Prestige SOLO 155/175/250 - ACVMax Boilers 

Natural to Propane Instructions  

4

2.0 Combustion Test and Adjustments

1.   The installer MUST perform a complete com-

bustion check to ensure the following combus-

tion levels in Table 2 are met at high and low

input firing rates and the burner is operating at

optimum conditions.

Table 2: Recommended Propane Combustion Settings

The  combustion  testing  and  adjustments

must  be  performed  by  a  qualified  installer,

service agency or the gas supplier.  All com-

bustion  measurements  must  be  performed

with calibrated equipment to ensure proper

readings and accuracy.

Failure  to  perform  a  complete  combustion

test  at  both  high  and  low  input  rates  may

result in incomplete combustion and the pro-

duction  of  carbon  monoxide,  which  can

result in substantial property damage, seri-

ous injury, or death.

The combustion levels should be measured at

high firing rate.  If the combustion levels are

not within the range given in Table 2 for Low

Fire after adjusting High Fire, shut the boiler

down  and  contact  Triangle  Tube  Technical

Support  Department.    Failure  to  comply

with this requirement can result in substan-

tial  property  damage,  serious  injury,  or

death.

The gas valve outlet pressure is factory set to the

correct value and does not require field adjust-

ment or measurement.  Measurement or adjust-

ments  could  result  in  damage  to  the  gas  valve

and can result in substantial property damage,

serious injury, or death.

2. Press the round INSTALLER button.  See Fig.

3.

3.  Enter the installer access code “054” by using

the 

LEFT

and 

RIGHT

buttons to select a digit

and the 

UP

and 

DOWN

buttons to change the

digit.  Press the 

OK

button to enter the access

code.

4. Press  the 

RIGHT

button  to  highlight  the

Manual Operation icon

then press the 

OK

button.

5.   Press  the 

OK

button  while  the  FAN  icon  is

highlighted  to  manually  fire  the  burner  and

power the CH1 circulator (see Fig. 4)

WARNING

WARNING

WARNING

WARNING

DHW Demand

Target = 186°F

Installer Button

Fig. 3: ACVMax Navigation Buttons

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

 

 

 

Fig. 4: ACVMax Manual Operation

Hi

gh

 Fi

re

CO2 Range

10.7 to 12.0%

CO2 Target

11.0%

O2 Range

2.7 to 4.7%

O2 Target

4.2%

Lo

w

 Fi

re

CO2 Range

0.5 to 0.6% 

Lower than H.F. CO2

O2 Range

0.8 to 0.9% 

Higher than H.F. O2

CO Max

150 ppm