Inverter Trienergia SunUno Plus Series
- 39 -
E-today 0.05kWh
P-ac 3210W
Peripheral
>Self Test
ENT
ENT
ENT
>9 All test
ENT
All test [0]
[0] result
All test [1]
[1] result
9 All test
Please Wait...
Tests passed!
ENT
All test
Note:
1.This setting only appears when the grid compliance selects Italy.
2.This setting shall be operated when the inverter is under normal grid-connected
state.
3.“All test” is starting from the item 1 to item 8 of the autotest.
4.The self test information could be reviewed after successful setting.Self test
from item 1 to item 8 could only show the test results of each item respectively.
By “All test”, all test results from item 1 to item 8 could be checked all at once. as
example:
over-voltage protection test
E-today 0.05kWh
P-ac 3210W
Peripheral
>Self Test
ENT
ENT
ENT
ENT
>1 Ovp(59.S2)
2 Ovp10(59.S1)
ENT
Ovp(59.S2) [0]
[0] result
1 Ovp(59.S2)
Vt264.5V Tt200ms
Vs230.7V To190ms
Vo230.2V Pass
2018/6/28 8:00