Tridonic 87500975 Manual Download Page 4

www.tridonic.com

4

Subject to change without notice. Information provided without guarantee.

Data sheet 11/21-LC888-6

LED Driver

Linear fixed output

1. Standards

EN 55015
EN 61000-3-2
EN 61000-3-3
EN 61347-1 
EN 61347-2-13 
EN 61547
EN 62384
EN 60598-1

3.7 Mounting of device

Max. torque for fixing: 0.5 Nm/M4

The LED Driver is designed for a life-time stated above under reference 
conditions and with a failure probability of less than 10 %.

2. Thermal details and life-time

2.1 Expected life-time

3. Installation / wiring

3.1 Circuit diagram

3.2 Wiring type and cross section

The wiring can be stranded wires with ferrules or rigid wires with a cross 
section of 0.5 – 1.5 mm².
Strip 8.5 – 9.5 mm of insulation from the cables to ensure perfect operation 
of the push-wire terminals (WAGO 250).

��� – ��� mm

wire preparation:
��� – ��� mm² 

3.3 Release of the wiring

Press down the “push button” and remove the cable from front.

3.4 Wiring guidelines

•  All connections must be kept as short as possible to ensure good EMI 

behaviour.

•  Mains leads should be kept apart from LED Driver and other leads 
  (ideally 5 – 10 cm distance)
•  Max. length of output wires is 2 m.
•  Incorrect wiring can damage LED modules.
•  To avoid the damage of the Driver, the wiring must be protected against  
  short circuits to earth (sharp edged metal parts, metal cable clips, louver,  
 etc.).

3.5 Earth connection

The earth connection is conducted as protection earth (PE). The LED Driver 
can be earthed via metal housing. If the LED Driver will be earthed, 
protection earth (PE) has to be used. There is no earth connection required 
for the functionality of the LED Driver. Earth connection is recommended to 
improve following behaviour.

•  Electromagnetic interferences (EMI)
•  Transmission of mains transients to the LED output

In general it is recommended to earth the LED Driver if the LED module is 
mounted on earthed luminaire parts respectively heat sinks and thereby 
representing a high capacity against earth.

For Class II application, protection earth is no need to be connected, below 2 
scenarios should be considered:

•  If the LED Driver housing is screw on a metal part inside the luminaires, 
  both LED Driver and LED module must be insulated.
•  If the LED Driver housing is screw on a plastic part inside the luminaires, 
  the LED module need to be insulated.

3.6 Replace LED module

1. Mains off
2. Remove LED module
3. Wait for 30 seconds
4. Connect LED module again

Hot plug-in or output switching of LEDs is not permitted and may cause 
a very high current to the LEDs.

SEC

PRI

220–240 V

L

50/60 Hz

+ LED

3.3Vaux

GND

5Vaux

PWM

– LED

N

1
2

ON

I-select

LC stepDIM lp SNC

Motion
Sensor

Type

ta

50 °C

60 °C

LC 35/200-350/121 stepDIM lp SNC

tc

70 °C

80 °C

Life-time

100,000 h

50,000 h

Driver LC 35W 200-350mA stepDIM lp SNC4

Product description

 

The relation of tc to ta temperature depends also on the luminaire design. 
If the measured tc temperature is approx. 5 K below tc max., ta temperature 
should be checked and eventually critical 
components (e.g. ELCAP) measured. Detailed information on request.

Summary of Contents for 87500975

Page 1: ...nt 350 300 250 and 200 mA Max output power 35 W Up to 87 efficiency Nominal life time up to 100 000 h 5 year guarantee conditions at www tridonic com Housing properties Casing Driver metal white Casing sensor polycarbonat white Type of protection IP20 Functions Overload protection Short circuit protection No load protection È Technical data LED Driver page 3 Product description LED Driver page 4 6...

Page 2: ...etween L N 1 kV Mains surge capability between L N PE 2 kV Surge voltage at output side against PE 4 kV Life time up to 100 000 h Guarantee conditions at www tridonic com 5 years Dimensions L x W x H 230 x 30 x 21 mm Hole spacing D 218 mm Driver LC 35W 200 350mA stepDIM lp SNC essence series non SELV stepDIM 230 21 122 4 tc 4 30 218 ø4 1 tc 16 2 side fixing feature Ordering data Type1 Article numb...

Page 3: ...n angle 150 Max detection area1 ø 14 m Max mounting height 6 m tc 70 C Ambient temperature ta 20 70 C Storage temperature ts 20 70 C Humidity min 5 max 95 Type of protection IP20 Protection class Protection class II Casing material PC halogen free Casing colour White Dimensions L x W x H 89 x 15 8 x 12 1 mm Hole spacing D 84 mm Motion Sensor included Automatic switching based on motion and light l...

Page 4: ...Driver can be earthed via metal housing If the LED Driver will be earthed protection earth PE has to be used There is no earth connection required for the functionality of the LED Driver Earth connection is recommended to improve following behaviour Electromagnetic interferences EMI Transmission of mains transients to the LED output In general it is recommended to earth the LED Driver if the LED m...

Page 5: ...0 100 12 10 2 4 6 8 Load THD 82 85 86 84 83 87 88 89 90 30 50 70 60 80 90 40 100 Load Efficiency 0 75 0 80 0 90 0 85 0 95 1 00 30 60 50 70 80 90 40 100 Load Power factor 0 50 80 70 90 60 50 30 40 100 5 15 10 25 20 40 45 35 30 Load Input power W 0 210 80 70 90 60 30 40 50 100 180 150 120 90 60 30 Load Input current mA 3 8 Current setting 200 mA Switch 1 Off Switch 2 Off 350 mA Switch 1 On Switch 2 ...

Page 6: ...f the product is used outside a luminaire the installation must provide suitable protection for people and environment e g in illuminated ceilings Automatic circuit breaker type C10 C13 C16 C20 B10 B13 B16 B20 Inrush current Installation Ø 1 5mm2 1 5mm2 1 5mm2 2 5mm2 1 5mm2 1 5mm2 1 5mm2 2 5mm2 Imax Time LC 35 200 350 121 stepDIM lp SNC 36 47 58 73 36 47 58 73 12 A 80 µs THD 3 5 7 9 11 LC 35 200 3...

Page 7: ...anti interference ability it is not affected by temperature humidity airflow dust noise brightness and other factors Avoid installing metal accessories or shells metal will block the microwave and affect the effect The antenna surface should avoid large current circuit coverage which may cause interference The photosensitive position should avoid being blocked by opaque objects which will change t...

Page 8: ...trate the metal is close to the RF hollow width of the lamp board or alu minum substrate is required as follows 1 When the thickness of the baffle plate and the aluminum substrate all the metal part is D 1 mm the suggested hollow length is 80 mm width 13 mm 2 When the thickness of the baffle plate and the aluminum substrate all the metal part is 1 mm D 2 mm the suggested hollow length is 80 mm wid...

Page 9: ...Continuous trigger valid Continuous trigger valid Continuous trigger valid Continuous trigger valid Model ON OFF Timing Output Monitor Power losses on stand by system 1 W Power losses on stand by system 1 W In this sequence diagram the default state of dialing is all ON state When the PWM output signal changes from 100 to 10 or 30 the gradual change time is 1 s followed by a blocking time of about...

Page 10: ...devices in accordance with the WEEE directive to suitable recycling facilities h d Take 3 m as an example the detected moving target person is approx 170 cm high and weighing approx 65 kg In the test room the module is installed with the antenna facing down and the person is moving in the direction of the sensor at a speed of 1 m s A person moved towards the sensor with a speed of 1 m s during the...

Reviews: