background image

Prestige SOLO 155/175/250 - ACVMax Boilers 

Natural to Propane Instructions  

2

1.0 Installation of the Propane Orifice

1.   Turn off the electrical power supply to the boiler.

2.   Close the manual gas shut off valve to the unit.

3.   Remove  the  front  panel  of  the  Prestige  by

removing the screws along the bottom edge of

the unit.  Pull the bottom of the panel forward

and then lift up to remove the front panel from

the unit.

4.   Remove  the  air  inlet  elbow  from  the  venturi

using a twist and pull motion.

5.  Disconnect  the  gas  supply  piping  inside  the

Prestige  enclosure  at  the  brass  union  located

just below the gas valve.

6.   Remove Molex plug from gas valve.

7.   Remove  the  two  T-25  Torx  head  screws  used  to

mount the venturi / gas valve assembly to the blow-

er.  Do not discard the screws.  Dismount the venturi

/ gas valve assembly from the blower.  See Fig. 1.

There  is  a  gasket  between  the  venturi  and  the

blower housing.  This gasket must be reinstalled

when the venturi is mounted back onto the blow-

er.  Use care not to damage the gasket.

8.   Using  a  T-25  Torx  wrench  remove  the  three

mounting screws  attaching the gas valve to the

venturi.  Note the orientation of the gas valve to

the  venturi  for  reference  later  when  the  gas

valve is reassembled to the venturi.

9.   Install  the  appropriate  brass  propane  orifice

from  Table  1  in  the  gasket  between  the  gas

valve and the venturi.  The black rubber gasket

must remain attached to the gas valve. See Fig.

2.

NOTICE

1

3

3

2

1.   Gas Valve

2.   Venturi

3.   T-25  Torx  Head  Screws  Attaching  Gas

Valve/Venturi to Blower Housing

Fig. 1:  Prestige Burner Assembly

3

2

1

Fig. 2:     Venturi/Gas Valve Assembly

1.   T-25 Torx Head Screws Attaching Venturi to

Gas Valve

2.   Brass Orifice

3.   Rubber Gasket