Red / 24 VAC / 30Va
connected to the HMS
Slow Blow
Fuse
Ground
}
}
- Or -
120 VAC
50/60 Hz
Black
White
Stepdown Isolation Transformer
(provided with HMS-1655L)
Only Class 2 wiring in
this compartment.
Note:
This product should be installed with the manufacturer provided isolated power supply and connected to an electrical
circuit protected by a minimum 20A circuit breaker. This circuit breaker should be mounted in an approved electrical
enclosure located separately, but in close proximity to this product. Make sure you cap off any unused lead.
}
240 VAC
50/60 Hz
Blue
Transformer
50/60 Hz
Stepdown Isolation Transformer
HMS-1655L
-
23
-
Triatek reserves the right to change product specifications without notice.