TS4 连接器安装手册 TS4 Connector Installation Manual

 

 

12 

 

           

 

将剥好线的线芯插入金属端子铆接孔内,需确保所有芯线都在孔内。保证金属件和电

缆线的同轴度。最后按下铆接工具手柄,一直按到底,完成铆接。铆接后线缆拉力参

照下表。铜丝都要被包扎。

 

Insert  stripped  cable  into  the  rivet  hole  of  the  metal  terminal,  and  make  sure  all  the 

individual strands are in the hole. Ensure the coaxially  of metal parts and cables. Finally, 

press  the  riveting  tool  handle  and  press  it  to  the  end  to  complete  the  riveting.  The  cable 

tension after riveting is referenced to the following table. All individual strands should be 

bandaged. 

线缆规格

 

Cable specifications 

拔出力

 

Cable pull-out force 

4.0mm

2

 / 12AWG 

≥312N 

6.0mm

2

 / 10AWG 

≥356N 

10.0mm

2

 / 8AWG 

≥401N 

 

下方图例为铆接好的插针插套

The picture below are riveted pins and sockets 

                 

 

 

压接钳(

70930051

)根据不同规格线缆,需要先调节到相应的档位。

 

According to different specifications of the cable, you need to adjust to the corresponding gear of 

Summary of Contents for 70900350

Page 1: ...TS4 TS4 Connector Installation Manual 1 File No TS IM TS4 1 Version 01 Date 2017 12 18...

Page 2: ...6 3 Product Selection Form 7 4 Connector Appearance Size Drawing 7 4 1 Positive Connector 7 4 2 Negative Connector 8 5 Installation 9 5 1 Requirements of Tools 9 5 2 Assembly Steps 11 6 Connecting an...

Page 3: ...s event in the situation of self assembly no guarantee can be given as to safety or conformity with the technical data Do not modify the product in any way 1 1 2 Connector must be mated with connector...

Page 4: ...core double insulation and insulating material is XLPE Trina prohibits the use of either untinned cable PVC cables otherwise Trina Solar will disclaim any responsibility 1 3 2 Unmated plug connectors...

Page 5: ...wed to be stored with the affected chemicals The plug connectors should be installed in one year 1 3 6 Trina Solar has the rights to make certain correction for the printing errors improvements and in...

Page 6: ...ed impulse voltage 16KV Ambient temperature range 40 85 Contact resistance 0 5m Application degree Class A Protection class Class Pollution degree 2 Degree of Protection IP68 1m 1h mated IP2X unmated...

Page 7: ...42 4 7 6 0 4 0 6 0 12 10 70930046 70930047 70900354 TS4 M1 70930041 TS4 F2 70930085 5 6 6 8 TS4 M2 70930084 TS4 F3 70900351 6 0 6 6 TS4 M3 70900350 TS4 F4 70930044 6 0 7 2 TS4 M4 70930043 TS4 F5 70930...

Page 8: ...TS4 TS4 Connector Installation Manual 8 4 2 Negative Connector TS4 M1 TS4 M2 TS4 M3 TS4 M4 TS4 M5 TS4 M6...

Page 9: ...llation Manual 9 5 Installation 5 1 Requirements of Tools 5 1 1 Wire Stripper 70930046 70930049 70930046 70930049 P N Jaw Crimping Range 70930046 Middle 4 0mm2 12AWG Right side 6 0mm2 10AWG 70930049 R...

Page 10: ...47 P N Jaw Riveting Range Picture 70930047 Middle 4 0mm2 12AWG Right side 6 0mm2 10AWG 70930051 Adjustable 4 0 6 0 10 0mm2 8AWG 5 1 3 Plastic Spanner 1 set 2 pc P N 70900354 5 1 4 Tool Box P N 7093004...

Page 11: ...the insulating layer of cable L 6 0 5mm Be attention and not to cut off the individual strands 5 2 2 Inserting pin and socket 70930047 70930051 Place the metal terminal in the hole of the riveting too...

Page 12: ...eting tool handle and press it to the end to complete the riveting The cable tension after riveting is referenced to the following table All individual strands should be bandaged Cable specifications...

Page 13: ...2AWG TS4 F5 TS4 M5 6 6 0mm2 10AWG 8 10 0mm2 8AWG TS4 F6 TS4 M6 5 2 4 Pushing pin Insert the crimped on contact into the insulator until they engage Pull gently on the lead to check that the metal part...

Page 14: ...6 6 8mm TS4 F3 M3 6 0 6 6mm TS4 F4 M4 6 0 7 2mm TS4 F5 M5 7 2 8 7mm 1 0 X 1 8mm TS4 F6 M6 1 Note 1 Ensure the concentricity of cable and cable nut when you screw cable nut 2 pin Note 2 Make sure the n...

Page 15: ...er when it connected 7 Cable 7 1 Connection of Cable 20mm In order to avoid the cable sealing element deformation that a force generated by bending the wire the cable need keep at least 20mm straight...