AM-4 Alarm Wiring

The alarm contacts of the AM-4 module are rated
for 2 amps at 120 volts.

Test / Verify Alarm Contacts

The AM-4 module will close the alarm relay

contacts on any hard lockout (manual reset

required) of the Prestige MCBA control

module.  The AM-4 will not close the alarm

contacts on a soft lockout (auto reset).

1. Disconnect power supplied to the boiler.

Remove the factory jumpers from terminals 13
and 14 on the low voltage terminal of the
Prestige boiler.  See Figure 3 on how to use the
wire tool to remove the jumper from the terminal
block.

2.  Restore power to the boiler, initiate a demand

and allow the boiler to proceed through its start-
up sequence.

3.  The Prestige MCBA control module should

enter a hard lockout, causing the alarm contacts
on the AM-4 to close.  The remote alarm should
then be activated.

4.  Disconnect the power supplied to the boiler and

replace the jumper across the terminals 13 and
14 on the terminal block.

5.  Restore power to the boiler placing it back into

service.

6.  Repeat the verification sequence with the

remaining boilers.

NOTICE

Terminal Block

Wiring Tool

(Included in Kit)

Fig. 3:  Insertion of the Wire Tool into

Terminal Block

2005-34 AM_4 Module Kit

Date 12/14/06

Summary of Contents for PSRKIT23

Page 1: ...uipment but not related to personal injury hazards NOTICE WARNING Failure to follow instructions below can result in severe personal injury or damage if ignored Instructions are for a qualified installer service technician Read all instructions before proceeding Follow instructions in the proper order For your safety turn off electrical power supply at service panel and allow unit to cool before p...

Page 2: ...wires through the wire ways of the Prestige boiler and along the Prestige factory wiring Strip the wire ends and connect to the AM 4 terminals X2 1 and X2 2 for the 0 10 vdc analog signal and X1 1 and X1 2 for the alarm as shown in Figure 1 Use the cable clamps pro vided in the AM 4 kit to secure the incoming wires to the module Ensure the polarity of the wire connections from the Boiler Controlle...

Page 3: ...ule operational parameter settings reference the Prestige Control Supplement Program Access To enter the parameter listing of the MCBA control the installer must enter the activation code as fol lows 1 Press and hold the MODE button 2 Continue holding the MODE and press STEP button until STBY appears and hold both STEP and MODE buttons for 2 to 3 seconds The display should read CODE 3 Release the ...

Page 4: ...hange the value of the display Press the STORE button once to save the change If a parameter setting is changed from the factory default and the STORE button is not pressed to save the setting the MCBA mod ule will automatically store the setting after 15 minutes Ensure all parameters settings are either factory default or revised based on the application Review all parameters set tings on page 10...

Page 5: ...ing listed below and press STORE to save the set ting Test Verify Boiler and Control Operation 1 Refer to and follow the instructions given in the Prestige Installation manual to test operation of the boiler and the MCBA control To initiate any calls for heat during the test you will have to operate the external boiler controller 2 Verify the boiler modulates correctly by adjust ing the external b...

Page 6: ... to use the wire tool to remove the jumper from the terminal block 2 Restore power to the boiler initiate a demand and allow the boiler to proceed through its start up sequence 3 The Prestige MCBA control module should enter a hard lockout causing the alarm contacts on the AM 4 to close The remote alarm should then be activated 4 Disconnect the power supplied to the boiler and replace the jumper a...

Reviews: