background image

www.tridonic.com

2

Subject to change without notice. Information provided without guarantee.

Data sheet 10/20-EM090-8

Emergency lighting units

EM converterLED

   

EL

 

     

 

 

 

Technical data

Rated supply voltage

220 – 240 V

AC voltage range

198 – 264 V

Mains frequency

50 / 60 Hz

LED module forward voltage range

10 – 54 V

Output current

see chapter 5.3

Starting time

< 0.5 s from detection of emergency 
event

Overvoltage protection

320 V (for 48 h)

U-OUT (including open- / short-circuit and 
double load)

60 V

Max. open circuit voltage

60 V

Ambient temperature range ta

-25 ... +55 °C

Max. casing temperature tc

80 °C

Mains voltage changeover threshold

according to EN 60598-2-22

Mains surge capability (between L – N)

1 kV

Mains surge capability (between L/N – PE) 2 kV
Type of protection

IP20

Rest mode max. number of emergency 
units

100

Rest mode max. wiring distance

1,000 m

Functional test

Weekly 5s test

Duration test

Yearly 1 h / 2 h / 3 h test

Life-time

up to 100,000 h

Dimensions LxWxH

179 x 30 x 21 mm

EM converterLED ST MH/LiFePO4 50 V

SELFTEST series

 

30

21

30

179

169.2

Position A
   3 h

No duration 
link    2 h

Position B
   1 h

Note: LED Driver supplied with duration link in 3 hours position. Duration link must be set 
before battery and mains connection.

Ordering data

Type

1

Article 

number

Rated 

duration

Packaging, 
carton

Packaging, 
pallet

Weight 
per pc.

EM converterLED ST 202 MH/LiFePO4 50V

 

89800624

1/2/3 h 10 pc(s).

1,600 pc(s).0.07 kg

EM converterLED ST 203 MH/LiFePO4 50V

89800625

1/2/3 h 10 pc(s).

1,600 pc(s).0.07 kg

EM converterLED ST 204 MH/LiFePO4 50V

89800626

1/2/3 h 10 pc(s).

1,600 pc(s).0.07 kg

Test switch EM3

 

A

CCES

-

SORIES

 

Ordering data

Type

Article number

Packaging, 
bag

Packaging,
carton

Weight 
per pc.

Test switch EM 3

 

89899956

25 pc(s).

200 pc(s).

0.013 kg

Status indication bi-colour LED

 

A

CCES

-

SORIES

 

Specific technical data

Type

Battery 

technology

Rated 

duration

Typ. λ  

(at 230 V, 

50 Hz)

Typ. output 

power 

P emergency

Mains current in charging operation

Rated power in charging operation

Initial charge

Fast recharge

Trickle charge

2

Initial charge

Fast recharge

Trickle charge

2

EM converterLED ST 202  
MH/LiFePO4 50V

 

NiMH

1 h

0.65C

1.5 W

15 mA

16 mA

15 / 11 mA

1.9 W

2.2 W

1.9 / 1.4 W

2 h

0.65C

1.5 W

19 mA

19 mA

19 / 11 mA

2.6 W

2.6 W

2.6 / 1.4 W

3 h

0.65C

1.5 W

19 mA

19 mA

19 / 11 mA

2.6 W

2.6 W

2.6 / 1.4 W

LiFePO

4

1 h

0.65C

1.5 W

15 mA

15 mA

15 / 11 mA

2.1 W

2.1 W

2.1 / 1.4 W

2 h

0.65C

1.5 W

19 mA

19 mA

19 / 11 mA

2.8 W

2.8 W

2.8 / 1.4 W

3 h

0.65C

1.5 W

19 mA

19 mA

19 / 11 mA

2.8 W

2.8 W

2.8 / 1.4 W

EM converterLED ST 203  
MH/LiFePO4 50V

 

NiMH

1 h

0.7C

2.5 W

16 mA

18 mA

16 / 11 mA

2.1 W

2.6 W

2.1 / 1.4 W

2 h

0.7C

2.5 W

20 mA

20 mA

20 / 11 mA

3.1 W

3.1 W

3.1 / 1.4 W

3 h

0.7C

2.5 W

20 mA

20 mA

20 / 11 mA

3.1 W

3.1 W

3.1 / 1.4 W

LiFePO

4

1 h

0.7C

2.5 W

19 mA

19 mA

19 / 11 mA

2.8 W

2.8 W

2.8 / 1.4 W

2 h

0.7C

2.5 W

24 mA

24 mA

24 / 11 mA

3.8 W

3.8 W

3.8 / 1.4 W

3 h

0.7C

2.5 W

24 mA

24 mA

24 / 11mA

3.8 W

3.8 W

3.8 / 1.4 W

EM converterLED ST 204  
MH/LiFePO4 50V

NiMH

1 h

0.7C

3.5 W

17 mA

20 mA

17 / 11 mA

2.3 W

2.9 W

2.3 / 1.4 W

2 h

0.7C

3.5 W

23 mA

23 mA

23 / 11 mA

3.6 W

3.6 W

3.6 / 1.4 W

3 h

0.7C

3.5 W

23 mA

23 mA

23 / 11 mA

3.6 W

3.6 W

3.6 / 1.4 W

LiFePO

4

1 h

0.7C

3.5 W

19 mA

19 mA

19 / 11 mA

2.8 W

2.8 W

2.8 / 1.4 W

2 h

0.7C

3.5 W

24 mA

24 mA

24 / 11 mA

3.8 W

3.8 W

3.8 / 1.4 W

3 h

0.7C

3.5 W

24 mA

24 mA

24 / 11 mA

3.8 W

3.8 W

3.8 / 1.4 W

EM = Emergency

2

 

In case of NiMH batteries: Intermittent charge is used. Value 1 is for 4 min. charge on / Value 2 is for 16 min. charge off. In case of LiFePO

batteries voltage dependent constant current charging is used.

Summary of Contents for 89800624

Page 1: ...e changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Two colour status display LED Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by by 3 pole connector Automatic detection of the connected battery technology NiMH or LiFe...

Page 2: ...h 10 pc s 1 600 pc s 0 07 kg Specific technical data Type Battery technology Rated duration Typ λ at 230 V 50 Hz Typ output power P emergency Mains current in charging operation Rated power in charging operation Initial charge Fast recharge Trickle charge2 Initial charge Fast recharge Trickle charge2 EM converterLED ST 202 MH LiFePO4 50V NiMH 1 h 0 65C 1 5 W 15 mA 16 mA 15 11 mA 1 9 W 2 2 W 1 9 1 ...

Page 3: ...bag Packaging carton Weight per pc Test switch EM 3 89899956 25 pc s 200 pc s 0 013 kg Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Page 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Page 5: ... LED modules with a total forward voltage of 10 to 54 V can be connected to the EM converterLED These LED module s marked with Emer gency are operated in emergency mode from the associated battery In normal mains mode all LED modules are operated by the mains LED Driver Meaning of marking Double or reinforced insulation for built in electronic LED Drivers The control gear relies upon the luminaire...

Page 6: ...r LED Not connected Not connected Control gear LED LED Control gear Battery Battery LED Module Emergency EM converterLED SELFTEST with one LED module for non maintained emergency operation EM converterLED SELFTEST with a standard LED Driver and one LED module for mains and emergency operation EM converterLED SELFTEST with a standard LED Driver and series operation of LED modules One LED module is ...

Page 7: ...ol Un Switched Line Switched Line out EM ConverterLED SELFTEST One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED Driver supply 3 3 Battery co...

Page 8: ...nducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the emc performance of the luminaire The length of LED leads to the LED module must not be exceeded...

Page 9: ...EM converterLED ST MH LiFePO4 50V 90 130 130 130 180 260 260 260 10 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED REST Mains Switched Live Battery LED Test switch Indicator LED REST Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver i...

Page 10: ...tery discharge current tolerance EM converterLED ST 203 MH LiFePO4 50V Article number 89800625 NiMH battery 3 6 V battery voltage 890 960 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 770 830 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED ST 204 MH LiFePO4 50V Article number 89800626 NiMH battery 4 8 V battery volta...

Page 11: ...s commissioned will be reloaded in order to randomise the tests between adjacent units 5 4 LED Driver compatibility The EM converterLED emergency unit use 3 pole technology and is compa tible with most LED Drivers on the market however it is important to check that the rating of the LED Driver does not exceed the values specified below The max allowed output current rating of the associated LED Dr...

Page 12: ...CON 28002327 side by side 2 x 1 Accu LiFePO42B CON 28002319 side by side 4 x 1 Accu LiFePO44B CON 28002323 side by side 5 x 1 Accu LiFePO45B CON 28002326 Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is activated the discharging of the battery will be minimized by switching off the LED output If the Inhibit Mode has been ...

Page 13: ... emergency lighting LED Driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions EM converterLED ST 1 2 3 h LiFePO4 Type EM converterLED ST 202 MH LiFePO4 50V EM converterLED ST 203 MH LiFePO4 50V EM converterLED ST 204 MH LiFePO4 50V Article no 89800624 89800625 89800626 Duration 1 h 2 3 h 1 h 2 3 h 1 h 2 3 h Battery charge time Initial c...

Page 14: ...cles EM converterLEDs are tested with 50 000 mains switching cycles of the associated LED driver 8 2 Battery replacement After a battery replacement and a subsequent full charge cycle 24 h a duration test is mandatory to prove that with the new battery the rated duration is achieved 8 3 Additional information Additional technical information at www tridonic com Technical Data Guarantee conditions ...