background image

www.trioniaq.com

the volume and counter clockwise decreases the 

volume. When adjustment has been made, be 

sure to retighten the set screw.

System

Detergent Required

ATS-2

.2

ATS-4

.4

ATS-6

.63

ATS-8

.91

ATS-10

1.2

ATS-12

1.4

 

Programming Time Clock for Automatic Wash

General Information

The panel-mounted digital timer 

series included with the ATS 

Control can be operated in four 

separate power supplies, ranging 

from 240 VAC to 12 VDC.  Output 

format can be produced to be volt-

free or voltiac-output.  Batteries of 

lithium CR2032 or rechargeable 

V80H are optional for retaining the programming during 

timer’s disconnected operating power.

The digital timer is accurate to the minute, designed 

with either six or eight ON/OFF (events) per day.  It 

also provides 15 combinations of daily programs 

which can lead great convenience to users upon 

choosing the required days in a week for operating 

the timer.

Programming Functions

•  TIMER: Programs review and setting programs

• 

MANUAL: To select “ON, AUTO, or OFF”

•  CLOCK: To adjust current DAY and TIME

•  DAY: To adjust day of week

•  HOUR: To adjust hour

•  MIN: To adjust minute

•   P : Reset timer’s setting

•  LED: To indicate ON/OFF status

Press  P  button to reset timer before programming.

Adjusting Clock

Press and hold CLOCK and then press DAY key, HOUR 

key, MIN key respectively to adjust clock of timer to 

ATS Series

9

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   S e r v i c e   M a n u a l

accurate DATE, HOUR, MINUTE.  In 12-hour format, 

PM and AM shall appear on LCD screen.  In 24-hour 

format, LCD screen shall indicate 0:00 - 23:59.

Programming the Timer

1.  Press TIMER key.  LCD screen shall show 1

ON

.

2.  Press DAY key to select any of the 15 combinations 

of daily programs to your application demand.  

Continuing to press DAY key will cause the LCD 

screen to alternate among 15 combinations.

3.  Press HOUR and MIN respectively to set desired 

hour and minute for 1

ON

.

4. 

After finished setting 1

ON

, press TIMER key again.  

1

OFF

 should appear on the LCD screen.

5.  Press DAY key to select any of the 15 combinations 

of daily programs to your application demand.  

Continuing to press DAY key will cause the LCD 

screen to alternate among 15 combinations.

NOTE: Day combinations chosen in each of the ON/

OFF program periods must be consistent. The OFF 

time will need to be one minute after the programmed 

ON time.

6.  Repeat programming procedure 3 to set desired 

hour and minute for 1

OFF

.

7. 

When finished setting 1

ON  

and 1

OFF

,  press  TIMER.  

2

ON 

shall appear on LCD screen.

8.  Repeat programming procedure above to complete 

the rest of ON/OFF program period event or just to 

the desired number of ON/OFF (event) setting for 

demand of practicable application.

9.  When  finished  program  setting  (event),  press 

CLOCK.  Timer shall start to execute programs.

Reviewing Programs

Keep pressing TIMER, and the display on the LCD 

screen shall alternate display among each of 6 or 8 

ON/OFF events.

Using Override Functions

Timer is designed with two override functions to widen 

its usage among practicable applications.  Override 

function is only effective when timer is running in 

AUTO mode.

Temporary Override

Condition 1: When timer’s output status is ON, press 

MANUAL key to move indicator from AUTO to OFF.  Timer 

X

X

Summary of Contents for Air Boss ATS Series

Page 1: ...T R I O N w w w t r i o n i a q c o m Air Boss ATS Series Electrostatic Precipitators Commercial Industrial Applications READ AND SAVE THESE INSTRUCTIONS ...

Page 2: ...tion 2 Operation 5 Initial Startup 8 Routine Maintenance 10 Preventative Maintenance 10 Troubleshooting 11 Troubleshooting Chart 13 Spare Parts 14 SAFETY NOTE Factory designed access to all electrically charged high voltage components contain electrical interlocks for the safety of operating personnel Any additional access that may be provided in the system where there is access to high voltage mu...

Page 3: ...ments Condensation freezing and elevated temperatures must be considered CAUTION In addition to the previous space requirements installation of the Model ATS in NFPA applications shall have a clearance of at least 18 inches to a combustible material 3 inches to limited combustible material and 0 inches to noncombustible material Any reduction in clearance or exceptions must be in compliance with N...

Page 4: ...TE LOCAL CODES High Voltage Wiring The high voltage wiring requires connecting the power supplies to the ionizing collecting cells located in the electronic air cleaner section cabinet On multicell units the wiring between the cells within a tier is automatically made with intercell spring contacts Two high voltage wires must be connected to each tier of cells in the ATS one for the ionizers and o...

Page 5: ...eriodicalmanualfillingofthedetergenttank and to gain access to the pump and motor assembly After positioning the unit must be secured in place The Detergent System should not be installed more than 30ft below the ATS System Local disconnect is recommended for detergent tank motor Note TRION Tridex Detergent is specially formulated for use with TRION electronic air cleaners Use of other cleaners an...

Page 6: ...matter from the air The modular sections can be built in several widths and heights to accommodate different air flow requirements Refer to the System Outline drawing for information on the specific system design for this project The first section the prefilter is primarily designed for capturing relatively large liquid particulate The second section houses an electronic air cleaner technically kn...

Page 7: ...panels have become saturated or fully loaded they may be replaced with new or reactivated carbon The fifth section the Exhaust Fan Motor has been sized to handle the air flow requirements for the systems and the adjoining ducting Fire Suppression System OPTIONAL When the fire suppression system has been specified to be factory furnished it consists of strategically located chemical spray nozzles D...

Page 8: ...ve fire suppression capabilities Some contaminate is harder to remove and may require a stronger detergent solution Average settings have been factory set Best possible settings for any given installation however are determined through experience Visually examine the collecting elements after the first few washings Control System The control system is custom configured to support the ATS System de...

Page 9: ...ieces of foreign material are lodged between the plates Also verify that the cells are properly installed in the cabinet with the spiked ionizing blades located on the air entering side Follow the air flow directional arrows Check that the high voltage wiring is connected to the proper terminals both at the ionizing collecting cells and on the power supplies Be sure that the drain lines from the d...

Page 10: ...n In 24 hour format LCD screen shall indicate 0 00 23 59 Programming the Timer 1 Press TIMER key LCD screen shall show 1ON 2 Press DAY key to select any of the 15 combinations of daily programs to your application demand Continuing to press DAY key will cause the LCD screen to alternate among 15 combinations 3 Press HOUR and MIN respectively to set desired hour and minute for 1ON 4 After finished ...

Page 11: ...ervoir level should be checked on a routine basis a minimum tank level established Never let the tank run dry which will damage the pump The inside of the tank should be kept clean free from dirt and foreign objects The detergent as supplied by TRION is formulated specifically for electronic air cleaners and should not be diluted when using a pre mix solution For a concentrated mix dilution will b...

Page 12: ...ell Alvania 2 Texaco Multifac 2 or Mobilux 2 At this time examine the exhaust fan for any accumulated dirt and clean as required Troubleshooting WARNING EXERCISE THE USUAL PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE THE MAXIMUM OPERATING OUTPUT FROM THE POWER SUPPLY IS 5 5MA 11 0MA WHEN CONNECTED IN PARALLEL AND 15 000VDC IF DOOR INTERLOCK SWITCHES ARE CLOSED AND CIRCUIT IS ENERGIZED DO NOT TOUCH H...

Page 13: ...to a single cell or ionizing or collector section of a given cell as follows First determine if the short is in the ionizing section or the collecting section by connecting each high voltage lead to its respective section one at a time and energizing the power pack The lead not connected must be supported away from any point of contact The short symptoms will still exist for the section in which t...

Page 14: ...switch Extremely dirty insulators Clean Cracked insulators Replace Foreign object between plates Remove Bent or warped plates Repair or replace cell Leads grounded short circuit Replace Indicating light flickering Reversed high voltage leads Reconnect leads Poor filtration Loose or defective intercell connection on multicell units Tighten or replace Foreign object adrift in ionizer or plate sectio...

Page 15: ...llation For specific recommendations consult the TRION factory or nearest Sales Office Consideration however should be given to stocking the following components Description Quantity Complete Power Supply 1ea Power Supply Indicating Light 1ea Ionizing Collect Cell Insulator 6ea TRION Detergent 55gal Part numbers are not listed as they are subject to change Always state Unit Model and Serial Number...

Page 16: ...TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com TRION 2017 All Rights Reserved Form No 147207 001 Rev 09 17 ...

Reviews: