Trident Emergency Products, LLC
2940 Turnpike Drive | Suite #9 | Hatboro, PA 19040 USA
8
AirPrime
™ Fire Pump Priming System
™
5.22"
2.00"
1.00
"
2.50"
2.38"
1.125"
.281" Hole
Panel Cutout
3.22"
.781"
Manual Single Location AirPrime
™
Systems
Installation
1. Install the AirPrime unit
VERTICALLY
within the pump enclosure. Unit must be mounted
ABOVE
the highest point in suction piping.
2. Install the manually operated primer push-to-operate air control on pump panel (see
Figure #13
).
3. Install 3/8"
OD
air hose piping with 1/4" NPT fittings from the PPV protected air tank to the primer manually operated push-to-operate
control and then to the primer unit. (See
Figure #14
).
4. If the AirPrime is equipped with an optional lift gauge, connect a 1/4" tubing line from the push-to-connect fitting supplied on the back
of the panel lift gauge to the 1/8" NPT connection on side of the primer body using the 1/8" male NPT x 1/4"
push-to-connect swivel
elbow provided with the AirPrime unit. (See
photo bottom right
for tubing connection location).
2.00"
Panel Cutout
.281" Diameter
.781"
1.00"
3.22"
3.22
1.125
"
OPERATION: Manual Priming Control
The manual AirPrime pump primer is operated simply by increasing the engine speed to a maximum of 1000 RPM and depressing the push
button on the panel. Hold the button down until the discharge pressure gauge begins to rise. The primer will stop running when the push
button is released. The push button will operate the primer regardless of whether the fire pump is engaged or not.
1. Depressing the Push-To-Prime button directs air to the primer inlet.
2. An internal valve to the water pump is opened with air pressure from chassis air system.
3. Vacuum for drafting is created by air-flow through multi-stage internal venturi nozzles.
4. The Panel Control Valve has no water, plumbing or electrical lines.
5. Never run a dry pump at engine speeds above 1200 RPM for more than 45 seconds in accordance with fire pump manufacturer's
operating instructions.
Figure 13
Figure 14
Primary Air Supply
Panel
Push
Button
™
Pressure
Protection
Valve
Plugged
Opening
Filter
Port
Figure 15
The lift gauge provides the following features:
a)
Visual indication of the vertical lift of water during priming operation.
b)
Lift gauge will not be damaged by positive water pressure supply line.
c)
Lift gauge can be used for positive periodic in-service ramp test without
pump engagement.
d)
Operation is the same as a manual
AirPrime without a lift gauge.
Swivel Connection for
1/4" OD Lift Gauge Tubing