background image

www.tridonic.com

3

Subject to change without notice. Information provided without guarantee.

Data sheet 03/20-EM042-21

Emergency lighting units

EM powerLED

 

Specific technical data

Type

3

Number 

of battery 

cells

Output 
current

Min. 

output 

voltage

2

 

Max. 

output 

voltage

2

Min.

output 

power

Max. 

output 

power

Input power 

(at 230 V, 50 
Hz, full load)

Input current 

(at 230 V, 50 Hz, 

full load)

Efficiency 
(at 230 V, 

50 Hz)

λ 

(at 230 V, 50 
Hz, full load)

Ambient 

temperature 

ta

1

tc/ta for ≥ 

50.000 h

1

I sel 

 resistor value

Normal operation

EM powerLED BASIC FX 
103 / 104 SR 50W 50V

300 mA

16.6 V

50.0 V

5.0 W

15.0 W

20 W

110 mA

74

0.80

-5 ... 50 °C

79 / 50 °C

open

350 mA

16.6 V

50.0 V

5.8 W

17.5 W

22 W

120 mA

79

0.80

-5 ... 50 °C

79 / 50 °C

69.80 kΩ

400 mA

16.6 V

50.0 V

6.6 W

20.0 W

25 W

130 mA

79

0.85

-5 ... 50 °C

79 / 50 °C

62.00 kΩ

450 mA

16.6 V

50.0 V

7.5 W

22.5 W

27 W

140 mA

82

0.85

-5 ... 50 °C

79 / 50 °C

56.00 kΩ

500 mA

16.6 V

50.0 V

8.3 W

25.0 W

31 W

150 mA

81

0.90

-5 ... 50 °C

79 / 50 °C

48.70 kΩ

550 mA

16.6 V

50.0 V

9.1 W

27.5 W

34 W

165 mA

81

0.90

-5 ... 50 °C

79 / 50 °C

43.20 kΩ

600 mA

16.6 V

50.0 V

10.0 W

30.0 W

36 W

175 mA

83

0.90

-5 ... 50 °C

79 / 50 °C

36.50 kΩ

650 mA

16.6 V

50.0 V

10.8 W

32.5 W

40 W

185 mA

81

0.90

-5 ... 50 °C

79 / 50 °C

28.70 kΩ

700 mA

16.6 V

50.0 V

11.6 W

35.0 W

44 W

200 mA

80

0.95

-5 ... 50 °C

79 / 50 °C

24.00 kΩ

750 mA

16.6 V

50.0 V

12.5 W

37.5 W

46 W

210 mA

82

0.95

-5 ... 50 °C

79 / 50 °C

20.50 kΩ

800 mA

16.6 V

50.0 V

13.3 W

40.0 W

49 W

225 mA

81

0.95

-5 ... 50 °C

79 / 50 °C

18.00 kΩ

850 mA

16.6 V

50.0 V

14.1 W

42.5 W

52 W

235 mA

81

0.95

-5 ... 40 °C

76 / 40 °C

16.00 kΩ

900 mA

16.6 V

50.0 V

15.0 W

45.0 W

55 W

250 mA

82

0.95

-5 ... 40 °C

76 / 40 °C

13.30 kΩ

950 mA

15.7 V

50.0 V

15.0 W

47.5 W

58 W

265 mA

82

0.95

-5 ... 40 °C

76 / 40 °C

11.00 kΩ

1,000 mA

15.0 V

50.0 V

15.0 W

50.0 W

61 W

275 mA

82

0.97

-5 ... 40 °C

76 / 40 °C

9.31 kΩ

1,050 mA

15.0 V

47.6 V

15.0 W

50.0 W

60 W

280 mA

84

0.97

-5 ... 40 °C

76 / 40 °C

7.87 kΩ

1,100 mA

15.0 V

45.5 V

15.0 W

50.0 W

60 W

280 mA

88

0.97

-5 ... 40 °C

76 / 40 °C

6.49 kΩ

1,150 mA

15.0 V

43.5 V

15.0 W

50.0 W

60 W

280 mA

88

0.97

-5 ... 40 °C

76 / 40 °C

4.70 kΩ

1,200 mA

15.0 V

41.7 V

15.0 W

50.0 W

60 W

280 mA

88

0.97

-5 ... 40 °C

76 / 40 °C

3.83 kΩ

1,250 mA

15.0 V

40.0 V

15.0 W

50.0 W

60 W

280 mA

88

0.97

-5 ... 40 °C

76 / 40 °C

2.70 kΩ

1,300 mA

15.0 V

38.5 V

15.0 W

50.0 W

60 W

280 mA

88

0.97

-5 ... 40 °C

76 / 40 °C

2.20 kΩ

1,350 mA

15.0 V

37.0 V

15.0 W

50.0 W

61 W

280 mA

87

0.97

-5 ... 40 °C

76 / 40 °C

1.50 kΩ

1,400 mA

15.0 V

35.0 V

15.0 W

50.0 W

62 W

285 mA

87

0.97

-5 ... 40 °C

76 / 40 °C

short circuit 

(0 Ω)

CF operation

EM powerLED BASIC FX 
103 / 104 SR 50W 50V

30 mA

0.5 W

1.7 W

4.0 W

50 mA

50

0.40

open

38 mA

0.6 W

2.1 W

4.5 W

50 mA

56

0.40

69.80 kΩ

39 mA

0.6 W

2.1 W

4.5 W

50 mA

56

0.40

62.00 kΩ

52 mA

0.9 W

2.9 W

5.0 W

55 mA

60

0.40

56.00 kΩ

52 mA

0.9 W

2.9 W

5.0 W

55 mA

60

0.40

48.70 kΩ

52 mA

0.9 W

2.9 W

5.0 W

55 mA

70

0.40

43.20 kΩ

66 mA

1.1 W

3.6 W

5.5 W

55 mA

73

0.45

36.50 kΩ

69 mA

1.1 W

3.8 W

5.5 W

55 mA

73

0.45

28.70 kΩ

80 mA

1.3 W

4.4 W

6.0 W

60 mA

75

0.45

24.00 kΩ

83 mA

1.4 W

4.6 W

6.0 W

60 mA

83

0.45

20.50 kΩ

85 mA

1.4 W

4.7 W

6.0 W

60 mA

83

0.45

18.00 kΩ

92 mA

1.5 W

5.1 W

6.5 W

60 mA

85

0.50

16.00 kΩ

92 mA

1.5 W

5.1 W

6.5 W

60 mA

92

0.50

13.30 kΩ

105 mA

1.6 W

5.8 W

7.0 W

60 mA

86

0.50

11.00 kΩ

106 mA

1.6 W

5.8 W

7.0 W

60 mA

86

0.50

9.31 kΩ

118 mA

1.8 W

6.2 W

7.5 W

65 mA

87

0.55

7.87 kΩ

119 mA

1.8 W

6.0 W

7.5 W

65 mA

87

0.55

6.49 kΩ

130 mA

2.0 W

6.2 W

8.0 W

65 mA

88

0.55

4.70 kΩ

131 mA

2.0 W

6.0 W

8.0 W

65 mA

88

0.55

3.83 kΩ

144 mA

2.2 W

6.3 W

8.0 W

65 mA

88

0.55

2.70 kΩ

144 mA

2.2 W

6.1 W

8.0 W

65 mA

88

0.60

2.20 kΩ

145 mA

2.2 W

5.9 W

8.5 W

65 mA

88

0.60

1.50 kΩ

158 mA

2.4 W

6.1 W

9.0 W

70 mA

83

0.60

short circuit 

(0 Ω)

Emergency operation
EM powerLED BASIC FX 
103 SR 50W 50V

3

see page 8

15 V

50 V

2.1 W

2.75  W

all

EM powerLED BASIC FX 
104 SR 50W 50V

4

see page 8

15 V

50 V

2.7 W

3.50 W

all

1

 

Ambient temperature range ta defined in normal operation

2

 

Output voltage range defined in normal operation. LED forward voltage will decrease in CF operation.

EM = Emergency

y

Summary of Contents for 89800412

Page 1: ...ED operation 300 1 400 mA output current in mains operation selectable with I SELECT PLUG in steps of 50 mA Simple CORRIDOR FUNCTION CF with 10 light level Integrated emergency lighting unit 1 or 3 h rated duration selectable with plug duration link Automatic shutdown of output if LED load is out of range Green charge status display LED Electronic charge system Polarity reversal protection for bat...

Page 2: ...a 40 W output power 50 C Max casing temperature tc 80 C Dimensions LxBxH 209 x 82 x 34 mm Mains voltage changeover threshold according to EN 60598 2 22 Type of protection IP20 Charge current 1h 100 mA Charge current 3h 200 mA Discharge current 1h 960 mA Discharge current 3h 960 mA EM powerLED BASIC FX SR 50 W Combined emergency lighting LED Driver ø4 5 ø 8 6 33 34 82 175 5 209 Duration link 3 h No...

Page 3: ... W 50 0 W 60 W 280 mA 88 0 97 5 40 C 76 40 C 6 49 kΩ 1 150 mA 15 0 V 43 5 V 15 0 W 50 0 W 60 W 280 mA 88 0 97 5 40 C 76 40 C 4 70 kΩ 1 200 mA 15 0 V 41 7 V 15 0 W 50 0 W 60 W 280 mA 88 0 97 5 40 C 76 40 C 3 83 kΩ 1 250 mA 15 0 V 40 0 V 15 0 W 50 0 W 60 W 280 mA 88 0 97 5 40 C 76 40 C 2 70 kΩ 1 300 mA 15 0 V 38 5 V 15 0 W 50 0 W 60 W 280 mA 88 0 97 5 40 C 76 40 C 2 20 kΩ 1 350 mA 15 0 V 37 0 V 15 0...

Page 4: ...2 ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc Test switch EM 2 89805277 25 pc s 600 pc s 0 009 kg Product description A green LED indicates that charging current is flowing into the battery Status indication green LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM green 89899605 25 pc s 200 pc s 0 0...

Page 5: ...ess Delay time detection range and light value for the bright out function can be set via 9 dip switches Max installation height 5 m Two housing options allowing flexible installation Variable detection area 100 10 Zero cross switching supported 5 year guarantee smartSWITCH HF 5DP f Automatic switching based on motion and light level ACCES SORIES smartSWITCH HF 5DP f smartSWITCH HF 5DP S f Orderin...

Page 6: ...6 50 kΩ 10 pc s 0 001 kg I SELECT PLUG E 28000622 Green 28k7 28 70 kΩ 10 pc s 0 001 kg I SELECT PLUG E 28001165 Green 24k 24 00 kΩ 10 pc s 0 001 kg I SELECT PLUG E 28001164 Green 20k5 20 50 kΩ 10 pc s 0 001 kg I SELECT PLUG E 28001163 Green 18k 18 00 kΩ 10 pc s 0 001 kg I SELECT PLUG E 28001162 Green 16k 16 00 kΩ 10 pc s 0 001 kg I SELECT PLUG E 28001161 Green 13k3 13 30 kΩ 10 pc s 0 001 kg I SELE...

Page 7: ...e time in operation at max temperature Certified quality manufacturer Casing material made of polycarbonate 0 2 m double insulated cable with plug connection 0 8 m double insulated cable with plug and pre stripped ends for connection with the emergency unit 1 0 mm solid wire pre stripped Suitable for emergency lighting equipment as per IEC 60598 2 22 NiCd Battery pack 1 8 4 5 Ah Batteries ACCES SO...

Page 8: ...s 25 pc s 0 40 kg Pack NiMH 4Ah 4 CON 28001897 5 pc s 25 pc s 0 48 kg Product description High temperature NiMH battery pack for use with emergency lighting units 4 year design life 1 year guarantee Properties Constant high temperature operation Temperature depending on the used emergency lighting unit refer to respective emergency control gear datasheet Good charging properties at high temperatur...

Page 9: ...M powerLED ACD EM LED INDICATOR HOLDER ACCES SORIES ø39 95 ø6 ø19 9 ø26 29 42 9 ø35 1 8 6 8 13 Ordering data Type Article number Colour Packaging carton Weight per pc ACD EM LED INDICATOR HOLDER 28002189 White 10 pc s 0 010 kg Product description Holder for indicator LED in emergency operation Glow wire test with a temperature of 850 C passed ...

Page 10: ... an insulation test with 500VDC for 1 se cond This test voltage should be connected between the interconnected phase and neutral terminals and the earth terminal The insulation resistance must be at least 2 MΩ As an alternative IEC 60598 1 Annex Q describes a test of the electrical strength with 1 500VAC or 1 414 x 1 500VDC To avoid damage to the electronic devices this test must not be conducted ...

Page 11: ...0 V L N 50 60 Hz LED module 15 50V Orange Pink Indication LED When using the EM powerLED without a sensor connect the terminals C F and L link with a wire The connected LED module will be used for mains and emergency operation The mains power must be removed before changing the LED load Secondary switching of LEDs is not allowed and may cause damage to the LEDs The hot plug in of LEDs during norma...

Page 12: ...be routed in parallel to ensure good EMC performance Maximum lead length for the Test switch and Indicator LED connection is 1 m The test switch and Indicator LED wiring should be separated from the LED leads to prevent noise coupling Battery leads are specified with 0 5 mm cross section and a length of 1 3 m To avoid the damage of the control gear the wiring must be protected against short circui...

Page 13: ...SIC FX 104 SR 50W 50V 20 30 40 50 16 24 32 40 6 6 A 30 μs Harmonic distortion in the mains supply at 230 V 50 Hz and full load in Type THD 3 5 7 EM powerLED BASIC FX 103 SR 50W 50V 6 5 4 5 2 1 EM powerLED BASIC FX 104 SR 50W 50V 6 5 4 5 2 1 5 1 Maximum loading of automatic circuit breakers 5 2 Harmonic distortion in the mains supply at 230 V 50 Hz and full load in 5 3 Insulation matrix Mains Switc...

Page 14: ...werLED module based on the total forward voltage of the LED modules connected and the associated battery Note LED peak current is measured at the max battery discharge current LED current at nominal battery voltage and min battery discharge current LED current at nominal battery voltage and max battery discharge current LED current mA VLED V VLED V LED current mA 50 400 350 300 250 200 150 100 10 ...

Page 15: ...s reset is required to restart the LED Driver 6 3 Overload protection LED Driver will switch off at overload operation Mains reset is required to restart the LED Driver 6 4 Underload operation LED Driver will switch off at underload operation Mains reset is required to restart the LED Driver 6 5 Forward voltage out of range If the forward voltage is out of range the unit switches to shut down mode...

Page 16: ...iCd 4C 55 28002775 side by side 3 x 1 Accu NiCd 3B 55 89800384 side by side 4 x 1 Accu NiCd 4B 55 89800385 NiMH 2 2Ah Cs cells stick 1 x 3 Accu NiMH 3A 28002088 stick 1 x 4 Accu NiMH 4A 28002089 NiMH 4Ah LA cells stick 1 x 3 Accu NiMH 4Ah 3A CON 89800441 stick 1 x 4 Accu NiMH 4Ah 4A CON 89800442 stick stick 2 2 Accu NiMH 4Ah 4C CON 89800438 NiCd 1 8Ah Cs cells remote box 1 x 3 Pack NiCd 3C CON 280...

Page 17: ... comissioning Max storage time 12 months 7 4 Accupack NiCd 1 8 Ah Battery voltage cell 1 2 V Cell type Cs Ambient temperature range to ensure 4 years design life 5 C to 40 C tc point 45 C Max short term temperature reduced life time 70 C Max number discharge cycles 4 cycles per year plus 4 cycles during comissioning Max storage time 6 months 4 5 Ah Battery voltage cell 1 2 V Cell type D Ambient te...

Reviews: