Comfort
BREEZE
TM
Model CB707
I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
5
www.trioniaq.com
3.3 Unit Specifications
Type of Unit
Centrifugal Atomizing
Mounting
Return Duct/Wall/Table-top/Ceiling
Capacity (GPD)
6 GPD, 2 Lbs./Hr., 0.9 Kg/Hr.
Water Supply
20-80 PSI (138-552 KPa)
Voltage(Amps)
120VAC(0.8A), 220VAC(0.4A)
Unit Dimensions
11”"W x 9.5" D x 12" H
279mm W x 241mm D x 305mm H
Water Connection
1/4” (6.35 mm) OD Tubing
Overflow Connection
1/2” (12.7 mm) ID Tubing
Ducted Connection
3” Diameter (76 mm)
Shipping Weight
12.75 Lbs. (28 Kg)
Operating Weight
9 Lbs. (19.8 Kg)
Approvals
ETL (US & Canada) CE (220V)
4. Installation
Prior to installing this product:
•
Read the instructions carefully and completely to ensure
safe operation. Failure to follow the instructions could lead
to damage to the product or cause a hazardous condition.
•
Check the ratings given on the product to make sure it is
suitable for your application.
Remember to select a location that is readily accessible for peri-
odic inspection, cleaning, and service. The following table indi-
cates the minimum allowable installation clearances.
4.1 Clearances
Left
2”
Right
2”
Top
5”
Bottom
0” (for surface mounting)
Back
2”
CAUTION
Trion recommends that this humidifier be installed by a
trained HVAC professional. Do not connect the unit to the
power source until the installation is complete. A thorough
checkout of the unit installation should be completed before
operating the unit. Failure to follow these directions may void
the manufacturer’s original warranty.
4.2 Selecting A Location
The ComfortBREEZE CB-707 Humidifier may be mounted di-
rectly to the return duct of your HVAC system with the discharge
entering the ductwork, it may be wall-mounted for atmospheric
dispersion, it may be hung from a ceiling (mounting hardware
not included for this type of installation), or it may be simply
mounted to a shelf. An indicating LED is located on the oposite
side of the base from the plumbing and electrical connections.
Ensure that this LED is visible, if desired, when selecting a
mounting location.
When mounting the humidifier on the face of a horizontal return
duct or on the face of a vertical return duct, certain conditions
must be met to ensure proper unit operation.
•
Ensure that the duct surface is reinforced, if necessary, to
allow the unit to remain level and plumb.
•
Locate the humidifier at least four (4) linear feet upstream of
either the furnace fan and/or filter and any turn in the duct.
This will ensure that moisture does not accumulate in the
duct that may cause leakage, corrosion, or mold growth.
•
Mount the humidifier at least six (6) linear feet (preferably
10 feet) upstream of any electronic air cleaner. Failure to
follow this recommendation may result in excessive arcing
or power supply failure in the air cleaner.
•
If the duct seams inside the duct are not flat, locate the hu-
midifier at least three (3) linear feet upstream of the seam.
•
If the humidification needs of the space require more than
one humidifier, each unit should be installed a minimum of
three (3) linear feet apart.
•
DO NOT use this humidifier on the discharge or warm air
supply side of a forced air heating system. This will reduce
the efficiency of the humidifier and may cause additional
operational problems.
•
DO NOT mount the humidifier in a furnace jacket.
•
DO NOT install the humidifier where freezing conditions
could occur.
•
DO NOT install on gravity hot air systems.
4.2.1 Wall Mounting The Humidifier
Figure 1
1.
Referring to figure 1, using the mounting template, mark
the mounting holes on the wall. Ensure that the mounting
screws will penetrate wall-studs.
2. While holding the template against the wall, check with a