Data sheet 03/20-EM042-21
Emergency lighting units
EM powerLED
3. Installation / Wiring
3.1 Wiring diagrams
220–240 V
L
N
50/60 Hz
Tridonic Sensor
L
N
L´
EM powerLED
BASIC FX
N
L
+
–
+
–
–
+
S/L
C/F
L link
LED
Battery
Test switch
Duration link
Orange
Pink
Indication LED
I set
–
+
LED
module
15 – 50V
Wiring diagram EM powerLED BASIC FX without sensor
Wiring diagram EM powerLED BASIC FX with sensor
PIR output
≙
230 V
EM powerLED
BASIC FX
N
L
+
–
+
–
–
+
S/L
C/F
L link
LED
Battery
Test switch
Duration link
I set
220–240 V
L
N
50/60 Hz
–
+
LED
module
15 – 50V
Orange
Pink
Indication LED
When using the EM powerLED without a sensor, connect the terminals C / F and
L link with a wire.
The connected LED module will be used for mains and emergency operation.
The mains power must be removed before changing the LED load.
Secondary switching of LEDs is not allowed and may cause damage to the
LEDs. The hot plug-in of LEDs during normal operation may result in high
current peaks.
Note
The EM powerLED BASIC FX 50W uses pulse width modulation (PWM) for
the LED operation in CORRIDOR mode. This can have an adverse effect on
video recording equipment e.g. cctv.
Caution should be observed when using the CORRIDOR FUNCTION in cctv
monitored areas.
Switching behaviour
S/L
C/F
LED
off
off
off
off
on
off
on
off
10 %
on
on
100 %