MOUNTING/WIRING
Triatek reserves the right to change product specifications without notice.
0-5v (JP7)
Jumper Setting
AI 1
AI 2
AI 3
AI 4
1
2
3
4
= JUMPER ON
Analog Input
0-10v (JP7)
AI 1
AI 2
AI 3
AI 4
JP7
1
2
3
4
Analog Input
4-20mA (JP6)
AI 1
AI 2
AI 3
AI 4
Analog Input
JP6
0-5v (JP5)
AO 1
AO 2
AO 3
AO 4
Analog Output
0-10v (JP5)
AO 1
AO 2
AO 3
AO 4
JP5
Analog Output
Note: 4-20mA can only be used if the
corresponding JP7 Analog Input Jumper
is set to OFF.
Note: Each Analog Input or Output value can be set independent of one another.
Example:
AI 1 can be set to 0-5v jumper OFF (JP7 PIN 1)
AI 2 can be set to 0-10v jumper ON (JP7 PIN 2)
AI 3 can be set to 4-20mA jumper ON (JP6 PIN 3) and jumper OFF (JP7 PIN 3)
AO 1 can be set to 0-10v jumper ON (JP5 PIN 1)
AO 2 0-5v can be set to 0-5v jumper OFF (JP5 PIN 2)
= JUMPER OFF
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Provided by Triatek
Power
HMS-1655L
-
21
-
Triatek reserves the right to change product specifications without notice.
MOUNTING/WIRING
NC
No Connection to Field Wiring
Field Wiring w/space for Number
Internal Wiring
Screw Terminal
Wiring Guide Legend
Symbol Description
Air Flow To and From Unit
Between Room and Corridor