
www.trioniaq.com
ATS Series
2
I n s t a l l a t i o n , O p e r a t i o n , & S e r v i c e M a n u a l
Installation
Unpack and Inspect
At the time the unit is received, all shipping containers
and their contents should be examined for damage. Any
damage occurring in shipment must be immediately
reported to the carrier, an inspection report completed
and a claim filed at the receiving point.
The unit modular sections are shipped completely
assembled and joined and, where size permits, the
electronic air cleaner ionizing-collecting cells are
shipped inside the cabinet. On large units, the upper
tier of cells may be shipped in separate containers.
The Control System, detergent feeder and other
separate accessories are shipped in the containers
as noted on the packing list.
Position Air Cleaner Cabinet
If necessary, to remove weight for ease in handling,
the filtration elements can be removed from their
respective cabinets. Position the unit in the designated
location giving consideration to the following points.
• Excluding the exhaust fan section, there are
access doors on one side of the section modules.
Provide sufficient clearance (39”
minimum
) in
front of the doors on at least one side for service
and element removal.
• Level the unit to ensure proper drainage from the
drain pans. After the cabinet has been properly
located, it must be secured in place by bolting or
welding. Reinstall any section elements removed
during installation.
Make sure air flow direction
is correct.
INSTALLATION WARNING
Precautions must be taken to protect
the ATS System and its subsystems
if it is installed outdoors or in extreme
environments. Condensation, freezing, and
elevated temperatures must be considered.
CAUTION
In addition to the previous space requirements,
installation of the Model ATS in NFPA
applications shall have a clearance of at least
18 inches to a combustible material, 3 inches
to limited combustible material, and 0 inches
to noncombustible material. Any reduction in
clearance or exceptions must be in compliance
with NFPA and acceptable to the Authority
Having Jurisdiction.
WARNING
Fire Suppression Systems
Extreme caution should be exercised when this
unit is installed in applications that are collecting
volatile or potentially flammable contaminates
such as cooking grease and petroleum based
oils. TRION strongly recommends a fire
suppression system be installed in the ductwork
and on the Model ATS in cases where these
contaminates are collected on the cell plates
and collect on the attached ductwork. Contact
the factory for questions or concerns regarding
a fire suppression system.
WARNING
Motor/Starter Disconnects – UL Listing
To maintain agency listing on this equipment, all
customer provided Combination Motor Starter/
Disconnects shall be UL Listed (NLDX) and
utilize at least a UL type 1 enclosure.
Connect Adjoining Duct Work
When the adjoining ducting is installed on the air en-
tering side, the bottom of the horizontal duct should be
relatively flat and sloped toward the section housing
drain pan for an 18-inch length. This will enable any
wash water splashback occurring during the washing
operation to run back into the drain pan. Secure the
adjoining ducting to the section housing utilizing the
.375” holes provided. The seams should be made air
and watertight by caulking or gasketing. Upstream
ducting conveying warm air and subjected to cold
temperatures must be insulated to prevent excessive
condensation.