RF transmitter T16
“Events” tab
Enabled
– tick the box to turn on the sending of internal events:
o
Sleep mode
– power supply voltage less than 10 V.
o
Low battery
– power supply voltage less than 11,5 V.
o
Configuration change
– change in transmitter’s configuration.
o
RS485 error
– problem with devices connected to the RS485 bus.
o
Panel lost
– lost connection between transmitter and security panel.
o
Power ON
– power turned on for the transmitter.
o
Special
– usage of special code in the radio network, when a radio signal repeater with “listen”
and “cancel” modes is used.
o
Test
– periodic test message.
o
Open/Close
– for sending Open/Close messages when the TM17 reader is used.
o
Power supply failure
– power supply failure event is sent when the DC power source voltage is
less than 11,5 V when sending messages.
Radio frequency 1
– internal event codes that will be sent using the first radio channel after event
trigger and restore.
Radio frequency 2
– internal event codes that will be sent using the second radio channel after event
trigger and restore.
“Periods” tab
Test period
– specify the time interval between two test messages using the 1st and 2nd channels.
The purpose of periodic tests is to periodically inspect the functionality of radio systems. A typical