www.trikdis.com
18
May, 2019
RF transmitter T16
“Module 1” tab
It is possible to connect a
TM17
reader to the
T16
transmitter. After connecting the
TM17
reader, the
transmitter can be used as a security control panel. Up to 9 contact (iButton) keys can be assigned to the
reader (one of which is the “Master key”) for controlling the security system’s state (armed/disarmed).
Dkey 1 – Dkey 9
– enter identification numbers of contact (iButton) keys.
Sound level
– enter the reader’s audio signal strength level (from 0 to 100).
3.4.1
Adding contact (iButton) keys
1.
If the list of contact keys is empty, the first key held against the reader is added, saved to the first line
of the list and becomes the
Master key
.
2.
To turn on contact key registering mode, you need to hold the
Main key
against the key reader for
at least 10 seconds. The “State” indicator will turn off. When registering mode is turned on, the LED
indicator on the
TM17
reader will begin blinking in green and an audio signal will be played.
3.
Hold the key you want to register against the reader. The reader’s audio signal will switch off. The
key is now added to the list. Remove the key from the reader. The green indicator on the reader will
stop blinking and will light up in solid green. After a few seconds the reader automatically exits key
registering mode. The “State” indicator lights up in green and the green LED on the reader switches
off.
4.
To add another key, enter key registering mode again.
5.
To delete all keys (including the main key), hold the
Main key
against the reader for no less than 20 s.
3.4.2
Using the transmitter as a security control panel
After connecting the
TM17
reader, the transmitter can be used as a security control panel. Contacts of
security sensors can be connected to the transmitter’s inputs (IN1 – IN6).
Default settings of inputs (IN) and output (OUT)
Terminal
Description
IN1
1
st
input terminal, selectable types: NC, NO, EOL (2,2 kΩ). (default setting NO).
Delay zone. Right after the alarm system is armed, the zone can be violated during the exit
time. If the zone remains violated after the exit time, an output OUT1 signal will be formed
and a message will be sent.