Product manual EM converterLED ST | 08-2018 | 1.0 | en
Settings for emergency tests
c
23 / 38
6.6.1. Starting the function test
6.6.2. Starting the test mode
6.6.3. Setting the test time
The time and day for the function and duration test is stored in the internal timer. To change the test time, the timer needs to be
reset. The previously stored test time will be deleted and replaced by the time of resetting.
The timer can be reset for one luminaire or for multiple luminaires:
Setting the test time for one luminaire
Setting the test time for all the luminaires in an emergency lighting circuit
...
I
NOTICE
The test switch can remain permanently connected and used as a startup tool.
A short press on the button (0.15 - 1 s) starts a function test lasting 5 seconds.
The indicator LED flashes GREEN.
The result of the function test is displayed on the two-colour indicator LED.
_
A longer press on the button (1 - 10 s) switches the light source to emergency mode but does not perform a time controlled
function test.
On release of the button the emergency units switch back to charge mode.
The indicator LED goes off for 1 second and then on for the rest of the time (maximum of 9 seconds).
_
I
NOTICE
Resetting the timer deactivates the
. Because of this, the test time is no longer adapted to the room
adaptive test mode
, p. 22
usage of the building. The function test and duration test is always carried out at the newly set test time.
Holding down the button (> 10 s) resets the timer.
The indicator LED goes off for 1 second and then shows GREEN and goes off again after 10 seconds.
By going off after 10 seconds the indicator LED confirms that the timer has been successfully reset (to the current time).
_
If the unswitched power supply of an emergency lighting circuit is switched on and off 5 times within 60 seconds, the timers
for all the emergency units in the emergency lighting circuit is reset (to the current time).
_