RF transmitter T16
2.2
Schematic for connecting security control panel’s landline dialer
IMPORTANT:
T16
should not be connected to a working telecom landline
.
Referring to the control panel’s programming instructions, set the following parameters for the control
panel’s landline dialer:
Enter the control panel’s 4-symbol identification number (account number, 0-9, A-F);
Enter the 2-symbol cellular receiver number that the panel will call when an event occurs (e.g.: 12).
If the panel’s TLC programming rule requires, enter a number end symbol at the end of the number;
Set the method of relaying messages to DTMF tones;
Set the automatic message transfer protocol Contact ID.
If you want to transfer special messages or the panel does not have automatic Contact ID code
formatting, manually enter the required event codes.
Form a panel message and check the operation of the interface. Blinking of the DATA indicator will show
when the transmitter is reading the panel’s messages.
Check to make sure that the transmitter correctly sent all of the control panel’s messages formed during
the test to the set recipient.
2.3
Schematics for connecting inputs
The transmitter has 6 input terminals (IN1, IN2, IN3, IN4, IN5, IN6) for connecting NO, NC, EOL type circuits.
The factory settings for all of the inputs is NO type. The input circuit type can be changed in the
TrikdisConfig
window
Reports → Inputs
.
Schematics for connecting NO, NC, EOL type circuits: