Product manual EM converterLED ST | 08-2018 | 1.0 | en

Functions in emergency operation

c

17 / 38

5.4. Indicator LED

System status is locally indicated by a bi-colour indicator LED.

LED indication

Status

Description

Permanent GREEN

Standby, System OK

Mains operation, battery is charged

Fast flashing GREEN
(0,1 s on - 0,1 s off)

Function test underway

 

Slow flashing GREEN
(1 s on - 1 s off)

Duration test underway

 

Double pulsing
GREEN

Inhibit mode is
activated

The Inhibit mode makes it possible to set the emergency mode to "inhibited"; in this
mode, the power can be turned off without switching to emergency mode.

The Inhibit mode is activated by sending the inhibit signal, while the modules are still
connected to mains. Just as in Rest mode, the device supports the Relight functions.
After a break of 15 minutes, the inhibit mode is automatically reset.

Permanent RED

Lamp failure

Open circuit -or- Short circuit -or- LED failure

Fast flashing RED
(0,1 s on - 0,1 s off)

Charging failure

Incorrect charging current

I

NOTICE

After an exchange of the LED module, the indicator LED remains permanent
RED. The lamp failure indication remains set until a function test has been
successfully completed (automatically with the weekly function test or
immediately by briefly interrupting the power supply or by manually starting
the function test with a test switch (see 

)). 

Starting the function test

, p. 23

The LED module's mains operation does not reset the lamp failure indication.

I

NOTICE

While the battery is in trickle charge mode and the mains supply is connected,
the micro controller in the emergency unit monitors the charging parameters. If
an error is detected or a parameter is out of tolerance, the indicator LED
switches to fast flashing RED. If the error has been corrected, the indicator LED
immediately switches back to GREEN and continues the charging operation of
the battery.

Summary of Contents for EM converterLED ST

Page 1: ...8 2 1 7 5 3 4 1 8 3 3 4 2 0 9 ø 4 5 3 3 8 2 1 7 5 5 1 7 3 4 1 8 3 8 2 3 4 2 0 9 1 7 5 3 4 1 8 3 ø 4 5 4 1 8 2 3 4 2 0 9 1 7 5 5 1 7 5 3 4 1 8 3 ø 4 5 3 3 8 2 3 4 2 0 9 LED Driver EM converterLED ST Product Manual ...

Page 2: ...ustable output current 10 Intelligent multilevel charging system 13 Rest mode Inhibit mode and Relight command 14 Indicator LED 17 Settings for Emergency tests 19 Test times and test intervals 20 Commissioning test 20 Weekly function test 21 Annual duration test 22 Adaptive test mode 22 Functionality of the test switch 22 Determining light output in emergency operation 24 Parameter 1 LED forward v...

Page 3: ...roduct manual EM converterLED ST 08 2018 1 0 en Table of Contents c 3 38 Installation notes 35 Safety information 35 Routing the wires 36 Reference list 38 Related documents 38 Additional information 38 ...

Page 4: ...be changes in shape features and technology Claims can therefore not be made on the basis of information diagrams or descriptions in these instructions The latest version of these operating instructions is available on our home page at http www tridonic com com en operating instructions asp 1 2 Copyright This documentation may not be changed expanded copied or passed to third parties without the p...

Page 5: ...y supplied emergency lighting The device may only be used for this intended purpose 2 1 2 Improper use Outdoor use Extensions and modifications to the product 2 2 Dangers associated with the operation of the system 2 3 Environment WARNING Improper use could result in injury malfunction or damage to property It must be ensured that the operator informs every user of existing hazards DANGER Danger o...

Page 6: ...2 4 Additional instructions CAUTION Electromagnetic compatibility EMC Although the device meets the stringent requirements of the appropriate directives and standards on electromagnetic compatibility it could potentially interfere with other devices under certain circumstances ...

Page 7: ... selftest version ST of the portfolio The PRO version is covered in a separate documentation see Reference list p 38 3 2 Testing of emergency systems There are statutory requirements covering the testing of emergency systems in buildings accessible to the public This includes that testing must be carried out at a time of minimum risk normally during unsocial hours and must allow time for the batte...

Page 8: ... in a low profile housing 21mm Image Description Housing variant compact 4 2 Forward voltage The EM converterLED ST is available with three different forward voltages 10 52 V 40 97 V 50 200 V Compact shape _ For installations inside the luminaire _ Typical area of application Spotlights downlights _ Dimensions 179 30 21 mm _ ...

Page 9: ...Function test interval weekly Duration test interval annual Rated duration Adjustable to 1 or 2 hours Status display Via two colour indicator LED p 17 Battery charge system Intelligent multilevel charging system p 13 Intermittent charging pulse charging for NiMH batteries Adjustment of output current p 10 Automatic adjustment by device Commissioning Automatic Rest mode Inhibit mode and Relight com...

Page 10: ...ower ensures maximum light output in emergency mode for the specified operating time An EM converterLED ST with approx 3 4 or 5 watts output power operates the connected LED modules with the output power mentioned before For this purpose the device detects the connected LED forward voltage and adjusts the LED forward current to the appropriate value resulting in an output power of approx 3 4 or 5 ...

Page 11: ...ange SELV Number of battery cells EM converterLED ST 103 50V 10 52 V SELV 60 V 3 cells for light output in emergency operation EM converterLED ST 103 NiMH 50V 10 52 V SELV 60 V 3 cells for light output in emergency operation EM converterLED ST 104 50V 10 52 V SELV 60 V 4 cells for light output in emergency operation EM converterLED ST 104 50V NiMH 10 52 V SELV 60 V 4 cells for light output in emer...

Page 12: ...t in emergency operation EM converterLED ST 104 50V 50 200 V no 4 cells for light output in emergency operation EM converterLED ST 104 50V NiMH 50 200 V no 4 cells for light output in emergency operation EM converterLED ST 105 50V 50 200 V no 5 cells for light output in emergency operation EM converterLED ST 105 50V NiMH 50 200 V no 5 cells for light output in emergency operation I NOTICE There is...

Page 13: ...with an operating time of 1 hour and 15 hours for modules with an operating time of 2 and 3 hours Once the batteries are fully charged again the module automatically switches to trickle charge mode In trickle charge mode the battery status is continually monitored to ensure that the charging currents and battery voltages remain within the specified limits The status LED also shows such faults loca...

Page 14: ... different changes activating Rest mode and Inhibit mode and sending the Relight command DC voltage pulses of different lengths are used The table at gives an overview of all the operating modes Switching between operating modes p 16 5 3 1 Activate Rest mode Rest mode is activated as follows 5 3 2 Deactivate Rest mode via Relight command By sending the Relight command the Rest mode is deactivated ...

Page 15: ...se at the two terminal points REST L and REST N _ The signal of must have an amplitude 9 5 22 5 V with a pulse length of 1 001 2 000 ms _ The polarity of the voltage pulse does not matter _ I NOTICE Reapplying the power supply does also deactivate Rest mode In this case the device switches from Rest mode to charge mode Make sure that the mains supply is switched on _ Apply DC voltage pulse at the ...

Page 16: ... the device switches between these operating modes The following table gives an overview Applied pulse length Charging mode Emergency mode Rest mode Inhibit mode 150 1 000 ms Switches to Inhibit mode Switches to Rest mode 1 001 2 000 ms Relight command Switches to Emergency mode Switches to charging mode Apply DC voltage pulse at the two terminal points REST L and REST N _ The signal of must have ...

Page 17: ...ally reset Permanent RED Lamp failure Open circuit or Short circuit or LED failure Fast flashing RED 0 1 s on 0 1 s off Charging failure Incorrect charging current I NOTICE After an exchange of the LED module the indicator LED remains permanent RED The lamp failure indication remains set until a function test has been successfully completed automatically with the weekly function test or immediatel...

Page 18: ...icator LED is slow flashing RED After an exchange of the battery the indicator LED switches to GREEN To guarantee a satisfactory operating time the battery is then charged for 20 hours and a second duration test is carried out I NOTICE Battery is defect or incorrect battery voltage While the battery is in trickle charge mode and the mains supply is connected the micro controller in the emergency u...

Page 19: ...n to the power supply 2 Phase in which the power supply is switched on and off possibly numerous times 3 Phase in which the power supply is permanently connected no interruption for at least 5 days 4 Delaying the commissioning test for 1 28 day 5 Commissioning test begins 6 First function test 7 First duration test ...

Page 20: ...uminaire for a specified time 28 days after the start of the commissioning all devices will have completed the required commissioning test The day of the commissioning test serves as a reference point for all further function and duration tests see Test times and test Automatic setting of the function test The time of the function test is the same as the time when the device was first connected to...

Page 21: ...witched off which can take up to 24 hours the indicator LED shows that the test has not been carried out satisfactorily fast blinking GREEN If the function test detects a battery failure and the battery was not fully charged at the test time the device returns to charging mode and starts the function test a second time once the battery is fully charged _ I NOTICE In this case battery failure and b...

Page 22: ...ter the duration test before the room is in use again Room usage is monitored on a monthly basis and the time for the duration test is constantly adjusted This allows for seasonality in room usage to be taken into account If a suitable time cannot be found perhaps because the room is in use round the clock the duration test is performed at the time set during startup this is the time when the emer...

Page 23: ... indicator LED _ A longer press on the button 1 10 s switches the light source to emergency mode but does not perform a time controlled function test On release of the button the emergency units switch back to charge mode The indicator LED goes off for 1 second and then on for the rest of the time maximum of 9 seconds _ I NOTICE Resetting the timer deactivates the Because of this the test time is ...

Page 24: ... Parameter 1 LED forward voltage 7 1 1 Total forward voltage of all LED modules The forward voltage of a single LED module can be found in the data sheet When calculating the total forward voltage of all LED modules series and parallel circuits must be handled differently Series circuit Parallel circuit The values of the individual LED modules are summed up The total value is the same as the value...

Page 25: ...ency operation c 25 38 7 1 2 Example 1 1 LED module DLE Given Wanted Result Forward voltage DLE taken from data sheet 24 2 V _ Total forward voltage of all LED modules in emergency operation _ The total forward voltage of all LED modules is because there is only 1 LED module 24 2 V _ ...

Page 26: ...Given Wanted Result Forward voltage DLE taken from data sheet 24 2 V _ Total forward voltage of all LED modules _ The total forward voltage of all LED modules is V no addition of the values in a parallel circuit 24 2 _ I NOTICE As Example 2 shows parallel circuits make it possible to use multiple LED modules where the forward voltage does not add up ...

Page 27: ...on c 27 38 7 2 Parameter 2 LED current Each EM converterLED ST has a specific current voltage characteristic The corresponding current voltage curve can be found in the datasheet EM converterLED ST 103 50V EM converterLED ST 103 NiMH 50V EM converterLED ST 104 50V EM converterLED ST 104 NiMH 50V ...

Page 28: ...Product manual EM converterLED ST 08 2018 1 0 en Determining light output in emergency operation c 28 38 EM converterLED ST 134 NiCd 50V EM converterLED ST 104 90V EM converterLED ST 104 NiMH 90V ...

Page 29: ...ual EM converterLED ST 08 2018 1 0 en Determining light output in emergency operation c 29 38 EM converterLED ST 105 90V EM converterLED ST 105 NiMH 90V EM converterLED ST 104 200V EM converterLED ST 104 NiMH 200V ...

Page 30: ...battery voltage and max battery discharge current Knowing the total forward voltage of all LED modules the value for the LED current can be read from the current voltage curve The value of the LED current lies within this range The effective value depends on tolerances Mark the value of the total forward voltage of all LED modules on the x axis of the graph _ From that point move up vertically The...

Page 31: ...module DLE Given Wanted Result Figure Determining LED current for EM converterLED ST 103 50V Total forward voltage of all LED modules 24 2 V calculated before _ LED current _ The two crossing points are at around 85 mA minimum value and 111 mA maximum value _ The effective value of the LED current is between these two values _ ...

Page 32: ...rgency operation approx 85 mA minimum value and approx 111 mA maximum value taken from the previous example see Example 1 1 LED module DLE p 31 _ LED current in mains operation 750 mA taken from data sheet DLE G3 2000 lm Article number 89600574 _ Light output in mains operation 2 100 lm taken from data sheet DLE G3 2000 lm Article number 89600574 _ Light output in emergency operation _ Minimum lig...

Page 33: ...mportant to check that the rating of the LED Driver does not exceed the values specified below 8 3 Practical tests Practical tests are used to ensure fault free operation of the LED module and LED Driver The following aspects must be checked 8 3 1 Technical aspects 8 3 2 Visual aspects EM converterLED ST 50V 10 52 V _ EM converterLED ST 90V 40 97 V _ EM converterLED ST 200V 50 200 V _ Max allowed ...

Page 34: ...lowing conditions must be considered All tolerances _ Entire temperature range _ Different output voltage ranges incl no load _ Entire dimming range _ Short circuit _ I NOTICE If the values are slightly over or under the specified threshold values or if there are any other concerns or questions please contact Technical Support techservice tridonic com ...

Page 35: ...ons of the lamp manufacturer _ Observe all relevant standards Follow the instructions given in the standards _ WARNING Comply with the general safety instructions see Safety instructions p 5 _ To avoid failures due to ground faults protect the wiring against mechanical loads from sharp edged metal parts e g cable penetrations cable holders metal frames etc _ Electronic control gear from Tridonic a...

Page 36: ...rol gear with U 250 V out out For U 480 V the voltage for the type test is 2000 V out 9 2 4 Wiring Wiring guidelines I NOTICE The performance of the prescribed tests and compliance with relevant standards are the responsibility of the luminaire manufacturer The following descriptions merely indicate the most important tests and are no substitute for a full research of the relevant standards CAUTIO...

Page 37: ...iring the plug in terminal Release of the wiring Use solid wire with the correct cross section _ Strip off correct length of insulation you may need to twist the tool slightly _ Insert the bare end into the terminal _ Press down the push button and remove the cable from front _ ...

Page 38: ...terLED https www tridonic com com en download technical EM_converterLED_Product description_en pdf _ Brochure Emergency Lighting http www tridonic com com en download Emergency_Lighting_Overview_EN pdf _ EM converterLED current calculator https www tridonic com com en products converterled _ Data sheets http www tridonic com com en data sheets asp _ Company certificates http www tridonic com com e...