www.tridonic.com
2
Subject to change without notice. Information provided without guarantee.
Data sheet 10/20-EM090-8
Emergency lighting units
EM converterLED
EL
Technical data
Rated supply voltage
220 – 240 V
AC voltage range
198 – 264 V
Mains frequency
50 / 60 Hz
LED module forward voltage range
10 – 54 V
Output current
see chapter 5.3
Starting time
< 0.5 s from detection of emergency
event
Overvoltage protection
320 V (for 48 h)
U-OUT (including open- / short-circuit and
double load)
60 V
Max. open circuit voltage
60 V
Ambient temperature range ta
-25 ... +55 °C
Max. casing temperature tc
80 °C
Mains voltage changeover threshold
according to EN 60598-2-22
Mains surge capability (between L – N)
1 kV
Mains surge capability (between L/N – PE) 2 kV
Type of protection
IP20
Rest mode max. number of emergency
units
100
Rest mode max. wiring distance
1,000 m
Functional test
Weekly 5s test
Duration test
Yearly 1 h / 2 h / 3 h test
Life-time
up to 100,000 h
Dimensions LxWxH
179 x 30 x 21 mm
EM converterLED ST MH/LiFePO4 50 V
SELFTEST series
30
21
30
179
169.2
Position A
3 h
No duration
link 2 h
Position B
1 h
Note: LED Driver supplied with duration link in 3 hours position. Duration link must be set
before battery and mains connection.
Ordering data
Type
1
Article
number
Rated
duration
Packaging,
carton
Packaging,
pallet
Weight
per pc.
EM converterLED ST 202 MH/LiFePO4 50V
89800624
1/2/3 h 10 pc(s).
1,600 pc(s).0.07 kg
EM converterLED ST 203 MH/LiFePO4 50V
89800625
1/2/3 h 10 pc(s).
1,600 pc(s).0.07 kg
EM converterLED ST 204 MH/LiFePO4 50V
89800626
1/2/3 h 10 pc(s).
1,600 pc(s).0.07 kg
Test switch EM3
A
CCES
-
SORIES
Ordering data
Type
Article number
Packaging,
bag
Packaging,
carton
Weight
per pc.
Test switch EM 3
89899956
25 pc(s).
200 pc(s).
0.013 kg
Status indication bi-colour LED
A
CCES
-
SORIES
Specific technical data
Type
Battery
technology
Rated
duration
Typ. λ
(at 230 V,
50 Hz)
Typ. output
power
P emergency
Mains current in charging operation
Rated power in charging operation
Initial charge
Fast recharge
Trickle charge
2
Initial charge
Fast recharge
Trickle charge
2
EM converterLED ST 202
MH/LiFePO4 50V
NiMH
1 h
0.65C
1.5 W
15 mA
16 mA
15 / 11 mA
1.9 W
2.2 W
1.9 / 1.4 W
2 h
0.65C
1.5 W
19 mA
19 mA
19 / 11 mA
2.6 W
2.6 W
2.6 / 1.4 W
3 h
0.65C
1.5 W
19 mA
19 mA
19 / 11 mA
2.6 W
2.6 W
2.6 / 1.4 W
LiFePO
4
1 h
0.65C
1.5 W
15 mA
15 mA
15 / 11 mA
2.1 W
2.1 W
2.1 / 1.4 W
2 h
0.65C
1.5 W
19 mA
19 mA
19 / 11 mA
2.8 W
2.8 W
2.8 / 1.4 W
3 h
0.65C
1.5 W
19 mA
19 mA
19 / 11 mA
2.8 W
2.8 W
2.8 / 1.4 W
EM converterLED ST 203
MH/LiFePO4 50V
NiMH
1 h
0.7C
2.5 W
16 mA
18 mA
16 / 11 mA
2.1 W
2.6 W
2.1 / 1.4 W
2 h
0.7C
2.5 W
20 mA
20 mA
20 / 11 mA
3.1 W
3.1 W
3.1 / 1.4 W
3 h
0.7C
2.5 W
20 mA
20 mA
20 / 11 mA
3.1 W
3.1 W
3.1 / 1.4 W
LiFePO
4
1 h
0.7C
2.5 W
19 mA
19 mA
19 / 11 mA
2.8 W
2.8 W
2.8 / 1.4 W
2 h
0.7C
2.5 W
24 mA
24 mA
24 / 11 mA
3.8 W
3.8 W
3.8 / 1.4 W
3 h
0.7C
2.5 W
24 mA
24 mA
24 / 11mA
3.8 W
3.8 W
3.8 / 1.4 W
EM converterLED ST 204
MH/LiFePO4 50V
NiMH
1 h
0.7C
3.5 W
17 mA
20 mA
17 / 11 mA
2.3 W
2.9 W
2.3 / 1.4 W
2 h
0.7C
3.5 W
23 mA
23 mA
23 / 11 mA
3.6 W
3.6 W
3.6 / 1.4 W
3 h
0.7C
3.5 W
23 mA
23 mA
23 / 11 mA
3.6 W
3.6 W
3.6 / 1.4 W
LiFePO
4
1 h
0.7C
3.5 W
19 mA
19 mA
19 / 11 mA
2.8 W
2.8 W
2.8 / 1.4 W
2 h
0.7C
3.5 W
24 mA
24 mA
24 / 11 mA
3.8 W
3.8 W
3.8 / 1.4 W
3 h
0.7C
3.5 W
24 mA
24 mA
24 / 11 mA
3.8 W
3.8 W
3.8 / 1.4 W
1
EM = Emergency
2
In case of NiMH batteries: Intermittent charge is used. Value 1 is for 4 min. charge on / Value 2 is for 16 min. charge off. In case of LiFePO
4
batteries voltage dependent constant current charging is used.