Program Access of the MCBA Control

The Prestige MCBA control module must be

programmed to accept a 0 - 10 vdc analog

signal and correctly respond to the external

boiler control module.

To adjust the factory parameter setting of the
Prestige MCBA Control, the installer must enter
into the parameter menu of the control.

Do not attempt to revise any other control

parameter setting except those listed in this

supplement.  Perform only those parameter

revisions described in this supplement.

Failure to comply could result in erratic or

unreliable operation of the Prestige resulting

in severe personal injury, death or substan-

tial property damage.

For additional information on revising the

Prestige MCBA Control Module operational

parameter settings, reference the Prestige

Control Supplement.

Program Access 

To enter the parameter listing of the MCBA control,
the installer must enter the activation code as fol-
lows:

1.  Press and hold the MODE button

2. Continue holding the MODE and press

STEP button until 

STBY

appears and hold

both STEP and MODE buttons for 2 to 3
seconds.

The display should read 

CODE

3.  Release the STEP and MODE buttons on

the control panel.

4.  Press STEP once.

The display should read 

C_

XX

(XX should

be a random number from 00 to 99)

5.  Press the + or - button to change the display

number 

C_

XX

to read 

C_05

.  Press and

release the + or - to change the display one
number at a time.  Press and hold the + or -
to rapidly change the display number.

6.  When the display reads 

C_05

press STORE

to save the activation code.  The display

C_05

should flash when the code is entered

and saved.

NOTICE

WARNING

NOTICE

AM-4 Interface Module Kit

3

Rear Side of

Control Panel

AM-4 Mounting

Hole Location

Alternative

Mounting

Location

AM-4

Interface Module

Fig. 2:  Mounting the AM-4 Interface Module

Summary of Contents for PSRKIT23

Page 1: ...uipment but not related to personal injury hazards NOTICE WARNING Failure to follow instructions below can result in severe personal injury or damage if ignored Instructions are for a qualified installer service technician Read all instructions before proceeding Follow instructions in the proper order For your safety turn off electrical power supply at service panel and allow unit to cool before p...

Page 2: ...wires through the wire ways of the Prestige boiler and along the Prestige factory wiring Strip the wire ends and connect to the AM 4 terminals X2 1 and X2 2 for the 0 10 vdc analog signal and X1 1 and X1 2 for the alarm as shown in Figure 1 Use the cable clamps pro vided in the AM 4 kit to secure the incoming wires to the module Ensure the polarity of the wire connections from the Boiler Controlle...

Page 3: ...ule operational parameter settings reference the Prestige Control Supplement Program Access To enter the parameter listing of the MCBA control the installer must enter the activation code as fol lows 1 Press and hold the MODE button 2 Continue holding the MODE and press STEP button until STBY appears and hold both STEP and MODE buttons for 2 to 3 seconds The display should read CODE 3 Release the ...

Page 4: ...hange the value of the display Press the STORE button once to save the change If a parameter setting is changed from the factory default and the STORE button is not pressed to save the setting the MCBA mod ule will automatically store the setting after 15 minutes Ensure all parameters settings are either factory default or revised based on the application Review all parameters set tings on page 10...

Page 5: ...ing listed below and press STORE to save the set ting Test Verify Boiler and Control Operation 1 Refer to and follow the instructions given in the Prestige Installation manual to test operation of the boiler and the MCBA control To initiate any calls for heat during the test you will have to operate the external boiler controller 2 Verify the boiler modulates correctly by adjust ing the external b...

Page 6: ... to use the wire tool to remove the jumper from the terminal block 2 Restore power to the boiler initiate a demand and allow the boiler to proceed through its start up sequence 3 The Prestige MCBA control module should enter a hard lockout causing the alarm contacts on the AM 4 to close The remote alarm should then be activated 4 Disconnect the power supplied to the boiler and replace the jumper a...

Reviews: