FMS-2000M Lite

LIT-12013692

15

The FMS-2000M Lite Critical Environment Monitor includes one remote pressure sensor to measure the differential pressure of the 

monitored spaces. Install the remote pressure sensor module in the wall facing the monitored space such as an isolation room. Install 

the flow tube mounting plate facing the adjoining reference space such as the corridor or anteroom. With this sensor orientation, a 

positive pressure value indicates that the monitored space is positive with respect to the reference space. Choose a location that is 

away from any moving air source such as ceiling-mounted air registers. This can cause unstable sensor behavior. 

See 

Figure 8 

for more 

information.

Before you begin, determine the sensor location and gather the cable that you need. To mount the remote pressure sensor, make sure 

you have the following tools:

• 

a drill and a 7/16 in. drill bit

• 

a #2 Phillips head screwdriver

• 

a drywall saw or an oscillating tool with a drywall saw blade

To mount the remote pressure sensor, complete the following steps:

1. 

Connect a 4-conductor 22 AWG cable between the remote pressure sensor module. The length of the cable should not exceed 

1,000 ft.

2.  Remove the sensor’s louvered cover plate and stainless steel backplate from the orange wall bracket.

3.  Cut an opening in the wall of the monitored space for the orange low voltage mounting bracket and for the remote pressure sensor 

electronics. Nominal hole dimensions are 3.65 in. (9.271 cm) H x 2.15 in. (5.461 cm) W.

4.  Use the rotating clamps to secure the bracket to the wall safely.

5. 

Drill a 7/16 in. hole through the opposite wall for the flow tube.

6.  Pull the 4-conductor signal wire through the cut out.

7.  Install the mounting bracket in the drywall opening and pull the 4-conductor signal cable through the mounting bracket.

8. 

Push a length of flow tube through the hole and the 7/16 in. hole in the opposite wall.

9. 

Attach the flow tube to the sensor port.

 

When you install the mounting plate directly opposite the sensor, cut the flow tubing as short 

as possible to prevent kinks.

10. 

Push the tube and sensor module into place and secure it with the two #6-32 x 3/4 in. screws supplied.

11.  Screw the louvered cover plate to the front. 

12. 

In the reference space, attach the flow tube to the barbed fitting of the flow tube mounting plate.

 Apply thin silicone caulking around 

the tube, between the stainless steel plate and the wall to seal against penetration.

13.  Press the mounting plate into place. Allow the excess tube length to go into the wall space. Secure the mounting plate with the 

screws and anchors.

14.  Screw the louvered cover plate to the front.

Mounting the remote pressure sensor

Summary of Contents for FMS-2000M Lite

Page 1: ...1 FMS 2000M Lite Critical Environment Monitor LIT 12013692 December 2020 Installation Guide ...

Page 2: ...ork wiring and all network devices from high voltage wiring and equipment Failure to isolate network wiring and network devices from high voltage wiring and equipment can result in damage to network devices or poor network performance Risk of Property Damage Label all wires prior to disconnecting the equipment Failure to label the wires may cause improper equipment operation after reconnecting the...

Page 3: ...te Critical Environment Monitor where the maximum temperature exceeds 125 F 52 C Installing the device where maximum temperatures exceed 125 F 52 C may cause damage to the FMS 2000M Lite Critical Environment Monitor and may void the warranty IMPORTANT Only qualified personnel should install or service Johnson Controls products These instructions are a guide for such personnel Carefully follow all ...

Page 4: ...ation réseau dans les mêmes gaines chemins de câbles ou panneaux que les câbles à haute tension supérieure à 30 Vca Isolez tous les câbles et appareils réseau des câbles et appareils à haute tension Un défaut d isolement des câbles et appareils à haute tension peut provoquer des dommages aux appareils réseau et réduire les performances du réseau Risque de dégâts matériels Etiquetez tous les câbles...

Page 5: ...critique FMS 2000M Lite où la température maximum dépasse 52 C 125 F Installer l appareil dans un environnement où la température maximum dépasse 52 C 125 F peut endommager FMS 2000M Lite Critical Environment Monitor et peut annuler la garantie IMPORTANT N utilisez que des conducteurs en cuivre Assurez vous que tous les branchements de câbles sont effectués selon les réglementations locales nation...

Page 6: ...0M Lite Thin Mount display for a new application 11 Mounting the remote pressure sensor 15 Wiring the system and BACnet MS TP communications 17 Wiring one remote pressure sensor to the monitor 18 Configuring the display module settings 20 BMS integration 20 Ordering information 21 Cleaning the display 21 Technical specifications 22 Repair information 23 Table of contents ...

Page 7: ...een The FMS 2000M Lite provides maximum room status awareness with the color coded visual alarms that display on screen and the 360 Safety Halo illuminated edge which allows staff to easily monitor spaces down long corridors You can mute the audible alarm with one tap to the screen to reduce audible alarm fatigue The FMS 2000M Lite features two password protected access levels one for administrato...

Page 8: ...y 24 VAC power to the pressure sensor module Power Supply Input Cable Ferrite Install the cable ferrite A on the cable to provide power to the isolated power supply module as shown in the figure below Unlatch the clasp on the side of the ferrite to expose the core place it on the power cable near to the power supply enclosure and close the ferrite around the cable Ensure that the clasp latches sec...

Page 9: ...e retrofit ring 6 If the 2 conductor power cable terminates at the monitor pull the 2 conductor power cable through the retrofit ring 7 Insert the retrofit ring through the opening Make sure that the four tabs make contact with the inside of the opening and then pull the retrofit ring flush against the inside of the wall 8 Attach the monitor s mounting bracket to the retrofit ring with the four in...

Page 10: ...FMS 2000M Lite LIT 12013692 10 Item Component 1 FMS 2000M Lite Critical Environment Monitor 2 Monitor bracket 3 Wall 4 Retrofit ring 5 Mounting screw 6 Set screw ...

Page 11: ...flush with the finished surface of the drywall and the opening fits precisely with the rough in box 6 Align the monitor s mounting bracket to the four screw holes on the mounting tabs of the rough in box Use a 2 Phillips head screwdriver to secure the bracket with the screws provided Make sure the bracket is level Note To avoid warping the mounting bracket do not over tighten the screws 7 Connect ...

Page 12: ...FMS 2000M Lite LIT 12013692 12 Item Component 1 FMS 2000M Lite Critical Environment Monitor 2 Mounting bracket 3 Wall 4 Stud 5 Rough in box 6 Mounting screw 7 Set screw ...

Page 13: ...FMS 2000M Lite LIT 12013692 13 ...

Page 14: ...FMS 2000M Lite LIT 12013692 14 Number Description 1 Surface mount display 2 Existing wall box 3 Mounting plate ...

Page 15: ...nless steel backplate from the orange wall bracket 3 Cut an opening in the wall of the monitored space for the orange low voltage mounting bracket and for the remote pressure sensor electronics Nominal hole dimensions are 3 65 in 9 271 cm H x 2 15 in 5 461 cm W 4 Use the rotating clamps to secure the bracket to the wall safely 5 Drill a 7 16 in hole through the opposite wall for the flow tube 6 Pu...

Page 16: ...umber Description 1 Gasket 2 Stainless steel flow tube mounting plate 3 Wall section in cut away view 4 Flow tube 5 Stainless steel mounting plate 6 Gasket 7 Louvered cover plate 8 Remote pressure sensor 9 Mounting bracket 10 Terminal block 11 Thin silicone caulking ...

Page 17: ...ply Wiring one remote pressure sensor to the monitor Note The figure shows a 120 VAC to 24 VAC step down isolation transformer as an example For information about correct power supply termination see the following wiring information 4 Supervisory device 5 FMS 2000M Lite Critical Environment Monitor 24V_IN DSPLY RS485 BACnet MS TP REF 120 VAC 24 VAC ...

Page 18: ... P1 P2 COMMON 120 VAC input 240 VAC input White Black Blue REF 24V_IN DSPLY RS485 BACnet MS TP Landscape Portrait 120 VAC 240 VAC 60 50Hz input Callout Component 1 FMS 2000M Lite monitor 2 Remote pressure sensor DIP switch SW1 3 Supplied remote pressure sensor 4 Io terminal Note A 4mA to 20mA signal is present at the sensor s Io terminal which represents the monitored room pressure You can use it ...

Page 19: ...3 On 4 On 5 Sensor mode Set the switch to On for normal or Off for inverted After you change the sensor mode with switch 5 cycle power to the sensor for the mode change to take effect On or off 6 Reserved n a 7 Reserved n a 8 Sensor communications termination Off SW1 1 2 3 4 5 6 7 8 On ...

Page 20: ...ailability of analog value objects FMS2ML BxR AV 1 Network Variable temperature 1 Read or write Yes AV 2 Differential Pressure low alarm setpoint 1 Read or write Yes AV 3 Differential Pressure low warning setpoint 1 Read or write Yes AV 4 Differential Pressure high warning setpoint 1 Read or write Yes AV 5 Differential Pressure high alarm setpoint 1 Read or write Yes AV 6 Network Variable humidity...

Page 21: ...c chemicals such as paint thinner acetone tolulene xylene propyl or isopropyl alchohol or kerosene IMPORTANT N appliquez pas de nettoyant directement sur la surface du panneau tactile Si du nettoyant pénètre dans le panneau tactile essuyez immédiatement le nettoyant à l aide d un chiffon absorbant N utilisez aucun nettoyant qui est acide ou alcalin Utilisez un nettoyant dont le pH est neutre N uti...

Page 22: ...alo black and white on screen status icons audible alarm Alarm silence Touchscreen auto reset Password protection Single PIN access code Communications protocol BACnet MS TP to BAS 76 8k 38 4k 19 2k 9600 baud Power requirement 24 VAC nominal 21 6 VAC minimum 26 4 VAC maximum 50 60 Hz 30 VA power supply Class 2 Limited Energy or LPS isolated power supply Power consumption 30 VA maximum Pollution de...

Page 23: ...nts Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open source software information and other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms If you purchased a service agreement contact your Triatek r...

Reviews: