Prestige SOLO 155/175/250 - ACVMax Boilers
Natural to Propane Instructions
4
2.0 Combustion Test and Adjustments
1. The installer MUST perform a complete com-
bustion check to ensure the following combus-
tion levels in Table 2 are met at high and low
input firing rates and the burner is operating at
optimum conditions.
Table 2: Recommended Propane Combustion Settings
The combustion testing and adjustments
must be performed by a qualified installer,
service agency or the gas supplier. All com-
bustion measurements must be performed
with calibrated equipment to ensure proper
readings and accuracy.
Failure to perform a complete combustion
test at both high and low input rates may
result in incomplete combustion and the pro-
duction of carbon monoxide, which can
result in substantial property damage, seri-
ous injury, or death.
The combustion levels should be measured at
high firing rate. If the combustion levels are
not within the range given in Table 2 for Low
Fire after adjusting High Fire, shut the boiler
down and contact Triangle Tube Technical
Support Department. Failure to comply
with this requirement can result in substan-
tial property damage, serious injury, or
death.
The gas valve outlet pressure is factory set to the
correct value and does not require field adjust-
ment or measurement. Measurement or adjust-
ments could result in damage to the gas valve
and can result in substantial property damage,
serious injury, or death.
2. Press the round INSTALLER button. See Fig.
3.
3. Enter the installer access code “054” by using
the
LEFT
and
RIGHT
buttons to select a digit
and the
UP
and
DOWN
buttons to change the
digit. Press the
OK
button to enter the access
code.
4. Press the
RIGHT
button to highlight the
Manual Operation icon
then press the
OK
button.
5. Press the
OK
button while the FAN icon is
highlighted to manually fire the burner and
power the CH1 circulator (see Fig. 4)
WARNING
WARNING
WARNING
WARNING
DHW Demand
Target = 186°F
Installer Button
Fig. 3: ACVMax Navigation Buttons
Manual Operation
Released
Off
Off
Off
CH1
FAN
DHW
CH2
Fig. 4: ACVMax Manual Operation
Hi
gh
Fi
re
CO2 Range
10.7 to 12.0%
CO2 Target
11.0%
O2 Range
2.7 to 4.7%
O2 Target
4.2%
Lo
w
Fi
re
CO2 Range
0.5 to 0.6%
Lower than H.F. CO2
O2 Range
0.8 to 0.9%
Higher than H.F. O2
CO Max
150 ppm