LonWorks
®
Wiring
Communications connections require that the HMS-1655L units be
connected with twisted pair communication cable to each unit in the
network. The unique network address of each HMS unit is set by a
network management tool like LONMAKER. All wiring must be done in
accordance with the National Electric Code as well as regulations of all
authorities having jurisdiction, and must conform to applicable codes.
When required by code, communications wiring may be installed in a
conduit designed specifically for this purpose.
Wire Terminations
The HMS-1655L is provided with a removable connector block with
convenient screw terminals. Make the LON FTT-10 communications
connections as follows:
1 Connect a cable lead to the “NT1” terminal (#1).
2 Connect a cable lead to the “NT2” terminal (#2)
Guidelines for Wiring
Following these guidelines will help to keep wiring-related
communication problems to a minimum:
1. Do not splice communications cable or wire at any point between
controllers.
2. Avoid the “stub T-tap” technique of routing/connecting communication
cables. Conductor discontinuities produced by such connections
may generate RFI or other electromagnetic interference on the
communications circuit.
3. Do not use wire nut devices for connecting communication cables.
4. Do not route any part of communication cables through the conduit,
junction boxes, or other devices containing AC electrical wiring.
5. Do not strap communications cables to any conduit or other device
containing AC electrical wiring, or run communication cables parallel to
(or against) such devices.
6. Wire the LonWorks
®
network in accordance with LonWorks
®
network standards.
NOTE:
AC electrical devices such as transformers, disconnects,
fluorescent lighting, motor-controllers, variable frequency drives, or other
high voltage power sources may generate RF interference which could
cause intermittent problems in the communications network.
NOTE:
Be sure to observe installation instructions regarding the
possible need for a termination load or other device that may
have to be attached on the end of a run.
Wiring Display to Control Unit
The HMS-1655L display is supplied with a removable 4-position
terminal block connector for convenient connection to the control unit.
The recommended interface cable type (Belden 1325A) should be
connected as follows:
1. Connect the ‘+V’ terminal on the display connector to the ‘+V’
terminal on the display adapter module located inside the control unit.
2. Connect the ‘GND’ terminal on the display connector to the ‘GND’
terminal on the display adapter module.
3. Connect the ‘+’ terminal on the display connector to the ‘+’ terminal
on the display adapter module.
4. Connect the ‘-’ terminal on the display connector to the ‘-’ terminal on
the display adapter module.
General
LonWorks
®
Wiring
HMS-1655L
-
26
-
MOUNTING/WIRING
Triatek reserves the right to change product specifications without notice.
Typical Network Topologies
Singly Terminated Bus Topology
Doubly Terminated Bus Topology
Loop Topology
Star Topology
Mixed Topology
Termination
Termination
Termination
Termination
Termination
Termination