5.5 Output current setting
Output current can be set by connecting a resistor between the 2 “I set” termi-
nals. Relationship between output current and resistor value can be found at
the table “Specific technical data”. Resistor values specified from standardised
resistor value ranges.
Resistor value tolerance has to be ≤ 1 %.
Resistor power has to be ≥ 0.1 W.
Resistor detection at each start.
Change of the resistor value during the operation will be not considered.
Resistors for the main output current values can be ordered from Tridonic (see
accessories).
EM powerLED BASIC FX 103 SR 50W 50V – 3 cells
Article number: 89800430
3.6 V battery voltage
750 – 960 mA battery discharge current (tolerance)
EM powerLED BASIC FX 104 SR 50W 50V – 4 cells
Article number: 89800412
4.8 V battery voltage
750 – 960 mA battery discharge current (tolerance)
5.4 Typ. LED current/voltage characteristics
The LED current in emergency mode is automatically adjusted by the EM powerLED module based on the total forward voltage of
the LED modules connected and the associated battery.
Note: LED peak current is measured at the max. battery discharge current.
LED current at nominal battery voltage and
min. battery discharge current
LED current at nominal battery voltage and
max. battery discharge current
LED curr
ent [mA]
V
LED
[V]
V
LED
[V]
LED curr
ent [mA]
50
400
350
300
250
200
150
100
10
20
15
25
35
45
30
40
50
55
10
0
30
60
90
120
150
180
210
270
240
300
20
15
25
35
45
30
40
50
55
LED peak current at start in emergency mode – 3 cells
Voltage
Inrush current
Duration
46.0 V
209 mA
7.35 ms
43.5 V
218 mA
7.85 ms
41.0 V
229 mA
8.10 ms
38.5 V
241 mA
8.25 ms
36.0 V
255 mA
8.35 ms
33.5 V
270 mA
8.55 ms
31.0 V
288 mA
8.85 ms
28.5 V
307 mA
9.10 ms
26.0 V
330 mA
9.40 ms
23.0 V
354 mA
9.80 ms
20.5 V
383 mA
10.45 ms
18.0 V
417 mA
11.40 ms
15.5 V
455 mA
11.95 ms
13.0 V
500 mA
15.10 ms
LED peak current at start in emergency mode – 4 cells
Voltage
Inrush current
Duration
46.5 V
252 mA
8.65 ms
44.0 V
259 mA
9.30 ms
41.5 V
268 mA
8.10 ms
39.0 V
288 mA
8.45 ms
36.5 V
300 mA
9.45 ms
34.0 V
323 mA
9.60 ms
31.5 V
340 mA
9.95 ms
29.0 V
364 mA
10.85 ms
26.0 V
388 mA
11.60 ms
23.5 V
414 mA
12.40 ms
21.0 V
446 mA
13.35 ms
18.5 V
479 mA
15.20 ms
16.0 V
520 mA
16.90 ms
13.5 V
564 mA
18.95 ms