FMS-2000M Lite
LIT-12013692
22
Specification
Description
Intended use
Indoor use
Overvoltage category
II
Altitude
Up to 2000 m (6,561.67 ft)
Pressure range
± 0.2500 in. W.C. (± 62.27 Pa)
Alarm range
± 0.2500 in. W.C. (± 62.27 Pa)
Display range
± 0.2500 in. W.C. (± 62.27 Pa)
Accuracy
± 0.5% full scale
Air flow sensor type
Digital differential pressure sensor features no offset, zero drift and is hysteresis free
Displayed pressure resolution
± 0.0001 in. W.C. (± 0.0249 Pa)
Monitoring capability
Single space
I/O Resources
One remote monitoring output for the remote pressure sensor
Operating temperature
32°F to 104°F (0°C to 40°C)
Operating humidity
10% to 95% relative humidity, non-condensing
Mounting
Thin mount for shallow wall cavities
Alarm indication
Color coded 360˚ Safety Halo, black and white on screen status icons, audible alarm
Alarm silence
Touchscreen, auto-reset
Password protection
Single PIN access code
Communications protocol
BACnet MS/TP (to BAS) 76.8k, 38.4k, 19.2k, 9600 baud
Power requirement
24 VAC (nominal, 21.6 VAC minimum/26.4 VAC maximum), 50/60 Hz 30 VA power supply, Class 2,
Limited Energy, or LPS isolated power supply
Power consumption
30 VA maximum
Pollution degree
2
Display resolution
720 pixels x 1280 pixels
Pluggable screw terminal blocks
18 AWG to 22 AWG (1 mm to 0.6 mm diameter)
Display dimensions
(height x width x depth)
5.3 in. x 3.5 in. x 1.17 in. (134.62 mm x 88.9 mm x 29.72 mm)
Mounted depth
Thin mount: 0.58 in (14.73 mm)
Compliance
United States
UL Listed to UL 61010-1; FCC 47CFR Part 15; BTL Listed
Canada
cUL Listed to CAN/CSA C22.2 NO. 61010-1; ICES-003
Europe
CE (EMC Directive) to EN 61326-1
Australia and New
Zealand
RCM Mark (Australian Radiocommunications Act) to EN 61326-1
Technical specifications