Kg/Hr.

Water Supply

20-80 PSI (138-552 KPa)

Voltage(Amps)

120VAC(0.8A), 220VAC(0.4A)

Unit Dimensions

11”"W x 9.5" D x 12" H

279mm W x 241mm D x 305mm H

   Water Connection

1/4” (6.35 mm) OD Tubing

   Overflow Connection

1/2” (12.7 mm) ID Tubing

Ducted Connection

3” Diameter (76 mm)

Shipping Weight

12.75 Lbs. (28 Kg)

Operating Weight

9 Lbs. (19.8 Kg)

Approvals

ETL (US & Canada) CE (220V)

4. Installation

Prior to installing this product:

• 

Read the instructions carefully and completely to ensure 

safe operation.  Failure to follow the instructions could lead 

to damage to the product or cause a hazardous condition.

• 

Check the ratings given on the product to make sure it is 

suitable for your application.

Remember to select a location that is readily accessible for peri-

odic inspection, cleaning, and service.  The following table indi-

cates the minimum allowable installation clearances.

4.1 Clearances

Left

2”

Right

2”

Top

5”

Bottom

0” (for surface mounting)

Back

2”

CAUTION

Trion  recommends  that  this  humidifier  be  installed  by  a 

trained HVAC professional.  Do not connect the unit to the 

power source until the installation is complete.  A thorough 

checkout of the unit installation should be completed before 

operating the unit.  Failure to follow these directions may void 

the manufacturer’s original warranty.

4.2 Selecting A Location

The ComfortBREEZE CB-707 Humidifier may be mounted di-

rectly to the return duct of your HVAC system with the discharge 

entering the ductwork, it may be wall-mounted for atmospheric 

dispersion, it may be hung from a ceiling (mounting hardware 

not  included  for  this  type  of  installation),  or  it  may  be  simply 

mounted to a shelf.  An indicating LED is located on the oposite 

side of the base from the plumbing and electrical connections.  

Ensure  that  this  LED  is  visible,  if  desired,  when  selecting  a 

mounting location.

When mounting the humidifier on the face of a horizontal return 

duct or on the face of a vertical return duct, certain conditions 

must be met to ensure proper unit operation.

• 

Ensure that the duct surface is reinforced, if necessary, to 

allow the unit to remain level and plumb.

• 

Locate the humidifier at least four (4) linear feet upstream of 

either the furnace fan and/or filter and any turn in the duct.  

This will ensure that moisture does not accumulate in the 

duct that may cause leakage, corrosion, or mold growth.

• 

Mount the humidifier at least six (6) linear feet (preferably 

10 feet) upstream of any electronic air cleaner.  Failure to 

follow this recommendation may result in excessive arcing 

or power supply failure in the air cleaner.

• 

If the duct seams inside the duct are not flat, locate the hu-

midifier at least three (3) linear feet upstream of the seam.

• 

If the humidification needs of the space require more than 

one humidifier, each unit should be installed a minimum of 

three (3) linear feet apart.

• 

DO NOT use this humidifier on the discharge or warm air 

supply side of a forced air heating system.  This will reduce 

the  efficiency  of  the  humidifier  and  may  cause  additional 

operational problems.

• 

DO NOT mount the humidifier in a furnace jacket.

• 

DO  NOT  install  the  humidifier  where  freezing  conditions 

could occur.

• 

DO NOT install on gravity hot air systems.

4.2.1 Wall Mounting The Humidifier

Figure 1

1. 

Referring  to  figure  1,  using  the  mounting  template,  mark 

the mounting holes on the wall.  Ensure that the mounting 

screws will penetrate wall-studs.

2.  While holding the template against the wall, check with a 

Summary of Contents for ComfortBREEZE CB707

Page 1: ...T r i o n w w w t r i o n i a q c o m ComfortBREEZE TM CB707 Centrifugal Atomizing Humidifier READ AND SAVE THESE INSTRUCTIONS...

Page 2: ...4 3 3 What s in the Box 4 3 4 Hardware Details 4 4 Installation 5 4 1 Clearances 5 4 2 Selecting a location 5 4 2 1 Wall Mounting 5 4 2 2 Duct Mounting 6 4 2 3 Ceiling Mouning 6 4 2 4 Shelf Mounting...

Page 3: ...is limited to replacement of defective parts or components and does not include the pay ment of the cost of labor charges to remove or replace such defec tive components or parts 7 Trion will not be r...

Page 4: ...f the air If applicable set the humidistat in the recommended range of 30 40 relative humidity for automatic humidity control during the heating season A lower setting may be necessary to pre vent con...

Page 5: ...ic dispersion it may be hung from a ceiling mounting hardware not included for this type of installation or it may be simply mounted to a shelf An indicating LED is located on the oposite side of the...

Page 6: ...ounting holes as shown on the template for mounting the bracket to the duct 5 Cut out the discharge hole while taking care not to injure yourself Once the hole is cut out ensure that the edges will no...

Page 7: ...ge the water into a bucket or pan This will allow the water to flush any debris that may have accumulated in the line during the in stallation process Once this is complete close the saddle valve 3 At...

Page 8: ...up for continu ous operation by installing a jumper between the H terminals on the control board you must remove the jumper wire placed between terminals H1 H2 on the control board 5 3 End of Season...

Page 9: ...at care is taken not to damage bend or break the atomizing posts 7 Remove the cover from the electrical box and unwire the line cord and humidistat wires from the terminals It is not necessary to remo...

Page 10: ...logged solenoid valve or flow restrictor c Leaking reservoir d Bad control board 2 Red LED blinking repeatedly 1 second On 1 second OFF Unit will not function B Float switch not closing in 30 minutes...

Page 11: ...ler tube Motor will not operate turn Motor internal thermal protective device is open Remove power and allow motor to cool Restart unit and ensure proper operation If motor will not turn replace motor...

Page 12: ...1 19 G 109 G 109 SOLENOID VALVE ASSEMBLY 1 20 165001 001 PUSH TO LOCK MALE ELBOW 1 4 X 1 8 NPT 1 21 265305 001 FILL FITTING 1 8 NPT 2 22 166129 001 SCREW 8 X 3 8 PH PH THRD CUT SST 7 23 265378 220 SC...

Page 13: ...SHOWN 2 54 266793 001 FEMALE THREADED STANDOFF 1 55 266455 001 CONTROL BOARD BRACKET RH 1 56 266455 002 CONTROL BOARD BRACKET LH 2 57 266792 001 LOCKNUT PG9 1 58 266826 001 INLET RING 1 59 265442 001...

Page 14: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 14 www trioniaq com See Note 2 on page 13...

Page 15: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 15 www trioniaq com...

Page 16: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 16 www trioniaq com...

Page 17: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 17 www trioniaq com...

Page 18: ...Form No 265631 001 rev 01 15 2013 Trion 2013 All Rights Reserved Trion 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com...

Reviews: