AM-4 Interface Module Kit
4
After the activation code is entered press the
MODE button until the display shows
PARA
. At
this point the installer can access the parameters
required for application.
Once in the parameter mode, press the STEP
repeatedly to reach the appropriate parameter set-
ting. The display should show the following
sequence, as the STEP button is press repeatedly:
Press STEP once-
1140
Press STEP x2 -
2_01
Press STEP x3 -
3_01
Press STEP x4 -
4186
Press STEP x5 -
P_05
Press STEP x6 -
P_06
Etc......
After Parameter 4 the display will continue to show
P followed by a two-digit number that increases
with each press of the STEP button.
The actual parameter values displayed on
the unit may vary depending on the applica-
tion. The parameter sequence will always
occur in the order shown.
Once a particular parameter is reached, release the
STEP button. Wait a second and the display will
show the current setting for that parameter in the
right two display digits.
To Change a Parameter Setting
Use the + or - button to change the value of the
display.
Press the STORE button once to save the
change.
If a parameter setting is changed from the
factory default and the STORE button is not
pressed to save the setting, the MCBA mod-
ule will automatically store the setting after
15 minutes. Ensure all parameters settings
are either factory default or revised based on
the application. Review all parameters set-
tings on page 10 when completed and prior
to commission of the boiler. Failure to com-
ply could result in erratic or unreliable oper-
ation of the Prestige boiler.
Once a parameter setting value has been
revised and stored, if the STEP button is
pressed for the next parameter setting the
value setting of that parameter will appear.
The display will not show P_XX of the next
sequential parameter. The sequence of para-
meters may be scrolled through, as the dis-
play will roll over from parameter 42 to
parameter 1.
If sequential parameters are being revised
and since the display will not show P_XX of
the sequential parameter, it is recommend to
press and hold the STEP button to scroll
through the entire list of parameters before
making any additional changes to avoid any
potential confusion.