FMS-2000M Lite
LIT-12013692
20
BMS integration
Configuring the display module settings
FMS-2000M Lite DIP switch position
Demo mode
Run mode
Position 1
On
On
Position 2
On
On
Position 3
Off
On
Position 4
On
Off
Objects
Analog inputs
Read/Write
Availability of analog input objects
FMS2ML–BxR
AI-1
Analog input 1, differential pressure
Read only
Yes
Objects
Analog values
Read/Write
Availability of analog value objects
FMS2ML–BxR
AV-1
Network Variable temperature 1
Read or write
Yes
AV-2
Differential Pressure low alarm setpoint 1
Read or write
Yes
AV-3
Differential Pressure low warning setpoint 1
Read or write
Yes
AV-4
Differential Pressure high warning setpoint 1 Read or write
Yes
AV-5
Differential Pressure high alarm setpoint 1
Read or write
Yes
AV-6
Network Variable humidity 1
Read or write
Yes
Objects
Multistate value objects
Read/Write
Availability of multistate value objects
FMS2ML–BxR
MV-1
AI-1 Alarm Status
1 = positive, 2 = negative, 3 = neutral
Read only
Yes