Communication
TCD Electronics | Function Manual | Version: TCD_PROFI_S_EN_200326_E003
41
Index Parameter name
Data type
[size]
Access Annotation
25
SIMULATE
DS-50
Read
Write
Possibility to simulate the PROCESS_VALUE
parameter
(in‐
cluding the quality code). This could
be used to verify the PLC program behavior.
27
VIEW_1
Read
only
Read-only parameter to read
•
CURRENT_MODE
•
FRAME TEMPERATURE
•
FRAME TEMPERATURE UNITS
•
DAMPING
•
SIMULATE
Manufacturer Specific
37
PROCESS_VALUE
UNITS TEXT
Visible-
Stirng(8)
Read
only
Tab. 17: Slot 12: Analog Input block
–
Frame temperature
3.8.16.
Slot 13: Totalizer block 3
Index Parameter name
Data type
[size]
Access Annotation
16
BLOCK_OBJECT
DS-32
Read
only
Constant block information
17
CURRENT_MODE
Unsigned8
Read
only
Set to “Out of service” if the TARGET_MODE
parameter of the Physical Block is set to “Out of
service”.
Available modes:
8: Automatic
128: Out of service
22
PROCESS_VALUE
101
Read
only
32-bit floating point process value with quality code.
The value follows TOTAL_UNITS. TOTAL and
TOTAL_DOUBLE are always “on pair” i.e. both
showing the same totalized value but with a different
precision.
23
TOTAL_UNITS
Unsigned16 Read
Write
Influences the TOTAL, TOTAL_DOUBLE and
PRESET_TOT value. The INPUT_SELECTOR defines the
available physical unit codes that are allowed e.g.
INPUT_SELECTOR is set to mass flow, the
TOTAL_UNITS only accepts mass units.
Available Mass units:
1088: kg
1089: g
1090: mg
1091: Mg
1092: t
1093: oz
1094: lb