TMCM-1311 TMCL Firmware V1.11 Manual (Rev. 1.17 / 2015-NOV-05)
32
www.trinamic.com
5.7.8
RSAP (restore axis parameter)
For all configuration-related axis parameters non-volatile memory locations are provided. By default, most
parameters are automatically restored after power up. A single parameter that has been changed before can
be reset by this instruction also.
Internal function:
the specified parameter is copied from the configuration EEPROM memory to its RAM
location.
Relate commands:
SAP, STAP, GAP, and AAP
Mnemonic:
RSAP <parameter number>, 0
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
8
<parameter number>
<motor>
0*
don’t care
* Motor number is always O as only one motor is involved
Reply structure in direct mode:
STATUS
VALUE
100 – OK
don’t care
For a table with parameters and values which can be used together with this command please refer to
chapter 6.
Example:
Restore the maximum current of motor
Mnemonic:
RSAP 6, 0
Binary:
Byte Index
0
1
2
3
4
5
6
7
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Value (hex)
$01
$08
$06
$00
$00
$00
$00
$00