Data sheet 10/20-EM090-8
Emergency lighting units
EM converterLED
7.2 Battery charge / discharge data
EM converterLED ST, 1 / 2 / 3 h, NiMH
Type
EM converterLED ST
202 MH/LiFePO4 50V
EM converterLED ST
203 MH/LiFePO4 50V
EM converterLED ST
204 MH/LiFePO4 50V
Article no.
89800624
89800625
89800626
Duration
1 h
2/3 h
1 h
2/3 h
1 h
2/3 h
Battery charge
time
Initial charge
20 h
Fast recharge
10 h
15 h
10 h
15 h
10 h
15 h
Trickle charge
continuously
Charging current
Initial charge
110 – 150 mA
280 – 320 mA
110 – 150 mA
280 – 320 mA
110 – 150 mA
280 – 320 mA
Fast recharge
190 – 230 mA
310 – 350 mA
190 – 230 mA
310 – 350 mA
190 – 230 mA
310 – 350 mA
Trickle charge
110 – 150 mA / 4 min.
0 mA / 16 min.
180 – 220 mA / 4 min.
0 mA / 16 min.
110 – 150 mA / 4 min.
0 mA / 16 min.
180 – 220 mA / 4 min.
0 mA / 16 min.
110 – 150 mA / 4 min.
0 mA / 16 min.
180 – 220 mA / 4 min.
0 mA / 16 min.
Discharge current
730 – 790 mA
730 – 790 mA
770 – 830 mA
770 – 830 mA
785 – 845 mA
785 – 845 mA
Charge voltage range
1
0.9 – 1.65 V per cell
Discharge voltage range
1.65 – 1.05 V per cell
1
The battery will be charged below 0.9 V. The EM converterLED will indicate a battery fault.
The emergency lighting LED Driver will recharge the battery normally after running the test of 61347-2-7 CL 22.3 (abnormal operating conditions).
EM converterLED ST, 1 / 2 / 3 h, LiFePO
4
Type
EM converterLED ST
202 MH/LiFePO4 50V
EM converterLED ST
203 MH/LiFePO4 50V
EM converterLED ST
204 MH/LiFePO4 50V
Article no.
89800624
89800625
89800626
Duration
1 h
2/3 h
1 h
2/3 h
1 h
2/3 h
Battery charge
time
Initial charge
24 h
Fast recharge
24 h
Trickle charge
continuously and battery voltage controlled
Charging current
Initial charge
115 – 155 mA
250 – 290 mA
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
Fast recharge
115 – 155 mA
250 – 290 mA
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
Trickle charge
1
115 – 155 mA / 0 mA
250 – 290 mA / 0 mA
250 – 290 mA / 0 mA
430 – 470 mA / 0 mA
250 – 290 mA / 0 mA
430 – 470 mA / 0 mA
Discharge current
530 – 570 mA
530 – 570 mA
890 – 960 mA
890 – 960 mA
1,255 – 1,350 mA
1,255 – 1,350 mA
Charge voltage range
2
2.0 – 3.65 V
Discharge voltage range
3.65 – 2.60 V
1
Automatic recharge when battery voltage falls below 3.4 V. Charger off (0 mA) when battery voltage exceeds 3.6 V.
Note: Battery protected against operation at excessive temperatures (charging stopped when battery cell temperature < -5 °C or > 60 °C).
The emergency lighting LED Driver will recharge the battery normally after running the test of 61347-2-7 CL 22.3 (abnormal operating conditions).
2
The battery will not be charged below 2.0 V.