FAULT FINDING  

(Continued)

FAULT

POSSIBLE CAUSE

ACTION

FIRE OUT

Chimney blockage continued.

To start boiler, push the Safety Switch reset

button and re-light fire if necessary.

(See Fig 2.)

Note:

If a flue blockage is not found, the

Safety Switch may have operated as a 

result of persistent downdraught.  If this is 

the case, an anti-downdraught cowl should

be fitted to the top of the chimney such as 

an ‘OH’ pot or similar, or extend the chimney

height above the pressure zone.

FAILURE TO REACH

Continuous fan blowing

Check that system is not in excess of boiler

THERMOSTAT SETTING

output.

Blockage in hopper.

Empty hopper and remove obstruction.

Clinker and ash build up in fire box.

Declinker firebed and if necessary re-light

boiler.

Fan runner blades choked.

Remove and clean.

Air control flap not opening

Remove fan and clean flap to ensure free  

to “blast” setting.

operation.

BLOW BACK

Delayed ignition of flue gases.

Always recover fire to a bright condition as 

quickly as possible after clinkering.

Incorrect declinkering

Ensure fire is recovered by turning on fan

for a few minutes both before and after

declinkering.

Over declinkering

Do not declinker more than two strokes at 

any declinkering operation.

Hopper allowed to empty below fuel regulator

plate and then re-filled. Always keep hopper

topped up and never let fuel fall below fuel

regulator plate.

EXCESSIVE

No system controls.

Fit time-switch and room stat. to control

FUEL CONSUMPTION

heating pump for specific periods of the day.

Also fit thermostat radiator valves or zone

valves controlled by room stats..

Boiler thermostat sensing phial

Stop cause of draught and ensure stat. phial  

chilled by a cold draught causing

is thermally insulated by the fibre glass

stat, to keep fan running.

blanket inside boiler casing.

Firebed partly choked with ash

Declinker firebed several times until live fire

and clinker causing fan to blow

is seen at front of bed. Also remove any

continuously in an attempt to

large clinkers that may have built-up at 

reach stat. setting.

either side of fire-bed. Remember the more

fuel in combustion the quicker the fan is shut

off by the thermostat.

13

 

 

 

 

 

 

Summary of Contents for TRG 45

Page 1: ...SOLID FUEL CENTRAL HEATING BOILERS To be retained by householder TRIANCO TRG Range MKII Gravity Feed Forced Draught Boilers EMC 89 336 EEC USER INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS ...

Page 2: ... necessary personal protective clothing or equipment is worn appropriate to parts that could be considered as being hazardous to health and safety The installer should be aware of his responsibilities under the Act and provide where necessary appropriate protection for persons carrying out the installation INSULATION AND SEALS Glass Rope Mineral Wool Insulation Pads Ceramic Fibre Glass Insulation ...

Page 3: ...CONTENTS PAGE 1 USER INSTRUCTIONS 1 2 2 OPERATING DETAILS 3 3 TECHNICAL INFORMATION 4 4 INSTALLATION INSTRUCTIONS 5 6 7 5 SERVICING 8 6 SPARES 9 7 FAULT FINDING 12 13 ...

Page 4: ...l be made for parts and or labour providing An appliance fault is found and the appliance has been installed and commissioned within the past 12 months Reasonable evidence of this must be supplied on request A charge will be made where Our Service Engineer finds no fault with the appliance see note below or The cause of a breakdown is due to other parts of the plumbing heating system including sub...

Page 5: ...lator is located at the back of the hopper to control the depth of firebed Adjustment is provided by means of holes which engage over a hanger peg to suit the fuel being burned The following settings must be used 1 Fuel Regulator Settings Top hole Anthracite Grains 2nd hole from top Anthracite Beans Note Do not allow fuel level in hopper to fall below fuel regulator plate Declinkering Under averag...

Page 6: ...that the boiler is full of water and all valves are open 2 Switch on electrical supply to boiler 3 Ensure that the fuel regulator is correctly positioned to suit the fuel being used and fill hopper see under Fuel Regulator Settings 4 Thoroughly warm the chimney by lighting two or three wax firelighters in the boiler flue outlet 5 After warming the chimney insert three wax fire lighters in the midd...

Page 7: ...2 OPERATING DETAILS 3 TRG 80 TRG 45 60 ...

Page 8: ...in 5 5 5 Maximum Working head 15 8m 52ft Thermostat Adjustable between 55 C and 82 C in six settings Casing White stove enamel with two tone grey facia Insulation Glass fibre lining in side panels Draught Stabiliser Integral part of boiler Based on 160 Btu h sq ft 100 F difference An allowance of 8 000 Btu h has been made for domestic hot water NOTE THE BOILER MUST HAVE A CONTINUOUS ELECTRICAL SUP...

Page 9: ... acceptable temperature at the taps IMPORTANT SAFETY NOTES Read these instructions before installing your boiler IMPORTANT ISOLATE ELECTRICAL SUPPLY TO THE BOILER BEFORE CARRYING OUT ANY WORK The mains supply plug is the primary disconnect device and must be readily accessible during normal use To maintain the boiler s high thermal efficiency and reliable operation it should be serviced annually b...

Page 10: ... there is no means of dissipating the residual heat by way of a hot water cylinder or heat leak radiator then a pump overrun stat must be fitted to the boiler flow pipe Air Supply Adequate ventilation is required to ensure that sufficient air is available for combustion The room in which the boiler is installed must be provided with a permanent fresh air opening of not less than the following 148c...

Page 11: ...ed from a switched plug 5 amp fuse to the mains terminal block under thermostat cover Pass cable along bottom of boiler and through bush in left handside Check operation of forced draught fan by turning on thermostat also ensure that the air control flap pivots freely in fan throat 4 Position the fuel regulator on the appropriate hole to suit the fuel being used see Operating Instructions for sett...

Page 12: ...ce should be carried out as soon as possible after the end of the heating season Boiler Flue Cleaning To maintain the high thermal efficiency of the boiler and to avoid the possibility of DANGEROUS GASES being emitted it is necessary to keep the internal flue ways clear by scraping off deposits at regular intervals weekly in Winter and according to usage in Summer Important Always ensure the speci...

Page 13: ...BOILER BODY ASSEMBLY TRG 80 BOILER BODY ASSEMBLY TRG 45 60 9 6 SPARES ...

Page 14: ...ulator 37056 37272 37590 1 28 Hopper Lid Assembly 36571 36671 37570 1 30 Seal 98178 98178 98178 1 61 Clinker Tray Assembly 36505 36705 37720 1 62 Flue Scraper 38500 38500 38500 1 65 Seal 98178 98178 98178 1 81 Fan Unit 37134 37134 35534 1 86 Thermostat Ranco 206896 206896 206896 1 93 Thermostat Control Cover Assembly 36566 36641 36145 1 98 Blocked Flue Stat 45651 45651 45651 1 10 ...

Page 15: ...92 1 21 TOP ASSEMBLY 37770 1 23 LATCH SPIRE SCO2130 95190 95190 95190 4 FRONT REAR PANEL ASSEMBLY 36581 36681 24 REAR PANEL 36582 36682 25 FRONT PANEL 36586 36686 36686 26 L H HINGE BRACKET ASSEMBLY 36584 36584 27 R H HINGE BRACKET ASSEMBLY 36585 36584 11 LATCH FASTEX ITW 95163 95163 95163 1 16 STUD SPIRE No 5 BV2141 17 95191 95191 95191 4 17 WASHER SHAKEPROOF 4BA92211 92211 92211 92211 4 18 SCREW...

Page 16: ...k seal and replace if necessary Fire door not sealing Check seal and replace if necessary FIRE OUT Insufficient Idling Air Screw in Idling Screw one or two turns to increase air supply Firebed choked with clinker and ash Declinker firebed until fresh fuel is seen and re light Insufficient draught Clean boiler flue ways and sweep chimney Ensure that draught stabiliser closes when draught is low Wet...

Page 17: ...s possible after clinkering Incorrect declinkering Ensure fire is recovered by turning on fan for a few minutes both before and after declinkering Over declinkering Do not declinker more than two strokes at any declinkering operation Hopper allowed to empty below fuel regulator plate and then re filled Always keep hopper topped up and never let fuel fall below fuel regulator plate EXCESSIVE No sys...

Page 18: ...opyright in this brochure and the drawings or illustrations contained in it is vested in Trianco Limited and neither the brochure or any part thereof may be reproduced without prior written consent Trianco Limited s policy is one of continuous research and development This may necessitate alterations to this specification By appointment to H M Queen Elizabeth The Queen Mother Manufacturers of Dome...

Reviews: