An adequate CH load must be present to dis-

sipate the heat generated during the combus-

tion test.  If an adequate CH load is not avail-

able an indirect water heater can be used to

dissipate  the  heat  by  creating  a  DHW  call

which will enable the DHW circulator.

6.  Press the 

RIGHT

button to adjust the firing rate

to 100% (high fire).  Hold down the  

RIGHT

button to rapidly increase the firing rate.

7.   If  the  combustion  levels  during  high  fire  are

outside  the  recommended  combustion  settings

adjust  the  THROTTLE  SCREW  (see  Fig.  5)

using a flat-blade screwdriver as follows:

Counter-clockwise  adjustment  of  the  THROT-

TLE SCREW at High Fire (100% firing rate):

            O2 decreases and CO2 increases

Clockwise  adjustment  of  the  THROTTLE

SCREW at High Fire (100% firing rate):

            O2 increases and CO2 decreases
8.   Once  the  combustion  level  is  set  at  high  fire,

manually place the boiler into low fire mode by

pressing the 

LEFT

button to adjust firing rate

down to 1% (low fire) to verify low fire com-

bustion settings.

9.   If  the  combustion  levels  (O2 &  CO2)  during

low fire are outside the recommended combus-

tion settings in Table 2, contact Triangle Tube

Technical Support Department for assistance.

10. Press the 

OK

button while the fan icon is high-

lighted to shutdown the burner.

11. Press the 

LEFT

or 

RIGHT

button to highlight

the  home  screen  icon

to  exit  the  service

mode.

NOTICE

Prestige SOLO 155/175/250 - ACVMax Boilers 

Natural to Propane Instructions  

5

1

Fig. 5: Combustion Adjustment - Prestige Burner

1.   Throttle Screw

2016-1 Prestige ACVMax 250 NG to LP

Revised Date: 2/26/2016