(3) Feed the positive and negative cables into corresponding lock screws.
(4) Put the metal positive and negative terminals into positive cable and
negative cable whose insulated enclosure has been stripped, and crimp them
tightly with a wire crimper. Make sure that the withdrawal force of the pressed
cable is bigger than 400N.
(5) Plug the pressed positive and negative cables into relevant insulated
enclosure, a “click” should be heard or felt when the contact cable assembly is
seated correctly.
(6) Fasten the lock screws on positive and negative connectors into respondent
insulated enclosure and make them tight.
(7) Connect the positive and negative connectors into positive and negative DC
input terminals of the inverter, a “click” should be heard or felt when the
contact cable assembly is seated correctly.
1. Connection Port
Figure 5.10 Connect the Inverter
NOTICE
· Before inserting the connector into the DC input terminal of the inverter, please make sure
that the DC switch of the inverter is open (OFF).